| Sl No | Description | Qty | Unit | PNEUMATIC ENGINEERS PVT LTD. L4 | FAVOURITE ELECTRICALS L1 | M/S STAR NEOTECH ENGINEERS L3 | Chill Point Engineers Pvt Ltd L2 |
|---|---|---|---|---|---|---|---|
| 1.00INSULATED HOT / CHILLED WATER PIPING (EXPANDED POLYSTRENE INSULATION). Supplying, laying/ fixing, testing and commissioning offollowing nominal sizes of Hot / chilled water piping plumbing inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with fire retardant quality expanded polystrene moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date ) at joints repairing of damage to building etc. as per specifications and as required complete in all respect. Note : The Pipes of sizes 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. | |||||||
| 1.10 | 200mm dia.(75mm insulation) | 50 | Rmt | 6,500 ₹3,25,000 | 6,447 ₹3,22,350 Lowest | 7,000 ₹3,50,000 | 7,000 ₹3,50,000 |
| 1.20 | 150mm dia.(75mm insulation) | 50 | Rmt | 6,000 ₹3,00,000 | 4,822 ₹2,41,100 Lowest | 5,000 ₹2,50,000 | 5,000 ₹2,50,000 |
| 1.30 | 125mm dia.(50mm insulation) | 10 | Rmt | 5,500 ₹55,000 | 3,684 ₹36,840 Lowest | 4,000 ₹40,000 | 4,000 ₹40,000 |
| 1.40 | 100mm dia. (50mm insulation) | 100 | Rmt | 4,000 ₹4,00,000 | 3,100 ₹3,10,000 | 3,000 ₹3,00,000 Lowest | 3,000 ₹3,00,000 Lowest |
| 1.50 | 80mm dia. (50mm insulation) | 100 | Rmt | 2,000 ₹2,00,000 Lowest | 2,460 ₹2,46,000 | 2,500 ₹2,50,000 | 2,000 ₹2,00,000 Lowest |
| 1.60 | 65mm dia.(50mm insulation) | 200 | Rmt | 1,800 ₹3,60,000 Lowest | 2,095 ₹4,19,000 | 2,400 ₹4,80,000 | 2,000 ₹4,00,000 |
| 1.70 | 50mm dia.(50mm insulation) | 300 | Rmt | 1,500 ₹4,50,000 Lowest | 1,760 ₹5,28,000 | 2,000 ₹6,00,000 | 1,500 ₹4,50,000 Lowest |
| 1.80 | 40mm dia.(50mm insulation) | 60 | Rmt | 1,200 ₹72,000 | 1,463 ₹87,780 | 1,750 ₹1,05,000 | 1,000 ₹60,000 Lowest |
| 1.90 | 32mm dia.(50mm insulation) | 50 | Rmt | 1,000 ₹50,000 | 1,322 ₹66,100 | 1,400 ₹70,000 | 900 ₹45,000 Lowest |
Tender Value
₹5.6 Cr
EMD Value
₹11.3 L
Closing Date
28 Nov 2022, 3:00 pmClosed
Executive Engineer Mech
SKIMS Soura
Design, supply, installation, testing and commissioning of HVAC system (Low Side Works) to 250 Bedded New IPD Block at SKIMS MCH Bemina, Srinagar
2022_SKIMS_193072_1
e-NIT NO 108 of 2022-23 dt 27-10-2022
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
180 days
SKIMS MCH Bemina
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,500
As Described in SBD
₹11.3 L
Office of the Superintending Engineer Mech
13 Dec 2022
31 Oct 2022
29 Nov 2022
31 Oct 2022
28 Nov 2022
31 Oct 2022
15 Nov 2022
Amount
INSULATED HOT / CHILLED WATER PIPING (EXPANDED POLYSTRENE INSULATION). Supplying, laying/ fixing, testing and commissioning offollowing nominal sizes of Hot / chilled water piping plumbing inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with fire retardant quality expanded polystrene moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date ) at joints repairing of damage to building etc. as per specifications and as required complete in all respect. Note : The Pipes of sizes 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
200mm dia.(75mm insulation)
150mm dia.(75mm insulation)
125mm dia.(50mm insulation)
100mm dia. (50mm insulation)
80mm dia. (50mm insulation)
65mm dia.(50mm insulation)
50mm dia.(50mm insulation)
40mm dia.(50mm insulation)
32mm dia.(50mm insulation)
INUSLATED VALVE. Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified
100 mm dia
80 mm dia
65 mm dia
50 mm dia
40 mm dia
Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.
50 mm dia
40 mm dia
Providing and fixing in position the industrial type pressure gauge complete as required
Providing & fixing in position the mercury in glass industrial type thermometer complete as required
AIR DISTRIBUTION DUCT (FOR VENTILATION) Supply, installation, balancing and commissioning of factory/site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
0.63 MM (24 gauge) Galvanized Sheet Steel Ducting
0.80 MM (22 gauge) Galvanized Sheet Steel Ducting
1.0 MM (20 gauge) Galvanized Sheet Steel Ducting
1.25 MM (18 gauge) Galvanized Sheet Steel Ducting
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.
SUPPLY / RETURN AIR DIFFUSERS Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
SUPPLY / RETURN AIR GRILLES Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
FIRE DAMPERS. Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
Fire damper
Actuator
AIR HANDLING UNITS. Supply, installation, testing and commissioning of double skin modular construction, draw through Floor Mounted Air Handling Units of 0.6 mm thick Plain GSS Sheet from inside & 0.8 mm thick Preplasticized GSS Sheet from Outside with 40-50 mm thick puf insulation in between them. AHU Shall be complete with DIDW Centrifugal fan (plugfan/belt driven), Squirrel cage induction motor,straters (For AHUs Below 3 HP rating), cooling / heating coil (Copper tubes and Aluminium fins), pre-filter (Washable Synthetic fibre of efficiency 90% down to 10 micron), drain pan, V belt drive, fireproof double canvass connection and other accessories as per specifications (except water shut off valves, drain piping, Thermometer and pressure gauges which are covered under separate item). Motor shall be suitable for 415 ± 10% volts, 50 cycle, 3 Phase AC supply as indicated below.
First to sixth Floor,Corridor, wards & other rooms, 10000 CFM (FM) AHU, 46.0 KW heating capacity, 4 row deep heating coil, 50 mm Static Pressure with 7.5 HP/ 3 Phase motor
First to sixth Floor,Corridor, wards, & other rooms, 8000 CFM (FM) AHU, 37.0 KW heating capacity, 4 row deep heating coil, 50 mm Static Pressure with 7.5 HP/ 3 Phase motor
First Floor,Waiting Area & Corridor, 6000 CFM AHU, 27.5 KW heating capacity, 4 row deep heating coil, 40 mm Static Pressure with 5.0 HP/ 3 Phase motor (Ceiling Suspended)
Supply Installation testing and commissioning of Fan Coil units (Ceiling suspended/ Hi Wall) with fan motor, cooling coil, filter plenum with plenum supports etc as per specs and drawings
1200 CFM (3.0 TR)
1000 CFM (2.5 TR)
800 CFM (2.0 TR)
600 CFM (1.5 TR)
400 CFM (1.0 TR)
Supply Installation testing and commissioning of controls for Fan Coil units complete with pressure independent balancing valve, control wiring, etc
Variable Frequency Drive (VFD) with transducers, control wiring etc. as per specifications and drawings. (For AHUs above 2 HP ratings)
AXIAL FLOW FANS. Supply, installation, testing and commissioning of direct driven Axial Flow Fans as shown in drawings and as per specifications. Each fan shall be complete with totally enclosed fan cooled motor (IP:55), motor mount and vibration isolators.Quoted price shall include starters, control cables . Fan motor shall be suitable for 3 Phase, 415 +/- 10% V, 50 Hz AC supply.(Motor speed shall not exceed 900 rpm)
Duty : Floor Smoke Extraction (First Floor) Air Quantity : 12,000 CFM Static Pressure : 20 mm wg Motor Rating : 7.5 HP (Suggested)
Duty : Make Up Air Supply (First Floor) Air Quantity : 10,000 CFM Static Pressure : 20 mm wg Motor Rating : 5.0 HP (Suggested)
Duty : Floor Smoke Extraction (Second to Sixth Floor) Air Quantity : 7,000 CFM Static Pressure : 20 mm wg Motor Rating : 3.0 HP (Suggested)
Duty : Make Up Air Supply (Second to Sixth Floor) Air Quantity : 6,000 CFM Static Pressure : 20 mm wg Motor Rating : 3.0 HP (Suggested)
INLINE FANS. Supply, installation, testing and commissioning of inline ducted Fans as shown in drawings. Fan motor shall be suitable for single phase, 50 Hz AC supply. The capacity of the fan given as under:-
Air Quantity : 900 CFM Static Pressure : 20 mm wg Motor rating : 500 Watt Location : Stilt to Terrace Floor
Air Quantity : 700 CFM Static Pressure : 20 mm wg Motor rating : 500 Watt Location : Sixth & Terrace Floor
Air Quantity : 350 CFM Static Pressure : 20 mm wg Motor rating : 250 Watt Location : First to Terrace Floor
Air Quantity : 100 CFM Static Pressure : 5 mm wg Motor rating : 60 Watt Location : First to Sixth Floor
FAN SECTIONS. Supply, Installation, Testing and commissioning of single skin Fan Section as shown in drawing and as per specifications. Each unit shall be complete with casing (16G) DIDW centrifugal fan, belt drive, motor, starters, control cables, louvers etc. Fan motor shall be suitable for 3 Phase, 415 ± 10% V, 50 Hz AC supply.
Duty: Lift Well Pressurisation Air Quantity : 36,000 CFM Static Pressure : 40 mm wg Motor Rating : 20.0 HP Location : Terrace Floor
Duty: Lift Lobby Pressurisation Air Quantity : 16,000 CFM Static Pressure : 40 mm wg Motor Rating : 10.0 HP Location : Terrace Floor
Duty: Lift Lobby Pressurisation Air Quantity : 12,500 CFM Static Pressure : 40 mm wg Motor Rating : 10.0 HP Location : Terrace Floor
Duty: Pantry Exhaust Air Quantity : 2500 CFM Static Pressure : 40 mm wg Motor Rating : 3.0 HP Location : Terrace Floor
Duty: Pantry Exhaust Air Quantity : 2000 CFM Static Pressure : 40 mm wg Motor Rating : 2.0 HP Location : Terrace Floor
Supply, installation, testing and commissioning of cooling thermostats for various Air Handling Units and Fan Coil Units as per specifications including all accessaries ,mountings,wiring between thermostat & unit, terminations etc.
Proportional thermostats for Air Handling Units
Snap acting thermostat for FCU
Supply,Installation Testing and Commissioning of PICB Valves with electronic,modulating,2 way control device,adjustable to 51 different setting within the range of valve size.
48-35 USGPM
32-17 USGPM
Providing and fixing in position the following ball valves with strainer duly insulataed as per specifications and drawings
32 mm dia
25 mm dia
Providing and fixing in position the following ball valves without strainer duly insulataed as per specifications and drawings
32 mm dia
25 mm dia
Providing and fixing in position the following Drain Valves (For Drain) duly insulataed as per specifications and drawings
32 mm dia
25 mm dia
Providing and fixing in position the following Purge Valves duly insulataed as per specifications and drawings
32 mm dia
25 mm dia
DRIAN PIPE Providing and fixing in position the following GI medium class cut to required length and installed with screw joints including the necessary fittings (bends, tees, unions, sockets etc) duly insulated with 25 mm thick TF quality thermocole pipe section as per specifications.
32 mm dia
25 mm dia
AIR DISTRIBUTION DUCT (FOR AIRCONDITIONING) Supply, installation, balancing and commissioning of factory/site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
0.63 MM (24 gauge) Galvanized Sheet Steel Ducting
0.80 MM (22 gauge) Galvanized Sheet Steel Ducting
Supplying and fixing of 19 mm thick duly laminated aluminium foil of mat finish closed cell nitrile rubber (Class O) insulation on existing duct after applying suitable adhesive for nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation. Complete as per specs and as required
Supply, installation, testing and commissioning of extruded aluminium powder coated linear grills of approved shade and make as per specifications including any framework required for fixing of linear grilles.
150 mm wide Linear Grilles
200 mm wide Linear Grilles
Supply, installation, testing and commissioning of volume control damper of Anodised Aluminum material for Linear grills.
Supply, installation and balancing of extruded aluminium powder coated air louvers complete with aluminium wire mesh birdscreen & volume conrtol dampers as per specifications.
Fresh air louvers
Exhaust air louvers(without volume control dampers)
ACOUSTICS
Supply and fixing of Acoustic lining supply air duct and plenum with 25 mm thick resing bonded glass wool of density 32 Kg/ m3 with 25 mm x 25 mm GI Section of 1.25 mm thick at 600 mm centre to centre covered with reinforced plastic tissue paper and 0.5 mm thick perforated aluminum sheets fixed to inside of the ducts with cadmium plated nuts, bolts, stick pins, CPRX compound. Complete as required
Supply and fixing of Acoustic lining on Walls/Ceiling of AHU Rooms with 50 mm thick resing bonded glass wool of density 32 Kg/ m3 with friction fixed in 610mm x 610mm frame work made of 25x50x50x50x25 mm mafe out of 0.6 mm thich GI sheetU Shaped Channel covered with reinforced fiber glass tissue and finshed with 0.8 mm perforated aluminum sheets. Complete as required
SITC of thermal insulated flexible duct duly supported at regular intervals as per site requirement. Complete. 200 mm
Chill Point Engineers Pvt Ltd
M/S STAR NEOTECH ENGINEERS
PNEUMATIC ENGINEERS PVT LTD.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.22 MB
BOQ_506898.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .