Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.2 LAccepted-AOC | L1 | Accepted-AOC Lowest Bid Value | |
| 2 | L2₹29.2 L+₹44,454 (1.55%)Rejected-AOC | L2 | Rejected-AOC Higher Bid Value | |
| 3 | L3₹36.0 L+₹7.2 L (25.2%)Rejected-AOC NO 12 5TH B CROSS SHARADAMBA NAGAR M E S ROAD BANGALORE 560013 | BANGALORE | BANGALORE | KARNATAKA | 560013 | L3 | Rejected-AOC Higher Bid Value | |
| 4 | L4₹36.4 L+₹7.7 L (26.8%)Rejected-AOC | L4 | Rejected-AOC Higher Bid Value | |
| 5 | L5₹41.6 L+₹12.9 L (44.8%)Rejected-AOC | L5 | Rejected-AOC Higher Bid Value |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
2 Jun 2021, 6:00 pmClosed
GE (AF) BANGALORE
GE (AF) BANGALORE, HQ TC AIR FORCE , BANGALORE 560006
REPAIRS / MAINTENANCE TO LT PANEL INCLUDING MCCBs / LT CABLES / SWITHCH GEARS AND CONNECTED WORKS AT POCKET I AND II AT CHAF BANGALORE
2021_MES_442010_1
8776/GE/16
Open Tender
Civil Works
Item Rate
270 days
CH (AF) BANGALORE
as per NIT
5 documents required · 5 mandatory
₹500
Yes
GE (AF) BANGALORE
₹90,000
Yes
7 Sept 2021
11 May 2021
4 Jun 2021
11 May 2021
2 Jun 2021
28 May 2021
12 May 2021 - 25 May 2021
Amount
Excavation in trenches not exc. 1.5m wide and not exc 1.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying of cables, and pipes Etc. and getting out in soft /Loose soil, complete all as specified and directed.
Returning filling in, including spreading, levelling, watering and well ramming in layer not exc 25cm, complete all as specified and directed.
Removal of surplus soil (excavated soil) to a distance not exceeding 50m and depositing where directed at a level not exc 1.5m above the starting point, complete all as specified and directed.
Sand cushioning with fine sand as specified in clause 14.5 of SSR Part-I to under ground cable in trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable as specified in clause 19.75 of SSR Part-I, complete all as specified and directed.
Burnt bricks, sub class 'B' of designation 75, standard size laid in trenches as in protection of UG cables, complete all as specified and directed.
GI tubing light grade 50 mm bore as in cable protection fixed to poles/walls or laid intrenches/under road crossing etc. including taking up or down old unserviceable steel tubing and connections of any size, complete all as specified and directed.
All as per Srl Item No 06 but for 80 mm bore of pipe, complete all as specified and directed.
Boring of holes under road pavement hard standing by manual boring incl making good the disturbed surfaces, complete all as specified and directed.
LT UG cable 4 core x 16 sq mm 1100 Volts grade XLPE insulated , armored, heavy duty with aluminium conductor laid in trenches or fixed to walls/ poles or passing through pipes with and including,cable gland lugs/ thimbles/ ferrules including connecting, testing and commissioning including taking down existing LT UG cable of any size at site, complete all as specified and directed. Make : Havells/Polycab/Universal Notes: (a) Excavation earth work and sand cushioning brick protectionand connected work etc. Shall be measured and paid separately under relevant item of schedule (b) Rate quoted deemed to include for cutting and removing of defective joints where required as directed.
All as per Srl Item No 09 but for 3.5 core x 25 Sqmm, complete all as specified and directed.
All as per Srl Item No 09 but for 3.5 core x 35 Sqmm, complete all as specified and directed.
All as per Srl Item No 09 but for 3.5 core x 50 Sqmm, complete all as specified and directed.
All as per Srl Item No 09 but for 3.5 core x 70 Sqmm, complete all as specified and directed.
All as per Srl Item No 09 but for 3.5 core x 95 Sqmm, complete all as specified and directed.
All as per Srl Item No 09 but for 3.5 core x 120 Sqmm, complete all as specified and directed.
All as per Srl Item No 09 but for 3.5 core x 240 Sqmm, complete all as specified and directed.
1100 volts grade heavy duty cable with PVC insulated aluminium stranded conductor served with an inner sheathing of PVC tape unarmoured with galvanised steel wire or tape and overall PVC sheathed 10 sq.mm , 2 core nominal cross section in service connections including taking down of old unserviceable cable of any size, complete all as specified and directed. Make : Havells/Polycab/Universal
1100 volts grade heavy duty cable with PVC insulated aluminium stranded conductor served with an inner sheathing of PVC tape unarmoured with galvanised steel wire or tape and overall PVC sheathed 10 sq.mm , 4 core nominal cross section in service connections including taking down of old unserviceable cable of any size, complete all as specified and directed. Make : Havells/Polycab/Universal
Straight through joints heat shrink type suitable for 10 to 16 Sq. mm. x 3.5/4 core sizes of PVC/XLPE insulated and PVC sheathed armoured LT underground cable with aluminium conductors including joint kits and labour for making joints including taking down of old unserviceable joint, complete all as specified and directed. Make : Denson/3M
All as per Srl Item No 19 but for 25 to 50 Sq. mm. x 3.5/4 core, complete all as specified and directed.
All as per Srl Item No 19 but for 70 to 150 Sq. mm. x 3.5/4 core, complete all as specified and directed.
All as per Srl Item No 19 but for 240 to 300 Sq. mm. x 3.5/4 core, complete all as specified and directed.
Al cable lugs of size 16 Sqmm including taking down of old unserviceable Al cable lugs of any type and size, complete all as specified and directed. as specified
All as per Srl item No 23 but for size 25 Sq. mm, complete all as specified and directed.
All as per Srl item No 23 but for size 35 Sq. mm, complete all as specified and directed.
All as per Srl item No 23 but for size 50 Sq. mm, complete all as specified and directed.
All as per Srl item No 23 but for size 70 Sq. mm, complete all as specified and directed.
All as per Srl item No 23 but for size 95 Sq. mm, complete all as specified and directed.
All as per Srl item No 23 but for size 120 Sq. mm, complete all as specified and directed.
All as per Srl item No 23 but for size 240 Sq. mm, complete all as specified and directed.
Al IN-Line connectors of size 16 Sqmm including taking down of old Al IN-Line connectors of any type and size, complete all as specified and directed.
All as per Srl item No 31 but for size 25 Sq. mm, complete all as specified and directed.
All as per Srl item No 31 but for size 35 Sq. mm, complete all as specified and directed.
All as per Srl item No 31 but for size 50 Sq. mm, complete all as specified and directed.
All as per Srl item No 31 but for size 70 Sq. mm, complete all as specified and directed.
All as per Srl item No 31 but for size 95 Sq. mm, complete all as specified and directed.
All as per Srl item No 31 but for size 120 Sq. mm, complete all as specified and directed.
All as per Srl item No 31 but for size 240 Sq. mm, complete all as specified and directed.
MCCB, 4 pole, 415 Volts, 63 Amps, 16 KA, 50 Hz, AC, fixed thermal and fixed magnetic type in the existing LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing including taking down of old unserviceable MCCB of any size and type, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
MCCB, 4 pole, 415 Volts, 100 Amps, 16 KA, 50 Hz, AC, fixed thermal and fixed magnetic type in the existing LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing including taking down of old unserviceable MCCB of any size and type, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
MCCB, 4 poles 415 Volts, 160 Amps, 36 kA, 50 Hz, AC, adjustable type type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs and testingincluding taking down of old unserviceable MCCB of any size and type, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
MCCB, 4 poles 415 Volts, 200 Amps, 36 kA, 50 Hz, AC, adjustable type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs and testing including taking down of old unserviceable MCCB of any size and type, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
MCCB, 4 poles 415 Volts, 250 Amps, 36 kA, 50 Hz, AC, adjustable type in the existing LT panel board/sheet metal enclosure including connecting up incoming/out going cables with suitable lugs and testing including taking down of old unserviceable MCCB of any size and type, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
MCCB, 4 pole, 415 Volts, 320/350 Amps, 36 KA, 50 Hz, AC, adjustable type in the existing LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testingincluding taking down of old unserviceable MCCB of any size and type, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
Power contactor , 3/4 pole, 415 Volts, 265 Amps, 50 Hz, AC fixed in the existing ATS LT panel board including connecting up incoming/ out going cables with suitable lugs and testing including taking down of old unserviceable Power contactor of any size and type, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
Power contactor , 3/4 pole, 415 Volts, 315/330 Amps, 50 Hz, AC fixed in the existing ATS LT panel board including connecting up incoming/ out going cables with suitable lugs and testing including taking down of old unserviceable Power contactor of any size and type, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
M&L in replacment of ON LOAD change over switch with sheet metal enclosure 415V , 4 pole of capacity 250 Amps including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
ON LOAD change over switch with sheet metal enclosure, 415V , 4 pole of capacity 315/320 Amps including connecting up incoming/ out going cables with suitable lugs and testing including taking down of old unserviceable change over switch of any type and size, complete all as specified and directed. Make: HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
Sheet metal enclosure made out of 2mm thick CRCA sheet duly power coated suitable for fixing/mounting MCCB of 160A Amps 4 pole duly fixed on wall with all fixing arangements including taking down of old unserviceable Sheet metal enclosure of any type and size, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
Sheet metal enclosure made out of 2mm thick CRCA sheet duly power coated suitable for fixing/mounting MCCB of 250A Amps 4 pole duly fixed on wall with all fixing arangements including taking down of old unserviceable Sheet metal enclosure of any type and size, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
MCB TPN 63 A,'C' Curve,10KA rupturing capacity including taking down of old unserviceable MCB of any type and size, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
MCB TPN 40 A, 'C' Curve,10KA rupturing capacity including taking down of old unserviceable MCB of any type and size, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
RCCB 40 Amps TPN ,'C' Curve,10KA rupturing capacity having sensitivity 30mA including taking down of old unserviceable RCCB of any type and size, complete all as specified and directed.
RCCB 63 Amps TPN ,'C' Curve,10KA rupturing capacity having sensitivity 30mA including taking down of old unserviceable RCCB of any type and size, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
RCCB 40 Amps SPN ,'C' Curve,10KA rupturing capacity having sensitivity 30mA including taking down of old unserviceable RCCB of any type and size, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
Auto change over Switch SPN 63A in existing LT panel including testing including taking down of old unserviceable Auto change over switch of any type and size, complete all as specified and directed. Make : Havells Cat No : DHAAOSN6363 or equivalent
Cleaning, dusting and servicing LT panel ,MCCBS,Bus bars tightening cable connections, replacing of worn out parts such as busbar spout suppourts ,spacers,hinges,locks,glands and connected items/Mechanical parts etc for its smooth functioning including applying Becktrol red solution to the surface of the bus bars and spouts, applying Monoplast compound at the bus bar joints after tightening of joints ,cleaning the disturbed area beneath the LT panel and removing vegitation , derbis etc., complete all as specified and directed. (Note:- Rate quoted deemed to include for removing and replacing of defective items where required.)
Servicing of ACB 800/1200A rating by disconnect and taking out the breaker after taking power shut down of the respective panel and overhauling/ servicing the ACB by opening all parts and cleaning of electrical contacts with CTC/rust remover, lubricating electrical moving parts with petrolium jelly and mechanical moving parts with grease & applying Becktrol red solution to the surface of the bus bars and spouts, applying Monoplast compound at the bus bar joints after tightening of joints and replacing defective spare parts like springs/ bolts/ nuts/ washers etc, including testing, calibrating , refixing the circuit breaker and make fuctional, complete all as specified and directed.
Spray Painting the LT Panel complete of any capacity after preparation of surface and applying two coats of synthetic enamel (smoke grey) paint and black enamel paint on angle iron stand, replace the Danger notice plate, complete all
Danger notice plates, made out of 1.6mm thick MS sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for LT 20X15 cm size, fixed as in repairs, complete all as specified and directed.
APFC microcontroller Relays 8 steps fixed to existing APFC panel by taking down the existing un-serviceable relay, fixed as in repairs, complete all as specified and directed. Make:SELEC/HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
Capacitor duty APFC Contactor suitable to switching 20 KVAR capacitor, 3 pole , 415 V rating fixed to existing capacitor bank by taking down the existing un-serviceable contactor, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
Power factor capacitors MPPH type of 5 KVAR rating, fixed to existing capacitor bank including connecting up and testing, fixed as in repairs, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
APFC copper HD Harmonic reactor having Class 'H' insulation , low noise,low losses & high harmonic loading capability of 10 KVAR rating, 440V, fixed to existing APFC panel including taking down the existing un-serviceable Reacter and connecting up and including testing, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
APFC copper HD Harmonic reactor having Class 'H' insulation , low noise,low losses & high harmonic loading capability of 12.5 KVAR rating, fixed to existing APFC panel including taking down the existing un-serviceable Reacter and connecting up and including testing, complete all as specified and directed. Make:HAVELLS/STANDARD/INDOASIAN/L&T/SCHNIDER
Digital Multifunctional Panel meter for measuring Voltage ( 0-500V min ) ,Current , P.F , etc including necessary P.T & C.T's with all connected acccessories, fixed as in repairs, complete all as specified and directed Make : Selec/AE/Meco
Digital voltmeters 0-500V , with all connected accessories including connecting up and testing, fixed as in repairs, complete as all as specified and directed. Make : Selec/AE/Meco
Digital Ammetr 0-600A (min) , with CT's, all connected accessories including connecting up and testing, fixed as in repairs, complete as all as specified and directed. Make : Selec/AE/Meco
LED indicator lamp 240 V , with suitable colour Red/Blue/Yellow/Amber/Green and connected acccessories, fixed as in repairs, complete all as specified and directed Make : L&T/Siemens
Push button switch with NO/NC contacts 415 V ,6A , with add on Aux Contacts and connected acccessories, fixed as in repairs, complete all as specified and directed Make : L&T/Siemens
Power contactor AC coil 240V ,50Hz suitable for MNX 70 Contactor, fixed as in repairs, complete all as specified and directed. Make : L&T
Power contactor AC coil 240V ,50Hz suitable for MNX110/95/140 Contactor, fixed as in repairs, complete all as specified and directed. Make : L&T
Power contactor AC coil 240V ,50Hz suitable for MNX300/MNX400 Contactor, fixed as in repairs, complete all as specified and directed. Make : L&T
Power contactor AC coil 240V ,50Hz suitable for MCX40/25/32 Contactor, fixed as in repairs, complete all as specified and directed. Make : L&T
HBC/HRC Fuse up to 32A, fixed as in repairs, complete all as specified and directed. Make : LEGRAND/HAVELLS/L&T
HBC/HRC Fuse 40A to 125A, fixed as in repairs, complete all as specified and directed. Make : LEGRAND/HAVELLS/L&T
HBC/HRC Fuse 200A to 315A, fixed as in repairs, complete all as specified and directed. Make : LEGRAND/HAVELLS/L&T
HBC/HRC Fuse 350A to 400A, fixed as in repairs, complete all as specified and directed. Make : LEGRAND/HAVELLS/L&T
HBC/HRC Fuse 500A to 630A, fixed as in repairs, complete all as specified and directed. Make : LEGRAND/HAVELLS/L&T
Bus bar outdoor type powder coated chamber of suitable size made out of 3mm thick CRCA steel sheet and 40x5mm angle iron frame with locking arrangement including of 250A, 3 phase 4 wire, 4 way Aluminium bus bar mounted on PVC/Porcelain insulators and bus bar duly insulated with PVC sleeves in specified colour code connecting up connecting up incoming and outgoing cables completed with glands and lugs and testing including taking down old unserviceable bus bar, completed all as specified and directed.
Bus bar outdoor type powder coated chamber of suitable size made out of 3mm thick CRCA steel sheet and 40x5mm angle iron frame with locking arrangement including of 400A, 3 phase 4 wire, 6 way Aluminium bus bar mounted on PVC/Porcelain insulators and bus bar duly insulated with PVC sleeves in specified colour code connecting up connecting up incoming and outgoing cables completed with glands and lugs and testing including taking down old unserviceable bus bar, completed all as specified and directed.
Bus bar out door type, chamber of suitable size made out of 3mm thick CRCA steel sheet and 40x5mm angle iron frame with locking arrangement including provision of 800A 6 way Aluminium busbar connecting up incoming and out going cables complete with glands and lugs and testing including taking down old unserviceable bus bar, complete all as specified and directed. Note: Rate included Excavation, earth work and PCC work and complete connected work
Saftey protection relay 415 VAC, 3 Ph 4 Wire, 2 C/O with adjustable under voltage,over voltage, on delay,Neutral fail protection for lt Panel, fixed as in repairs, complete all as specified and directed. Make : L&T Cat No MAC04 D0100 or equivalent in ABB/Siemens
Repair/Reconditiong of exisitng earth pit by removing damaged Earth PCC chambers and excavate pit soil upto 25% of earth plate/electrode and adding alternate layers of charcoal, mixture of salt and copper sulphate up to 15cm above the earth plate/electrode and moist the mixture using water , cleaning/replacing of funnel with wire mesh where ever necessary , contractor should ensure that the earthing resistance should be below 5 Ohms , making good to distrubed surface, complete all as specified and directed. Note: 1. Deemed including excavation, returning filling and connected items. 2. Salt , charcoal , copper Sulphate, pit chamber , Testing will be measured and paid seperatly
Supply only pure charcoal granular/aggregate type having Ash content < 5% , stone free for earthing, complete all as specified and directed.
Supply only iodine free pure common salt crystal ( NaCl) for earthing, complete all as specified and directed.
Earth continuity conductor GI Strip 25 x 4mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for direct/loop earthing etc. or steel wire with proper PVC/Porcelain insulator etc., fixed as in repairs, complete all as specified and directed .
Replacement of old unserviceable earth pit with pre moulded cast iron eart pit with cover of size 300mm x300mm x 50mm including provision of funnel, wire mesh necessary excavation and earth work in any type of soil including paninting , marking of earth values with date, complete all as specified and directed
PVC Polymer/Porcelain insulator for existing GI/Aluminium/copper strip support, fixed as in repairs, complete all as specifed and directed
Earthing complete with galvanised steel earth plate electrode 60cm×60cm× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth strip of size 25 x 4 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 connected to earthing test point all as indicated including testing on completion and taking down old unserviceable earthing of any type and any size, complete all as specified and directed. Note : All earthing strips should be welded or brazing at each joint .
M & L for Testing of earthing resistance of existing earth pits using calibrated 3/4 wire digital Earth resistance meter and contractor is responsible to arrange calibrated earth resistance meter and also maintain earth resistance register with user signature to be submited to concerned office
M/S Bhagyawanticonstruction
Shanthi Construction
B5BUILDING SOLUTIONS
Vishwas Enterprises
RRK PROJECTS
SB CONSTRUCTIONS
OM Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .