Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.6 LAccepted-AOC GURDASPUR ROAD OPP WAREHOUSE PATHANKOT 145 001 PB | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹34.5 L+₹3.5 L (11.5%)Rejected-AOC KTA ROAD LAMBA LINE JUNGLIGHAT PO PORT BLAIR 744103 | PORT BLAIR | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744103 | L2 | Rejected-AOC L2 | |
| 3 | L3₹42.5 L+₹11.6 L (37.4%)Rejected-AOC | L3 | Rejected-AOC L3 | |
| 4 | L4₹43.1 L+₹12.2 L (39.5%)Rejected-AOC | L4 | Rejected-AOC L4 | |
| 5 | L5₹43.2 L+₹12.3 L (39.8%)Rejected-AOC MES WORKS SITE CARNICOBAR ANDAMAN NICOBAR ISLAND PIN 744301 | CARNICOBAR | NICOBAR | ANDAMAN AND NICOBAR ISLANDS | 744301 | L5 | Rejected-AOC L5 |
Tender Value
Refer Docs
EMD Value
₹79,000
Closing Date
7 Aug 2021, 6:00 pmClosed
GE(I) CAMPBELL BAY
GE(I) CAMPBELL BAY,ARMY LAND,GREAT NICOBAR-744302
PROVN OF RO PLANT AT PUMP HOUSE, SPL REPAIR TO OLD RUSTED GI PIPE LINES AND CONNECTED FITTINGS FROM SHALLOW WELL NEAR PUMP HOUSE TO DSC LINES AT INS BAAZ AND PROVN OF CHEMICAL EARTHING FOR EQUIPMENT IN ADMINISTRATIVE BUILDING AT CGDHQ-10, CAMPBELL BA
2021_MES_459690_1
8735/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE(I) CAMPBELL BAY
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE(I) CAMPBELL BAY
₹79,000
22 Sept 2021
14 Jul 2021
9 Aug 2021
15 Jul 2021
7 Aug 2021
20 Jul 2021
Amount
Design engineering fabrication supply, installation, testing, startup & comissioning of reverse osmosis plant of capacity 1000 LPH to treat the input raw water complete with all necessary equipments as required suitable to produce potable water with the following design conditions and comprising the following:- (a) TDS not more than 1926 mg/I (b) TSS less than mg/I (c) Turbidity 1 NTU (d) PH 6.72 (e) Conductivity 2510 micromho/cm (f) Total Hardness 857 mg/I (g) SiO2 28 mg/I (h) Fe ions 0.61 mg/I (i) Mg ions 47 mg/I (k) Ca ions 168 mg/I (l) CI ions 773 mg/I (m) Si04 ions 7.5 mg/I (Note:- The input water parameters mentioned above are not as per raw water analysis test results They are just given as guidelines for the purpose of quoting the tender. The contractor has to get the raw water tested from the approved laboratory and the design of RO plant shall be based on the raw water analysis data and to give the output water of quality conforming to IS 10500 and comprising of following components/ equipments etc complete all as specified:-
A. Raw water pump No of unit : 01 No Flow Rate : 3400LPH Material of Construction : CI Type : Monoblock
B. Pressure sand Filter No. of unit : 01 No Flow Rate : 1000LPH Material of Construction : NGMF 40 Vessel size : 16"(dia) x 65" (ht) C. Activated Carbon Filter No. of unit : 01 No Flow Rate : 1000LPH Material of Construction : NGMA 45
D. Antiscalent Dosing System No. of unit : 01 No Flow Rate : 0-4LPH Tank Capacity : 1000 Ltrs E. Cartridge filter No. of unit : 01 Set Flow Rate : 1000LPH Material of Construction : PPOf Housing Type of cartridge : PP spun type Micron Rating : 5 micron Size of Cartridge : 10" long B.B F. Reverse Osmosis System a) High Pressure pump No of Pump : 01 No Flow Rate : 3400 LPH Type : Vertjcal Multistage/Eqvit Material of Construction : FRP b) Size : 4" x 40" Type of membrane : SWC No of Membrane : 05 No's Feed Flow Rate : 1000LPH Perameter Flow Rate : 3400 LPH Total Recovery : 30% c) Membrane HousingSize : 4" x 40" Material of Construction : FRP
G. Ultraviolet Disinfevtant No of : 01 No Flow Rate : 1000 LPH H. Interconnecting piping & electric control panel Quality : 01 Set Material of construction : CPVC of pipe & fittings
Supply and fixing GI pipe medium grade complete including fitting of size 50 mm bore in trenches, walls complete all as specified and directed.
Supply and laying of CPVC pipes of size 50 mm SDR 11 and plain CPVC SDR 11 fittings in trenches, walls complete all as specified
S&F Gun metal gate valve,with iron wheel head, screwed both ends for iron pipe 50 mm bore dia complete all as specified and directed. Make : Leader, Zoloto, GMT
Supply, install and commissioning of submersible pumpsets of 3 HP of 20 m head & discharge 5.5 LPS as per actual design requirement froma alll causes complete 3 phase 415 V ± 5% volts 50 cycles, AC including 40 meter submersible copper cable of suitable size complete all has specified & directed Note : Rates for necessary mounting of pumps with suitable stand are deemed to be inclusive.
Supply & install pressure filter for flow rate of 22 cum / hr complete with filter media (fine river sand - 40%, dolomite- 20%, SHILACK - 20% and activated carbon - 20%) including by pass / backwash arrangement with 63 mm diaphragm valves - 06 Nos complete including all necessary fittings / fixtures / suitable PCC foundation at least 0.5 m above the ground level all as specified and as directed by Engr-in-charge Note : Necessary PCC foundation required are deemed to be inclusive in quoted rates
M&L for alteration of existing LT distribution switch board panel cubical type fabricated out of mild steel sheet and angle iron frame extendable type complete with bus bar chamber TPN 400 Amps rating copper bus bars suitable for operation on 03 phase 415 volt, 50 cycles, AC supply complete with cable connections with suitable size of PVC insulated unarmoured cable coper conductor to motor terminals and starters and starters and including the following : (a) MCCB 4 Pole 35 KA 63 AMPS -01 No (Incommer) (b) MCCB TP 40 A, 25KA, 415V -03 Nos (c) MCB DP 32 Amps'C' Series 03 Nos (d) Multifuncion meter (voltage, Amp Three Phase/Single phase/frequency/KW etc) with suitable CTs (e) Indicating lamps carbon filament type with re-wireable fused. (g) DOL stator suitable for submersible Pumpset (For Pumpset)
Supply and fixing XLPE insulated armoured heavy duty electric cable with alluminium conductor 1100 volt grade of crossection area 50 sqmm, 3.5 Core complete all as specified and directed by Engr-in-charge. Make : Havells / Polycab / Gloster / Finolex
Supplying, laying or fixing in repairs, 80 mm dia GI water tubing, medium grade, of size as shown below confirming to IS-1239 [Part-1] including all fittings such as bends, tees, short pieces, connectors, elbows, reducers, etc laid in tenches / floors etc complete all as specified and as directed :- Make: Bansal / Jindal / Tata
Supplying, laying or fixing in repairs, 50 mm dia GI water tubing, medium grade, of size as shown below confirming to IS-1239 [Part-1] including all fittings such as bends, tees, short pieces, connectors, elbows, reducers, etc laid in tenches / floors etc complete all as specified and as directed :- Make: Bansal / Jindal / Tata
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. n exc 10 sqm on plan and n exc 1.5m in depth and getting out in any type of soil complete as specified and as directed.
Returning, fillingin, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soil all as specified and directed.
Removing excavated materils (soil) not exc. 50m and depositing where directed at a level not exc 1.5m above the starting point all as specified and directed.
Material and labour for supply, installation, testing and commissioning of copper pipe electrode earthing maintenance free earthing based on 3 mtr long copper pipe 18 mm dia(ID) with wall thickness of 2 mm, copper strip in pipe and filled with MFC for improvement of conductivity of electrode duly fixed with connector at top connection of copper strip 25X3 mm riveted /nut bolt after 12 mm boring and further earth continuity conductor made of copper strip 25x3 mm upto 7.5 meter , 60 KGS BFC shall be filled around the copper pipe elecrode ,including providing FRP pit cover of size 250mm X 250mm X 250mm complete as per manufacturer specification and complete all as specified and directed by Engr-in-Charge. Note :- (i) Rate included for testing, commisioning including checking of earth continuity and earth result complete all as specified and directed. (ii) Vendors are bound to get earthing result upto 1 Ohm with grid of three earthings and 2 Ohm with grid of two earthing, 3 Ohm with single earthing, Any additional work and material required to achieve the required result in included in the cost. (iii) Earth strip beyong 7.5m shall be measured and paid separately. (iv) Rate is included for boring of earthing in any type of soil/rock, minimum dia of bore 150mm. (v) Continuity of good earth resistance shall maintained upto 1 year and testing will be carried out monthly by MES authority. Make of Earthing electrode and BFC. (a) KP TRODES sangli or equivalent with prior approval of Accepting Officer.
Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth strip of 32x6mm (up to 7.5m in length from earth plate) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shwon in electrical plate no 5 of SSR part 1 including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS bar 8mm dia 150mm c/c reingorcement, watering funnel 15mm dia light grade for protection of earth electrode 20mm dia for watering all as speicified and directed and tested on completion.
S & F copper earth continuity conductor or main earthing lead of size 32x6 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as directed.
Note : An amount of Rs 29,300/- towards Schedule of Credit shall be deducted to arrive the Contract Sum.
kakolil trade agencies
KCM BUILDERS & CONSTRUCTIONS INDIA PVT LTD
M/s Pooja Enterprises
ASHOK BISWAS
NAVJEEVAN ENTERPRISES
A. R. ELECTRICALS
T.THIYAGARAJAN
bansal construction
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .