Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.1 LAccepted-AOC LIG 10 VIVEK NAGAR NAVIBAGH BHOPAL MADHYA PRADESH 462038 | BHOPAL | MADHYA PRADESH | 462038 | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹34.3 L+₹77,035 (2.30%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹37 L
EMD Value
₹74,000
Closing Date
29 Sept 2022, 6:00 pmClosed
GE BHOPAL
GE BHOPAL BAIRAGARH BHOPAL
DAY TO DAY MAINT OF EXT ELECTRIC SUPPLY COMPREHENSIVE EM WORKS FIRE ALARM SYSTEM AT MH AND REPAIR MAINT OF SOLAR WATER HEATER AND ALLIED WORKS AT VARIOUS LOCATIONS AT BAIRAGARH AND CLEANING OF WATER TANKS OHT UG SEMI SUMP AND ALLIED WORKS AT SI LINE
2022_MES_545281_2
8921/E8
Open Tender
Electrical and Maintenance Works
Item Rate
274 days
BHOPAL
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE BHOPAL
₹74,000
Yes
9 Jan 2023
10 Sept 2022
1 Oct 2022
10 Sept 2022
29 Sept 2022
17 Sept 2022
Amount
DAY TO DAY MAINT OF EXT ELECTRIC SUPPLY, COMPREHENSIVE E/M WORKS, FIRE ALARM SYSTEM AT MH AND REPAIR/ MAINT OF SOLAR WATER HEATER AND ALLIED WORKS AT VARIOUS LOCATIONS AT BAIRAGARH
Taking down carefully copper/aluminum point wire for ligh, fan, point including fitting such as light fittings switch socket holder ceiling roses etc, complete all as specified and directed.
Taking down carefully service connection sub main wiring of any Nos of wore any type including making good distrubed surface complete all as specified and directed.
Dismantling unservicesable MCB DB of any size and capacity alongwith teakwood bords, complete all as specified and directed.
M&L for point wiring with 1.5 sqmm multi stranded copper conductor 1100 volts grade PVC insulated unsheathed cable drawn in including PVC conduit/PVC casing caping not less than 20mm dia with all accessories conduit or in PVC casing capping as approved by EIC with PVC 1.5 Sqmm multi standard insulated unsheathed copper wire for continous earth, sunk in cast iron/MS terminal box duly painted with aluminum inside and anticorrosive paint out side with 2.8 mm thick for the follwing, complete all as specified and directed.
(a) One light /fan / call bell point controlled by one switch, complete all as specified and directed.
(b) One light point controlled by two 2 way switches, with cables 1.5 sqmm, complete all as specified and directed.
(c) One 3 pin socket outlet 5 Amps on independent board, complete all as specified and directed.
(d) One 3 pin socket outlet on same board, complete all as specified and directed.
(e) One 3 pin socket out let 15 Amps on independent board elect wiring 2.5 sqm, complete all as specified and directed.
(f) One 3 pin socket out let 15 Amps on independent board elect wiring 4.0 sqm, complete all as specified and directed.
M&L point wiring with 1.5 Sq mm multi standard copper conductor 1100 volts grade PVC insulated unsheathed cable drawn in and including in concealed PVC conduit not less than 20 mm dia medium grade with fitting as approved with PVC insulated unsheathe copper wire green 1.5 Sq mm for continuous earth, sunk in cast iron / MS terminal box duly painted with aluminum inside and black bitumeneous paint all around out side over one coat of anticorrosive paint with 2.8 mm thick bakelite sheet, earth dolly for the following, complete all as specified and directed. :- (NOTE :- the rate inclusive of cutting, chasing, making good to disturbed surface with matching paint/distemper in existing of any type of wall).
(a) One light / fan / call bell point controlled by one switch, complete all as specified and directed.
(b) One 3 pin socket outlet 5 Amps on independent board, complete all as specified and directed.
(c) One 3 pin socket outlet on same board, complete all as specified and directed.
(d) One 3 pin socket outlet 15 Amps on independent board elect wiring 2.5 Sqm, complete all as specified and directed.
M&L point wiring with 1.5 Sq mm multi standard copper conductor 1100 volts grade PVC insulated unsheathed cable drawn in existing concealed PVC conduit with PVC insulated unsheathed copper wire green 1.5 Sq mm for continuous earth, sunk in cast iron / MS terminal box duly painted with aluminum inside and black bitumeneous paint all around out side over one coat of anticorrosive paint with 2.8 mm thick bakelite sheet, earth dolly for the following complete all as specified and directed. :- (NOTE :- the rate inclusive of making good to disturbed surface with matching paint/distemper in existing of any type of wall).
(a) One light / fan / call bell point controlled by one switch, complete all as specified and directed.
(b) One 3 pin socket outlet 5 Amps on independent board, complete all as specified and directed.
(c) One 3 pin socket outlet on same board, complete all as specified and directed.
(d) One 3 pin socket outlet 15 Amps on independent board elect wiring 2.5 Sqm, complete all as specified and directed.
(e) Two light points control by 2 Nos two way switch, complete all as specified and directed.
(f) One 3 pin socket out let 15 Amps on independent board elect wiring 4.0 sqm, complete all as specified and directed.
S&F in replacement switch piano type flush button type single pole one way 5 Amps front operated, complete all as specified and directed.
S&F in replacement socket outlet 5 pin flush 6 Amps, complete all as specified and directed.
S&F in replacement switch socket combined outlet 6 pin fulsh 15 Amp, complete all as specified and directed.
S&F in replacement ceiling rose surface bakelite 65mm dia three terminal, complete all as specified and directed.
S&F in replacement bell push flush type SP 5 Amp, complete all as specified and directed.
S&F in replacement switch piano type flush button type single pole two way 5 Amps fromt operated, complete all as specified and directed.
S&F in replacement bell electric single phase suitable for 240 V, complete all as specified and directed.
S&F in replacement Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings, complete all as specified and directed.
S&F in replacement fan regulator electronic type suitable for 240 volt 300 watt step socket type
S&F in replacement enclosure sheet metal for MCB DB TPN 440 volts 200 Amps rated bus bar 4 way double door openable recessed mounting complete all as specified and directed.
S&F in replacement enclosure sheet metal for MCB DB SPN 240 volts 200 Amps rated bus bar 12 way double door openable recessed mounting complete all as specified and directed.
S&F in replacement enclosure sheet metal for MCB DB SPN 240 volts 200 Amps roted bus bar 8 way double door openable recessed mounting complete all as specified and directed.
S&F in replacement enclosure sheet metal for MCB DB SPN 240 volts 200 Amps rated bus bar 4 way double door openable recessed mounting complete all as specified and directed.
S&F in replacement 63 Amps MCB TPN 'C' curve 415 V complete all as specified and directed.
S&F in replacement upto 40 Amps MCB TPN 'C'415 V complete all as specified and directed.
S&F in replacement 5 to 32 Amps MCB 'B' single pole 240 V complete all as specified and directed.
S&F in replacement MCB single pole with neutral 240 volts 6 to 32 Amps complete all as specified and directed.
S&F in replacement MCB single pole with neutral 240 volts 40 to 63 Ampscomplete all as specified and directed.
M&L for sub main wiring with approved colour coding as per IS (Red, Black and Green for single phase circuits) with two single core PVC insulated FRLS cable 1100V unsheathed with stranded copper conductor of 4.0 sqmm nominal cross section area and drawing into and including rigid non metallic PVC conduit, ISI marked, medium grade, inclusive of all fittings such as tees, bends, junction boxes, elbows, saddles, pipe hooks, couples, lock outs, etc. 25mm external diameter and PVC insulated stranded copper conductor of 4.0 sqmm nominal cross section area as earth wire complete all as specified and directed. (i) Wiring to be done as per approved colour code in IE rule. (ii) Two runs of 4.0 sqmm cable, one run of 4.0 sqmm cable of earth continuity conductor & PVC conduit pipe shall be measured as one unit length.
M&L for sub main wiring with approved colour coding as per IS (Red, Black and Green for single phase circuits) with two single core PVC insulated FRLS cable 1100V unsheathed with stranded copper conductor of 6.0 sqmm nominal cross section area and drawing into and including rigid non metallic PVC conduit, ISI marked, medium grade, inclusive of all fittings such as tees, bends, junction boxes, elbows, saddles, pipe hooks, couples, lock outs, etc. 25mm external diameter and PVC insulated stranded copper conductor of 6.0 sqmm nominal cross section area as earth wire complete all as specified and directed. (i) Wiring to be done as per approved colour code in IE rule. (ii) Two runs of 6.0 sqmm cable, one run of 6.0 sqmm cable of earth continuity conductor & PVC conduit pipe shall be measured as one unit length.
M&L for sub main wiring with approved colour coding as per IS (Red, Black and Green for single phase circuits) with two single core PVC insulated FRLS cable 1100V unsheathed with stranded copper conductor of 10 sqmm nominal cross section area and drawing into and including rigid non metallic PVC conduit, ISI marked, medium grade, inclusive of all fittings such as tees, bends, junction boxes, elbows, saddles, pipe hooks, couples, lock outs, etc. 25mm external diameter and PVC insulated stranded copper conductor of 10 sqmm nominal cross section area as earth wire complete all as specified and directed. Note : (i) Wiring to be done as per approved colour code in IE rule. (ii) Two runs of 10.0 sqmm cable, one run of 10.0 sqmm cable of earth continuity conductor & PVC conduit pipe shall be measured as one unit length.
Supply and fix in replacement sheet metal enclosures with socket plug top and MCB's with two pin and earth plug and socket complete with one single pole MCB 240 V grade 32 Amp, complete all as specified and directed.
S&F sheet metal enclosure factory fabricated for Multiphase Out going suitable for Mounting MCCB as Incomer of rating 100 Amp Vertical distribution board 4 way with suitable Amp rated bus bar having IP-43 protection and double metal door concealed in wall including connection with aluminium thimbles as required complete all as specified. Make: Cat No - DBVDD04160TAB -MCCB of HPL or Equivalent Model Havells/Legrand/ABB/ make as mentioned in list of make Appendix 'C' as Approved by GE. ( Note : MCCB & MCB Shall be Measured and Paid Separately )
S&F for MCCB 100 Amp, 16 KA 3 Pole including complete electrical connection by appropriate size of copper lugs complete all as specified and directed by the Engr-in-Charge.
M&L for earthing complete with galvanised steel earth plate electrode size 600x600x6.3mm thick burried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanised iron wire 4 mm earth lead by means of bolts, nuts, check nuts and washers of galvanised steel and GI pipe light grade 20mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including testing on completion.NOTES 1. The unit rate includes for protection pipe and GI strip dia from top of earth plate upto 5.00 meter above groung level.
M&L for hylam sheet 2.8 mm thick complete as per site requirement upto size 4x4 inch to 8x12 inch complete all as specified and directed.
Taking out U/S CFL lamp 11 W from light fittings and S&F LED 11W, 240V, 50Hz,suitable for 2X11 w surface mounting CFL Luminaires complete all as specified and directed.
Supply and fixing in replacement electronic ballast 11 watt,suitable for 2X11 W surface mounting CFL Luminaires complete all as specified and directed.
Taking out u/s CFL lamp 36W from light fittings and S&F in replacement LED Lamp 18W, 4 pin type, retrofit complete suitable for surface mounting CFL Luminaires 1X36W or 2X36W, complete all as specified and directed.
S&F in replacement CFL lamp 36W from light fittings, 4 pin type, retrofit complete suitable for surface mounting CFL Luminaires 1X36W or 2X36W, complete all as specified and directed.
Supply and fixing electronic ballast 36 watt, suitable for 2X36W or 1X 36W surface mounting CFL Luminaires complete all as specified and directed.
Taking down u/s light fitting any type and S&F LED 20 W/21 Watt tube light fitting (T8 type), including LED retrofit tube 20/21 W one side connection type, 240 v, PF > 0.90, colour Temp 6500 K, System Luminious efficacy > 100Lm/W, complete with powder coated CRCA decorative patti suitable for surface mounting on wall, complete fitting including connecting with PVC insulated multistranded copper flexible cable 0.5 sqmm two core, and PVC round block white colour x 2 Nos for mounting of fitting complete all as specified & directed. Make :-Bajaj ( For Batten Model No. BLRB DB 118 or suitable for mounting T8 LED tube 20 watt and For LED tube Moldel No. BLRB21WCWc) or C&S cat Part No. LTDC01220WLED/WD (LED battan T8 TARA -M) or Havells (Titania LED tube with Regal batten LED) or equivalent in Philips/ Crompton / make as mentioned in list of make Appendix 'C' as Approved by GE.
Supply and fixing in replacement electronic ballast 28 watt, suitable for T-5 fittings complete all as specified and directed.
Supply and fixing in replacement LED tube rod 28 watt, suitable for T-5 fittings complete all as specified and directed.
Supply and fixing in replacement electronic ballast 36 watt, suitable for T-5 fittings complete all as specified and directed.
Supply and fixing in replacement tube rod 36 watt, suitable for T-5 fittings complete all as specified and directed.
Dismantling of ceiling fans AC single phase 230 volts of sizes 1200mm/1400mm (collected from MES fan store ) any make / model except old vintage, dismantled its stator,rotor, cutting out burnt copper winding and providing new winding with super enamelled copper winding wire existing size including cleaning of slots providing oil impregnated insulation paper or minimax, fibre, insulation in slots and well wraping with cotton tape, bind with cotton thread and varnishing over all with winding varnish as aproved by Engineer - In - chargee cleaning of bearing housing and shaft, replacing spares such as split pins, blade screws etc as required complete all as specified and directed.
All as per item no.43.00 above but for exhaust fan of following sizes :-
(a) 400/450mm sweep AC single phase 230/240 volts
(b) 300/380mm sweep - do-
(c) 230/250mm sweep - do-
All as per item No 43.00 above but for wall fan/padestal fan of any sweep and capacity, complete all as specified and directed.
S&F condenser carrier clip (PVC) in build connector two way fixed with screw on down rod or housing complete all as specified and directed.
S&F upper set of clips for down rod with rubber Bush (Garari) including set of nut bolts and washer, pin complete all as specified and directed.
S&F rubber bush ( Garari ) for mounted at upper side of down rod clip all as specified and directed
S&F gun metal bush self lubricated, any size ,suitable for ceiling and wall fans complete all as specified and directed
S&F flexible copper conductor stranded 1100 Volt PVC insulated cable twin core twisted 23/0.0076 Sq mm size, complete all as specified and directed.
S&F Fan condenser, 230 Volts of the following sizes :-
S&F ball bearing of following sizes :-
(a) NBC/ SKF - 6201'ZZ' (set of two)
(b) NBC/ SKF - 6202'ZZ' (set of two)
(c) NBC/ SKF - 6203'ZZ' (set of two)
(d) NBC/ SKF - 6204'ZZ' (set of two)
Taking down ceiling fan/wall fan from fan hook and disconnection from ceiling rose and dismantling of ceiling parts i e. down rod and connector/condenser nut bolts, split pins, rubber bush (garari) condenser carrier clip (PVC) in build connector two way complete servicing by cleaning greasing/oiling before in side surface by CTC with sand paper and repair and re - fitted the same position and testing complete all as specified and directed on site. ( Note: - Only rubber packing (garari) condenser, condenser carrier clip (PVC) in build connector two way shall be measured and paid separately)
Taking down Exhaust fan any type and disconnection from ceiling rose and dismantling i.e connector/condenser nut bolts, condenser carrier clip (PVC) in build connector two way complete servicing by cleaning greasing/oiling before in side surface by CTC with sand paper and repair and re - fitted the same position and testing complete all as specified and directed on site (Note: - condenser, condenser carrier clip (PVC) in build connector two way shall be measured and paid separately
S&F in replacement down rod for ceiling fans duly painted with synthetic enameled paint 300 mm long19 mm outer dia with holes on both ends of the rod for connection wire replacement complete all as specified and directed.
S&F in replacement down rod for ceiling fans duly painted with synthetic enameled paint 600 mm long19 mm outer dia with holes on both ends of the rod for connection wire replacement complete all as specified and directed.
S&F in replacement Exhaust fan blade duly painted suitable for 450 mm/380mm sweep complete all as specified and directed.
S&F in replacement Exhaust fan blade duly painted suitable for 300 mm/230 mm sweep complete all as specified and directed.
S&F in replacement of fan blade suitable for 1200mm sweep ceiling fan complete similar to original make with new screws complete all as specified and directed.
All as per item No.59.00 above but 1400mm sweep, complete all as specified and directed.
Supply and replacement outer frame complete with clamps, rubber packing, nut bolts etc & all accessories duly painted suitable for 450 mm /380 mm sweep exhaust fans complete all as specified and directed.
Supply and replacement outer frame complete with clamps, rubber packing, nut bolts etc & all accessories duly painted suitable for 230/300 mm sweep exhaust fans complete all as specified and directed.
Painting of ceiling fan with two coat synthetic enamel paint after surface preparation including Writing/making of MES No size of letters not less than 2.0 CM high and not more than 50 alphabets as approved colour complete all as specified and directed.
Dismantling of cabin fan of any sweep and overhauling complete by means of cleaning of stator, oiling & greasing including replacement of nut and bolt etc and reassembling the same and testing complete all as specification and directed.
Dismantling of cabin fan of any sweep and rewinding the stator with super enameled copper winding wire of suitable size including greasing, cleaning of all components of fan reassembling , testing, commission complete all as specification and directed.
Removing unserviceable bearing shaft welding broken area and threading in lathemachine at appropriate size and refixing in ceiling fan any type complete all as specified and directed.
Taking down unserviceable Fresh Air fan and S&F PVC fresh air fan of 300 mm sweep in toilets compete with louvers including all civil work like cutting and making opening in existing wall of toilet etc , including connecting up with twin core twisted flexible copper conductor cable with suitable size, complete all as specified and directed.
S&F in replacement landscaping LED light 9 watt, mushroom shape, integral decorative, LED bollard with IP 65 protection complete all as specified and directed. Make:-Bajaj (Cat No.BLMC 9W WW LED) or equivalent in Philips/ Crompton/ Havells/ Wipro / make as mentioned in list of make Appendix 'C' as Approved by GE.
Taking down carefully storage type water heater (Geysers) of any make and any capacity at any height opening for inspection compete Including heating element inner copper tank etc. De-scaling cleaning and re-assembling of Geysers after repairs carrying out and re-fixing in same position (spares as required for repair geyser are measured and paid separately) including making good to walls with CM (1:3) or PCC (1:2:4) and plastering the wall surfaces with CM 1:6 and replacement of old nuts, bolts and rubber gasket etc complete all as specified and directed.
Taking down and Supply and Fixing 1.5 KW capacity Heating Element, Push/ Screw type with ‘O’ ring including making electrical connection complete all as specified and directed.
All as per item No 70.00 above but of capacity 2.0 KW, complete all as specified and directed.
Supply & Fix in replacement of Geyser assembly suitable for 25 ltr capacity ISI marked including dismantling of old unserviceable geyser assembly complete all as specified & directed.
All as per item No 72.00 above but capacity of geysers 50 litres, complete all as specified and directed.
Supply & Fix in replacement thermostate suitable for 25/50 Ltr Geyser ISI marked complete all as specified & directed.
Supply & Fix in replacement of inner tank made of steel suitable for 25 Ltr geyser including dismantling of old unserviceable inner tank complete all as specified & directed.
Supply & Fix in replacement inner tank made of steel suitable for 50 Ltr geyser including dismantling of old unserviceable inner tank complete all as specified & directed.
Supply & Fix in replacement outer tank made of steel suitable for 25 Ltr Geyser including dismantling of old unserviceable outer tank complete all as specified & directed.
Supply & Fix in replacement outer tank made of steel suitable for 50 Ltr Geyser including dismantling of old unserviceable outer tank complete all as specified & directed.
Supply & Fix in replacement bottom cover suitable for 25 Ltr Geyser including dismantling of old unserviceable bottom cover complete all as specified & directed.
Supply & Fix in replacement bottom cover suitable for 50 Ltr Geyser including dismantling of old unserviceable bottom cover complete all as specified & directed.
Supply & Fix in replacement indicating lamp 230 volts 50 HZ AC suitable for geyser any type (round,squire or rectangular type) any capacity complete all as specified & directed.
Supply & Fix in replacement sheet metal enclosure with industrial type 3 pin socket and plug including one MCB single pole 32 Amps 240 volts 50 HZ complete all as specified & directed.
Supply & Fix in replacement copper connection 15 mm dia 45 cm long with both side nut complete all as specified & directed.
Supply & Fix in replacement PVC connection heavy duty 15mm dia 45 cm long with PTMT nutscomplete complete all as specified and directed.
Supply & Fix in replacement pressure release valve suitable for 25/50 Ltr capacity geyser complete all as specified & directed.
Taking out old U/S voltage stabilizers of capacity 0.5 KVA to 5 KVA from MES store/site and repair the same in MES work shop (if the transformer found burnt, the in same shall be re-winded in the workshop of contractor complete all as specified and directed.
Taking out old burnt winding work and re-winded with super enameled copper winding wire (existing size) for 5 KVA voltage stabilizers including all necessary insulating material and testing complete all as specified and directed.
All as per item No. 87.00 above but capacity of voltage stabilizer 4 KVA/3KVA, complete all as specified and directed.
All as per item No. 88.00 above but capacity of voltage stabilizer 2 KVA / 1KVA, complete all as specified and directed.
Supply and fix LED high bay light of 100 W IP 65 Rating Voltage input 140V to 280V Efficacy 100Lm/W (+5%) complete all as specified and directed. Make: Orient Cat part No LHPNP-100-C ,Bajaj GV Duranto or equivalent in havells/ make as mentioned in list of make Appendix 'C' as Approved by GE.
Supply & Fix in replacement of microprocessor based main control panel of 10 zones having provision of indicator for fire alarm, fire, fault,open/short earth circuit complete all as specified and directed. Make : SAFE ZONE/APOLLO or equivallent by OEM as approved by GE
Supply & Fix in replacement of Zonal Indicator panel for fire alarm system zonal panel of upto 6 zone having provision for indicator fire,fault, open/short earth circuit dulyinterfaced with main control panel complete all as specified and directed. Modle SD-1165. Make : Safezone/Apollo as approved by GE
Supply & Fix in replacement of Repeater Panel for fire alarm system repeator panel of mann control panel hving provision of Audio Video indicators for fire, faukt, oen/short circuit duly interfaced with main control panel complete all as specified and directed. Make : Safezone/Apollo or equivalent as approved by GE
Supply & Fix in replacement of Multi criteria heat cum smoke detector complete all as specified and directed. Make : Apollo or equivalent as approved by GE
Supply & Fix in replacement of Response indicator for fire alarm system made of 1.6mm thick CRCA sheet having dual Red LED indicator complete all as specified and directed. Make : Safezone or equivalent as approved by GE
Supply & Fix in replacement of Siren for fire alarm system complete all as specified and directed. Make : Safezone or equivalent as approved by GE.
Supply & Fix in replacement of medium intensity hooter for fire alarm system complete all as specified and directed. Make : Safezone or equivalent as approved by GE
Supply & Fix in replacement of manual call points suitable for addressable system duly painted in red colour paint with front glass to be broken in case of fire) complete with test key to check the response with out breaking the glass and die cast aluminium housing with IFD indicator complete all as specified and directed. Make : APOLLO or equivalent as approved by GE
Supply & Fix in replacement of copper conductor multi stranded armoured cable fixed on wall/ceiling with proper saddles/spacers of size 2 Core 1.5 Sqmm complete all as specified and directed. Make : CCI/SUNLIGHT or equivalent as approved by GE
Supply & Fix in replacement of Zone cards, complete all as specified and directed. Make : HITESH/GURUTRONIC or equivalent as approved by GE
Supply & Fix in replacement of pillbox complete all as specified and directed. Make : MATHS/GURUTRONIC or equivalent as approved by GE
Taking down of Solar water heating system of 200 ltrs per day capacity from its position after disconnecting water connections, and re - fixing /reassembling in position after repair and testing, complete all as specified and as directed. Note:- (a) Rate quoted by the contractor deemed to have been included making good of missing Nuts,Bolts and washers, unions, sockets, flanges, screws etc to make it full functional, (b) Descalling/desludging, cleaning and washing of solar panels,hot water pipes,copper tubes,hot and cold water Tanks by using appropriate chemicals and reassembling the panels including necessary welding of collector fins as required, (c) Painting to staging,solar panel frames,hot water tank frame using one coat of synthetic enamel paint including necessary preparation of surfaces complete, (d) any other materials/Parts need to be replaced (to be measured and paid as supplied only).
All as per item No -102.00 here in above but 100 Litre per day capacity, complete all as specified and directed.
S&F in replacement of Stainless steel, Water heater tank, suitable for 100 LPD to match with existng SS tank specifications, with all arrangements, complete all as specified and directed Note: (i) Thickess of new tank to be matched with existing tank. (ii) The work should be executed at the top of 20m height building.
S&F in replacement of Stainless steel, Water heater tank suitable for 200 LPD , to match with existng SS tank specifications, with all arrangements, complete all as specified and directed Note: (i) Thickess of new tank to be matched with existing tank. (ii) The work should be executed at the top of appx 20m height building.
S&F Solar energy collector panel made of Aluminium body with 5mm thick toughened glass complete with copper fins of capacity 200 litres per day as per existing make complete all as specified & directed.
S&F Solar energy collector panel gasket made out of Supirior quality Rubber to make system air tight,dust and water proof complete of capacity 200 litres per day as per existing make complete all as specified & directed.
S&F compressed Glass wool (insulation materials) 48mm thick between Solar energy collector panel copper tubes frame andAluminium body panel including securing it on panel by means of necessary adhessive complete all as specified & directed.
S&F Solar energy collector panel manifold 1.40 mtr long, made out of 20mm dia copper tube having 1 No MS flange,74mm dia welded at each end duly drilled for Nuts,Bolts and washers as per existing make including welding of solar collector tubes with manifold complete all as specified & directed.
S&F in replacement of rotational moulded, triple layer HDPE water storage tank of 500 ltrs capacity (Cylindrical vertical with closed top) ISI (IS 12701-1996) marked fixed in position on existing places complete all as specified including 02 Nos 20mm dia full threaded GI tank niple, 20 mm dia brass ball valve with epoxy coated Aluminium rod with high density plastic float ball including fixing of inlet, outlet & overflow pipe etc, complete all as specified and as directed.
S&F in replacement of rotational moulded, triple layer HDPE water storage tank of 1000 ltrs capacity (Cylindrical vertical with closed top) ISI (IS 12701-1996) marked fixed in position on existing places complete all as specified including 02 Nos 20mm dia full threaded GI tank niple, 20 mm dia brass ball valve with epoxy coated Aluminium rod with high density plastic float ball including fixing of inlet, outlet & overflow pipe etc, complete all as specified and as directed.
S&F 20 mm bore GI tubing medium grade along with sockets, bends, tees and other fitting as required fixed to wall, floor, or ceiling with all fittings including taking down old tubing complete all as specified and diretced.
S&F 25 mm bore GI tubing medium grade along with sockets, bends, tees and other fitting as required fixed to wall, floor, or ceiling with all fittings including taking down old tubing complete all as specified and diretced.
S&F 15 mm bore GI tubing medium grade along with sockets, bends, tees and other fitting as required fixed to wall, floor, or ceiling with all fittings including taking down old tubing complete all as specified and diretced.
Supply and filling anti freezing liquid in 20 ltr PVC can for solar water heater system complete all as specified and directed.
S&F 3-layer PP-R Polypropylene random copolymer) concealed pipes SDR 7.4 (PN16) UVstabilized andantimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded p o l y p r o p y l e n e random fittings fixed complete to walls, ceilings or in floors etc including taking down old pipe any type of followings sizes :-
S&F in repairs toughened glass of size as per sample approx 2 Sqmtr, 4mm thick of solar water heater panel of capacity 200 LPD complete all as specified and directed.
S&F for Bib taps, cast copper alloy with chromium plated fancy type with capstan head, screwed down, screwed for 15 mm dia bore iron pipe, including taking down old one complete all as specified and as directed.
S&F Stop valves, cast copper alloy screwed down,high pressure,with crutch or butterfly handle, screwed both ends for 15 mm iron pipe or for unions and fixed including taking down old one complete all as specified and directed.
S&F Stop valves, cast copper alloy screwed down, high pressure, with crutch or butterfly handle, screwed both ends for 20 mm iron pipe or for unions and fixed including taking down old one complete all as specified and directed.
S&F Stop valves, cast copper alloy screwed down,high pressure, with crutch or butterfly handle, screwed both ends for 25 mm iron pipe or for unions and fixed complete all as specified and directed.
S&F in replacement thermostate suitable for 200/100 Ltr Geyser ISI marked complete all as specified & directed.
S&F in replacement 2 KW or existing capacity Heating Element, Push/ Screw type with ‘O’ ring including making electrical connection complete all as specified and directed.
S&F in repairs three core PVC insulated FRLS cable 1100V unsheathed with stranded copper conductor of 4 sqmm 3 core nominal cross section area complete all as specified and directed.
Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium conductor of size 35 sqmm, 3.5 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc including taking out old unserveciable cable, any type complete all as specified and directed.
Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium conductor of size 25 sqmm, 3.5 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc including taking out old unserveciable cable, any type complete all as specified and directed.
Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium conductor of size 16 sqmm, 4 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc including taking out old unserveciable cable, any type complete all as specified and directed.
S&F in repairs LED driver suitable for 45Watt LED light ( to suit as existing light fittings of any make) complet all as specified and directed. Make : Wipro/Bajaj/Cromption/Havells/Phiips as approved by GE)
S&F in repairs LED driver suitable for 60Watt LED light ( to suit as existing light fittings of any make) complet all as specified and directed. Make : Wipro/Bajaj/Cromption/Havells/Phiips as approved by GE)
Supply & Fix cable PVC insulated and PVC sheathed size 4 Sqmm twin core stranded aluminium conductor complete all as specified and directed .
M&L for bracket made of GI light grade pipe 1.2 Mtr long of size 40 mm bore bend to shape as per site requirment fixed to pole with 40 x 5 MM -02 Nos, size clamps bolts, Nuts, washers incuding painting two coats of aluminium paint over a coat of primer complete all as specified and directed.
Taking down existing street light fitting any type and S&F Integral LED Street light luminaire of 45 W, comprising of pressure die cast aluminium housing LED street light luminaire ,IP 66 protection and with all fixing arangement , nuts, bolts and washer connecting to electric system with 4.0 sqmm PVC Aluminium stranded conductor 2 coreof required length from light fitting to street light control box on pole , testing and completion, complete all as specified and directed at site. Make- Bajaj, Cat No BRTFG 45 W LED or Equivalent in CG/ Philips/Havells/ make as mentioned in list of make Appendix 'C' as Approved by GE.
Taking down existing flood light fitting any type (up to 17 mtr length) and S&F LED flood light luminaire 120 Watt with secondary optics made in pressure die cast housing & heat sink in aluminium extrusion with IP 66 protection and with all fixing arrangement, nut , bolt and washer connecting to electric system with 4.0 sqmm PVC Aluminium stranded conductor 2 core of required length from light fitting to street light control box on pole , testing and completion, complete all as specified and directed at site. Make- Bajaj Cat No. BJFL120W or Equivalent in CG/ Philips/Havells/ make as mentioned in list of make Appendix 'C' as Approved by GE.
S&F in replacement Nature switch (Model- Swadeep 02) sensor only with & including switching timer complete all as specified and directed. [MAKE: KAKATIYA ENERGY SYSTEM/BAJAJ/ HEALER/ make as mentioned in list of make Appendix 'C' as Approved by GE. ]
S&F in replacement 3 Pole contactor of AC 3 rating 25 Amp, 3 Phase, 415 V as per IS 13947-4-1 suitable for nature time switch (Model- Swadeep 02) complete all as specified and directed. [MAKE: BCH/L&T/SCHNEIDER/ make as mentioned in list of make Appendix 'C' as Approved by GE.
S&F in replacement single Pole contactor 16 Amp, single Phase, 240 V as per IS 13947-4-1 suitable for nature time switch (Model- Swadeep 02) complete all as specified and directed. [MAKE: BCH/L&T/SCHNEIDER / make as mentioned in list of make Appendix 'C' as Approved by GE.
S&F in replacement 3 Pole contactor of AC 3 rating 95 Amp, AC1 rating 160 Amp, type MNX 95, Aux cont 2NO +2NC, 3 Phase, 415 V , as per IS 13947-4-1, complete all as specified and directed. Make :- L&T, Cat No. CS 94136 or equivalent in Siemens/ Schinder/ make as mentioned in list of make Appendix 'C' as Approved by GE. .
M&L for PCC (1:3:6) type C-2 using (using 40mm graded stone aggregates) as in foundation filling and mass concrete (for foundation bed concrete in stays /poles or any other directed site) complete all as specified and directed.
M&L for making coping to the new/existing PCC/Steel Poles of size 600x600x450 mm above the GL with PCC 1:2:4 type B-1 using 20 mm graded broken stone aggregate as in mass concrete complete all as specified and directed. ( Note :- Quoted rates deemed to be including for dismantling of broken copings)
Taking out old unserviceable cable from trenches of any size and credit to contractor complete all as specified and directed.
Supply, Laying, commissioning and testing of UG LT cable XLPE insulated screened PVC bedded, galvanized steel strip armored, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 sqmm 4 core including aluminium lugs at the termination ends, complete all as specified and directed.
All as per item No 142.00 above but 16 sqmm 2 core, complete all as specified and directed.
Excavation in trenches in any type of soil not exceeding 1.5 mtr wide and n.exe 1.5 mtr depth including getting out complete all as specified and directed.
Returning filling in including spreading, leveling ,and well ramming, in layers not exceeding 25 cm each layer of any kind of soil, complete all as specified and directed.
Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding 1.5 mtr above the starting point, complete all as specified and directed.
M&L for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection (8 cm below cable & 15 cm above cable) complete all as specified and directed. [Note:-Compacted/punned thickness shall be measured & paid]
Supplying and laying sub class 'B' bricks (modular) for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable complete all as specified and directed
Taking out old rusted pipe and S&F of GI tubing Light grade, complete with all fittings as required for passing through cables under the trenches, floor ,along the wall or along the pole with suitable size M.S.flat iron clamps incl nut,bolt and washer of 50 mm bore complete all as specified and directed.
M&L Painting of steel pole (swan neck type or straight type) up to 12 mtr height with cross arms, clamp of any length and shape for LT overhead line/ for stree light with two coat of aluminium paint after scraching out old paint, cleaning and exiting surface rust free, preparation of the existing surface, including marking pole numbers in a 20 cm dia yellow circle with number writting with black syenthic paint & painting strips in alternate from bottom to top with three strips of black syenthatic paint & two strips of white fluorescent paint (up to 1.5 mtr height) through out the circumference of pole ( width of each strip shall be of 30 cm), including one coat of lime wash on PCC copping of pole complete all as specified and directed.
Taking down u/s automatic street light switch and Supply , fixing testing and comissioning, of automatic street light switch of capacity 8KW in three phase, using Nature switch for automatic switching of street lights based on LUX level of natural light. The sensor (nature switch) along with suitable power contractor, MCB and support terminals enclosed in pole/ wall mounted enclouser made of rust proof, electric shock proof, termite proof and FR grade SMC junction box (Make: Sintex) conforming to IP54, including mounting arrangement with suitable size of FI clamps 02 Nos with complete acessories all as specified and directed. Make:- KAKATIYA ENERGY SYSTEM LIMITED Model No. SWADEEP - 02EC8KW3P, The automatic switching unit shall comprising of following: (i) Contractor rating (AC3) 25Amp 4 Pole or 3 Nos 25Amp 1 Pole: Make : BCH/L&T/Schneider (ii) MCB 32Amps(SP),10 KA ,240 volts (SP 3Nos) Make : Schinder/ Legrand/ L&T (iii) NATURESWITCH-01 Make: KAKATIYA ENERGY SYSTEM LIMITED
Taking down u/s automatic street light switch and Supply , fixing testing and comissioning, of automatic street light switch of capacity 8KW in single phase, using Nature switch for automatic switching of street lights based on LUX level of natural light. The sensor (nature switch) along with suitable power contractor, MCB and support terminals enclosed in pole/ wall mounted enclouser made of rust proof, electric shock proof, termite proof and FR grade SMC junction box (Make: Sintex) conforming to IP54, including mounting arrangement with suitable size of FI clamps 02 Nos with complete acessories all as specified and directed. Make:- KAKATIYA ENERGY SYSTEM LIMITED Model No. SWADEEP - 02EC8KW1P, The automatic switching unit shall comprising of following: (i) Contractor rating (AC3) single phase 50-60 Amp : Make : BCH/L&T/Schneider (ii) MCB 63 Amps(SP),10 KA ,240 volts. Make : Schinder/ Legrand/ L&T (iii) NATURESWITCH-01 Make: KAKATIYA ENERGY SYSTEM LIMITED
S&F in replacement of MCCB, 250 Amp, 4 Pole, 25 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting , with thermal release range 200-250 Amp including spreader terminals and phase barriers. Make L&T (d - sine) Cat No. CM90638OOPO or equivelent in Schinder/ C&S/ make as mentioned in list of make Appendix 'C' as Approved by GE. .
S&F MCCB, 200 Amp, 3 Pole, 25 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting , with thermal release range 160-200 Amp including spreader terminals and phase barriers, complete all as specified and directed. Make L&T (d - sine) Cat No. CM90638OONO or equivelent in Schinder/ C&S / make as mentioned in list of make Appendix 'C' as Approved by GE.
S&F MCCB, 160 Amp, 3 Pole, 25 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting , with thermal release range 125-160 Amp including spreader terminals and phase barriers, complete all as specified and directed. Make L&T (d - sine) Cat No. CM90638OOMO or equivelent in Schinder/ C&S / make as mentioned in list of make Appendix 'C' as Approved by GE.
S&F MCCB, 100 Amp, 3 Pole, 25 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting , with thermal release range 80-100 Amp including spreader terminals and phase barriers, complete all as specified and directed. Make L&T Cat No. SL972090000 or equivelent in Schinder/ C&S/ make as mentioned in list of make Appendix 'C' as Approved by GE.
M&L for cutting PCC/floor/road and taking out cable and making good, including material as per existing after laying of pipe for cable protection all as specified and directed size of trench not more than 0.30 x 0.30 m complete all as specified and directed .
Taking out existing u/s street light control box and Supply and fixing MS Sheet 2mm thick control gear box for street security light of size not less than 250 (w) x 300(h) x 200(depth) mm , with aluminium bus bar of 32 Amps rating for single phase & neutral mounted on apoxy based insulators with locking arrangement fixed to pole with MS clamps -2 Nos of 20 mmx 4 mm and including MCB SP 6 Amps, B curve 230 volt- 01 No, complete all as specified and directed.
S&F in repair Analog time switch (FM series) complete all as specified and directed. Make : GIC (L&T) or equivalent asapproved by GE.
CLEANING OF WATER TANKS (OHT, UG, SEMI SUMP) AND ALLIED WORKS AI SI LINE
Cleaning & disinfection of water semi UG sump through mechanized dewatering, Sludge removal, High pressure cleanning, Vacuum cleaninng, Anti bacterial spray, UV radiation arrangments at main filter pump house at SI Line complete all as specified and directed. . NOTE:- Quoted rates is deemed to include for:- (i) Cleaning inside walls, floor, dome, ceiling with wire steel brush removing pile/sludge/ silt/ alge and other forgein material ,sludge removal , high pressure cleaning, anti bactrial spray, UV radiation and washout with clear water all as specified and upto the satisfaction of EIC . (ii) Applying one coat of super quality lime wash on inner wall surface after cleaning of tank.Date of Cleanning also mention on respective tank. (iii) Cleaning the surrounding area of the reservoir to a distance of 3 mtrs all around its circumference including cutting of grass, digging out roots, filling holes, levelling of ground and removing waste material to a distance not exceeding 50m complete all as directed. (iv) Contractor with provide them self all T&P required at site without any extra cost.
100000 gallons UG Sump
50000 gallons UG Sump
38000 gallons UG Sump
5000 Ltrs UG Sump
All as per item No 161.00 but cleaning of over head tank for the following capacity.
25000 gallons at 15mtr staging at New SI Line
50000 gallons at 18 mtr staging at Hill top reservoirs
M&L for washing out/cleaning of PVC water storage tank of 3x10000 ltr & 2x 5000 ltr cap at SCC Bhopal by mannually or mecahnically of inner surface with nylon brush and removing complete sludge material and wash out by clear water complete up satifaction of Engr in charge. Note :- Any damage to PVC tank repair/replacment shall be done by the contractor.
S&F Gun metal globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed in for following size complete all as specified and directed. :-
25 mm bore
20 mm bore
15 mm bore
40 mm bore
50 mm bore
S&F Plug type bib tapes, 15mm bore, cast iron screwed for iron pipe complete all as specified and directed.
S&F Plug type bib tapes, 20mm bore, cast iron screwed for iron pipe complete all as specified and directed.
S&F Plug type bib tapes, 25mm bore, cast iron screwed for iron pipe complete all as specified and directed.
S&F Plug type bib tapes, 40mm bore, cast iron screwed for iron pipe complete all as specified and directed.
S&F Bib taps cast copper alloy, 15 mm bore, with capstan heads, chromium plated, screwed down high pressure with or without lettered hot or cold with long screwed shanks and fly nuts screwed for iron pipe and fixed complete all as specified and directed.
S&F PVC Water hose pipe havy duty dia 50 mm (for swimming pool) complete all as specified and directed.
M&L for maint & cleaning of surrounding areas of water supply installations, pump house, etc by cutting all bushes, shurbs, sharkandas and any other type of vegetations and trees girth upto 30 cm and treeming the earth surface to make good soil pressions removing and disposal of the waste retreat to a distance not exceeding 100 mtr by deploying Mazdoor/T&P as required and taking all precautions complete all as specified and directed.
M&L for replacement of sluice valve class PN-1.6 heavy duty flanged ends drilled , ISI-marked confirming to IS:14846 suitable for following bore pipe, wheel oprated (Handle) with high tensile stainless steel spindle, including nuts, bolts and jointing with jointing materials etc. complete including taking out old existing unservicable sluice valve incl. making arrangement for safe working complete all as specified and directed.
80mm dia
100 mm dia
150 mm dia
Schedule of credit (calculation will be done off line) Rs. 147858.00
PRADEEP SISODIYA
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .