| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.2 LAdmitted-Finance V P O SAROTARI TEHSIL BAROH DISTRICT KANGRA PIN 176037 HP | KANGRA | HIMACHAL PRADESH | 176037 | ₹38.2 L | L1 | Admitted-Finance |
| 2 | L2₹40.3 LAdmitted-Finance | ₹40.3 L | L2 | Admitted-Finance |
| 3 | L3₹41.8 LAdmitted-Finance | ₹41.8 L | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Electromech Engineers L1 | m/s mohd saleem and co L2 | M/S NORTHERN ELECTRICAL WORKS L3 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of copper wound step-down distribution transformer, outdoor, floor mounted type, suitable for 11 KV / 433 V, 3 phase, 4 wire, 50 Hz AC system, of capacity 100 KVA , oil immersed, naturally cooled ONAN (Oil Natural Air Natural) type, complete with all standard accessories, fittings and mounting arrangements. The transformer shall conform to latest amendments of IS-1180 (Part-1):2014, BIS certified. Transformer shall be suitable for outdoor operation under Indian climatic conditions.
The transformer shall have:
HV side: Delta connected
LV side: Star connected with neutral brought out
Vector group: DYN-11
Tapping: Off-load tap changer on HV side with taps of ±2.5%, ±5%, ±7.5% in steps of 2.5%
Cooling: ONAN with radiators/cooling fins
Technical requirements
i. Winding: Electrolytic grade copper
ii. Insulation: As per IS standards
iii. Percentage impedance: As per IS 1180
iv. Losses: As per Energy Efficiency Level-2 / latest BEE norms
v. Temperature rise limits: As per IS 1180
vi. Vector group: DYN-11 mandatory
vii.Neutral brought out and suitable for solid earthing | 1 | Each | 7,30,000 ₹7,30,000 Lowest | 7,50,000 ₹7,50,000 | 7,75,000 ₹7,75,000 |
| 1.01Accessories & fittings i. Cable end box on HV side suitable for 95 sqmm 3 core size XLPE cable. ii. Cable end box on LV side suitable for 95 sqmm 3.5 Core size XLPE cable with cable glands. iii. Conservator with oil level indicator (min/max marking). iv. Silica gel dehydrating breather (first filling included). v. Cooling radiators / fins. vi. Explosion vent / pressure relief device (PRD). vii. Oil temperature indicator (OTI) with maximum reading and reset. viii. Thermometer pocket. ix. Oil filling hole with cap. x. Oil drain valve with sampling facility. xi. Air release valve. xii. Earthing terminals: Minimum 2 nos. for body earthing .Minimum 2 nos. for neutral earthing (separate bushing) xiii. Lifting lugs and pulling lugs. xiv. HV bushings with arcing horns. xv. LV bushings (porcelain/epoxy as per standard). xvi. Rating plate (as per IS) and terminal marking plate. xvii. Danger plate and phase indication markings. xviii. First filling of new, unused, ISI marked transformer oil conforming to IS 335. Notes:-B24 (i) The drawing of transformer shall be approved by accepting officer on receipt of request from the contractor through GE. (ii) The transformer shall be tested as per IS for all routine tests in the factory premises and reports will be deposited with purchase voucher. (iii) Factory inspection and testing of the transformer shall be carried out in the presence of the representative of the Accepting Officer/SEI/IEM, and all associated charges shall be borne by the contractor.B25 | ||||||
| 2.00 | Supply, Installation, testing and commissioning of LT feeder piller box outdoor type made out of 3.15 mm thick CRCA sheet and MS angle iron frame with weather proof canopy, mounted on PCC pedestal, cubical type, front and rear side openable, compartment type with hinged door lighting lugs 2 Nos, earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc and passivated nut, bolts spring and washers and locking arrangement for each compartment, provision of air vent, dust and vermin proof, provision of cable alley with 400 Amps rated aluminium bus bar having 1100 Volts grade slaving and internal connection should be provided with aluminium strips of suitable size and to accommodate and including the following MCCBs duly painted with 2 coats powder coating over a coat of anticorrosive red oxide primer should accommodate the following accessories.
Incomer:
200 Amps, 4 pole MCCB, 36 KA 415V Adj. Thermal & Adj. Magnetic Released - 01 No,
Digital Volt meter 0-500V with inbuilt selector switch - 01 No
Digital Amp meter 0-500A with inbuilt selector switch & CT Coils- 01 No
Set of LED type indicating lamps - 03 No Aluminium Bus Bar 300 Amps TPN
Outgoing:
160 Amps, MCCB 4 ,Pole 25KA 415 V,Adj.Thermal Adjustable type - 01 No
100 Amps, MCCB 4 ,Pole 25KA 415 V,Adj.Thermal Adjustable type - 01 No
MCB DP 40 Amps Outgoing -10 Nos | 1 | Each | 2,22,400 ₹2,22,400 | 1,20,000 ₹1,20,000 | 89,000 ₹89,000 Lowest |
| 3.00 | Supply, Installation, Commissioning and testing of transformer of capacity 160 KVA step down outdoor type Copper Wounded ONAN Cooling 11/0.433 KV (at no load) AC 3 Phase 50 Hz on secondary side double wounded oil immersed naturally all air cooled with external tubes/radiator, delta connected as on primary and star connected with neutral brought on secondary. The maximum temperature rise should not exceed 45 degree centigrade in oil and 50 degree centigrade in HV/LV winding when measured by the resistance method after continuous full load run in ambient temperature the transformer shall confirming to IS 2026, 1997 and comprising of following accessories :-
(a) 01 No cable end box on HV side consisting of with 03 Nos porcelain bushing with bushing rods and nuts washers and cable glands suitable for XLPE cable 3 Core 120 Sqmm including cable joint complete adopter box
(b) 01 No cable end box on LV secondary side consisting of 04 Nos porcelain bushing with bushing rods and nuts washers and cable glands suitable for XLPE cable 3.5 Core 185 Sqmm including cable joint complete adopter box
(c) Oil conservator with filter type drain valve and oil level gauge. | 1 | Each | 8,65,000 ₹8,65,000 | 8,50,000 ₹8,50,000 | 8,18,000 ₹8,18,000 Lowest |
| 3.01(d) Dehydrating breather with first filling of dehydrating agent. (e) Explosive vent. (f) Thermometer Pocket. (g) Two earthing terminal on tank body to facilitate fixing of 32x6mm GI Strip. (h) One No thermometer dial type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge max reading panted terminal. (j) Rating plate with terminal plate. (k) Oil drain filter valve. (l) Oil filling hole on top cover with plug. (m) Air release valve/plug. (n) 4 Nos plain solid cast steel detachable rollers. (o) Extra bushing for neutral out side the cable box providing independent earthing for neutral. (p) First fill of transformer oil confirming to relevant IS and tested upto 60KV dielectric strength. | ||||||
| 4.00 | Supplying and laying unreinforced precast concrete cable cover class HVP type 1 with peak, size 300 mm x 180 mm x 40 mm complete all as specified and directed. | 438 | Each | 28 ₹12,264 Lowest | 50 ₹21,900 | 32 ₹14,016 |
| 5.00 | S&F 3 phase prodigy (Secure) distribution transformer meter with built-in-current transformers, energy audit and system analysis, direct connected 3 Ph 4 Wire 415V with current range 40-200A, accuracy class 1.0, frequency 50 Hz, Insulation Class-Protection Class II, Impulse withstand 10KV, IS-13779, Dimensions (W x H x D) 365 x 283 x 221mm (with extended terminal cover) complete all as specified and directed. | 1 | Each | 75,000 ₹75,000 | 20,000 ₹20,000 | 16,900 ₹16,900 Lowest |
| 6.00 | M&L for cubical panel (dimension of meter to be fixed in Panel is 365x283x221mm) for 3 Ph Prodigy (Secure) Meter along with connected items like nuts & bolts, screws, binding wire, hold fast for fixing in wall/grouting including XLPE UG cable 95 Sqmm 3.5 Core from transformer to meter and panel complete all as specified and directed.
Note : The quoted rate shall be deemed to be included for connection of LT UG Cable from Transformer to panel and meter | 1 | Each Job | 25,000 ₹25,000 | 5,000 ₹5,000 | 2,000 ₹2,000 Lowest |
| 7.00 | Supply and Installation Voltage stabilizer copper wound for automatic operation, three phase naturally oil cooled indoor type & designed for input variation between 300 V to 480 V with output voltage stabilized at 415 Volts with accuracy ± 2.5% and speed of correction 8 Volts per second and of capacity 100 KVA complete all as specified and directed. | 2 | Each | 3,00,000 ₹6,00,000 Lowest | 4,40,000 ₹8,80,000 | 3,96,000 ₹7,92,000 |
| 8.00 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 Sq mm 3.5 core complete all as specified and directed. | 190 | RM | 730 ₹1,38,700 | 600 ₹1,14,000 Lowest | 999 ₹1,89,810 |
Tender Value
₹37.5 L
EMD Value
₹75,000
Closing Date
1 Aug 2026, 6:00 pmClosed
CWE, HQ 133 WORKS ENGRS
HQ 133 WORKS ENGRS, C/O 56 APO, PIN- 914133
CWEK/T-36/969 EWS/2026-27 PROVN OF 100 KVA TRANSFORMER, VOLTAGE STABILIZER AND ALLIED SERVICE AT SULTANPUR KANDI AND SPL REPAIR OF TRANSFORMER AND VOLTAGE STABILIZER AGAINST BER EQPT AT URI IN THE AOR OF AGE E/M UNDER GE 969 EWS
2026_MES_775341_1
CWEK/T-36/969 EWS/2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 969 EWS
Class D and above and Category b (ii)
7 documents required · 7 mandatory
₹500
GE 969 EWS
₹75,000
13 Aug 2026
30 Jun 2026
10 Aug 2026
30 Jun 2026
1 Aug 2026
14 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of copper wound step-down distribution transformer, outdoor, floor mounted type, suitable for 11 KV / 433 V, 3 phase, 4 wire, 50 Hz AC system, of capacity 100 KVA , oil immersed, naturally cooled ONAN (Oil Natural Air Natural) type, complete with all standard accessories, fittings and mounting arrangements. The transformer shall conform to latest amendments of IS-1180 (Part-1):2014, BIS certified, and BEE 5-star rated (latest applicable notification). Transformer shall be suitable for outdoor operation under Indian climatic conditions.
The transformer shall have:
HV side: Delta connected
LV side: Star connected with neutral brought out
Vector group: DYN-11
Tapping: Off-load tap changer on HV side with taps of ±2.5%, ±5%, ±7.5% in steps of 2.5%
Cooling: ONAN with radiators/cooling fins
Technical requirements
i. Winding: Electrolytic grade copper
ii. Insulation: As per IS standards
iii. Percentage impedance: As per IS 1180
iv. Losses: As per Energy Efficiency Level-2 / latest BEE norms
v. Temperature rise limits: As per IS 1180
vi. Vector group: DYN-11 mandatory
vii.Neutral brought out and suitable for solid earthing | 1 | Each | - | - |
| 1.01 | Accessories & fittings
i. Cable end box on HV side suitable for 95 sqmm 3 core size XLPE cable.
ii. Cable end box on LV side suitable for 95 sqmm 3.5 Core size XLPE cable with cable glands.
iii. Conservator with oil level indicator (min/max marking).
iv. Silica gel dehydrating breather (first filling included).
v. Cooling radiators / fins.
vi. Explosion vent / pressure relief device (PRD).
vii. Oil temperature indicator (OTI) with maximum reading and reset.
viii. Thermometer pocket.
ix. Oil filling hole with cap.
x. Oil drain valve with sampling facility.
xi. Air release valve.
xii. Earthing terminals: Minimum 2 nos. for body earthing .Minimum 2 nos. for neutral earthing (separate
bushing)
xiii. Lifting lugs and pulling lugs.
xiv. HV bushings with arcing horns.
xv. LV bushings (porcelain/epoxy as per standard).
xvi. Rating plate (as per IS) and terminal marking plate.
xvii. Danger plate and phase indication markings.
xviii. First filling of new, unused, ISI marked transformer oil conforming to IS 335.
Notes:-B24
(i) The drawing of transformer shall be approved by accepting officer on receipt of request from the contractor through GE.
(ii) The transformer shall be tested as per IS for all routine tests in the factory premises and reports will be deposited with purchase voucher.
(iii) Factory inspection and testing of the transformer shall be carried out in the presence of the representative of the Accepting Officer/SEI/IEM, and all associated charges shall be borne by the contractor.B25 | - | - | - | - |
| 2 | Supply, Installation, testing and commissioning of LT feeder piller box outdoor type made out of 3.15 mm thick CRCA sheet and MS angle iron frame with weather proof canopy, mounted on PCC pedestal, cubical type, front and rear side openable, compartment type with hinged door lighting lugs 2 Nos, earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc and passivated nut, bolts spring and washers and locking arrangement for each compartment, provision of air vent, dust and vermin proof, provision of cable alley with 400 Amps rated aluminium bus bar having 1100 Volts grade slaving and internal connection should be provided with aluminium strips of suitable size and to accommodate and including the following MCCBs duly painted with 2 coats powder coating over a coat of anticorrosive red oxide primer should accommodate the following accessories.
Incomer:
200 Amps, 4 pole MCCB, 36 KA 415V Adj. Thermal & Adj. Magnetic Released - 01 No,
Digital Volt meter 0-500V with inbuilt selector switch - 01 No
Digital Amp meter 0-500A with inbuilt selector switch & CT Coils- 01 No
Set of LED type indicating lamps - 03 No Aluminium Bus Bar 300 Amps TPN
Outgoing:
160 Amps, MCCB 4 ,Pole 25KA 415 V,Adj.Thermal Adjustable type - 01 No
100 Amps, MCCB 4 ,Pole 25KA 415 V,Adj.Thermal Adjustable type - 01 No
MCB DP 40 Amps Outgoing -10 Nos | 1 | Each | - | - |
| 3 | Supply, Installation, Commissioning and testing of transformer of capacity 160 KVA step down outdoor type Copper Wounded ONAN Cooling 11/0.433 KV (at no load) AC 3 Phase 50 Hz on secondary side double wounded oil immersed naturally all air cooled with external tubes/radiator, delta connected as on primary and star connected with neutral brought on secondary. The maximum temperature rise should not exceed 45 degree centigrade in oil and 50 degree centigrade in HV/LV winding when measured by the resistance method after continuous full load run in ambient temperature the transformer shall confirming to IS 2026, 1997 and comprising of following accessories :-
(a) 01 No cable end box on HV side consisting of with 03 Nos porcelain bushing with bushing rods and nuts washers and cable glands suitable for XLPE cable 3 Core 120 Sqmm including cable joint complete adopter box
(b) 01 No cable end box on LV secondary side consisting of 04 Nos porcelain bushing with bushing rods and nuts washers and cable glands suitable for XLPE cable 3.5 Core 185 Sqmm including cable joint complete adopter box
(c) Oil conservator with filter type drain valve and oil level gauge. | 1 | Each | - | - |
| 3.01 | (d) Dehydrating breather with first filling of dehydrating agent.
(e) Explosive vent.
(f) Thermometer Pocket.
(g) Two earthing terminal on tank body to facilitate fixing of 32x6mm GI Strip.
(h) One No thermometer dial type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge max reading panted terminal.
(j) Rating plate with terminal plate.
(k) Oil drain filter valve.
(l) Oil filling hole on top cover with plug.
(m) Air release valve/plug.
(n) 4 Nos plain solid cast steel detachable rollers.
(o) Extra bushing for neutral out side the cable box providing independent earthing for neutral.
(p) First fill of transformer oil confirming to relevant IS and tested upto 60KV dielectric strength. | - | - | - | - |
| 4 | Supplying and laying unreinforced precast concrete cable cover class HVP type 1 with peak, size 300 mm x 180 mm x 40 mm complete all as specified and directed. | 438 | Each | - | - |
| 5 | S&F 3 phase prodigy (Secure) distribution transformer meter with built-in-current transformers, energy audit and system analysis, direct connected 3 Ph 4 Wire 415V with current range 40-200A, accuracy class 1.0, frequency 50 Hz, Insulation Class-Protection Class II, Impulse withstand 10KV, IS-13779, Dimensions (W x H x D) 365 x 283 x 221mm (with extended terminal cover) complete all as specified and directed. | 1 | Each | - | - |
| 6 | M&L for cubical panel (dimension of meter to be fixed in Panel is 365x283x221mm) for 3 Ph Prodigy (Secure) Meter along with connected items like nuts & bolts, screws, binding wire, hold fast for fixing in wall/grouting including XLPE UG cable 95 Sqmm 3.5 Core from transformer to meter and panel complete all as specified and directed.
Note : The quoted rate shall be deemed to be included for connection of LT UG Cable from Transformer to panel and meter | 1 | Each Job | - | - |
| 7 | Supply and Installation Voltage stabilizer copper wound for automatic operation, three phase naturally oil cooled indoor type & designed for input variation between 300 V to 480 V with output voltage stabilized at 415 Volts with accuracy ± 2.5% and speed of correction 8 Volts per second and of capacity 100 KVA complete all as specified and directed. | 2 | Each | - | - |
| 8 | Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 Sq mm 3.5 core complete all as specified and directed. | 190 | RM | - | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.32 MB
Tender36.pdf
Tender Documents • 1.34 MB
BOQ_868210.xls
BOQ • 0.32 MB
Drawing36.pdf
Additional Documents • 0.96 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].