Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.7 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹41.0 L+₹1.3 L (3.33%)Rejected-Finance N A | NEW DELHI | DELHI | 110001 | L2 | Rejected-Finance Rejected due highest rate quoted | |
| 3 | L3₹43.8 L+₹4.1 L (10.3%)Rejected-Finance H NO 90 VILLAGE REWLA KHANPUR PO NAJAFGARH NEW DELHI 110043 | NEW DELHI | WEST DELHI | DELHI | 110043 | L3 | Rejected-Finance Rejected due highest rate quoted | |
| 4 | L4₹44.7 L+₹5.0 L (12.6%)Rejected-Finance | L4 | Rejected-Finance Rejected due highest rate quoted | |
| 5 | L5₹46.0 L+₹6.4 L (16.0%)Rejected-Finance D 35 1ST FLOOR CLOCK TOWER HARI NAGAR NEW DELHI 110064 | WEST | DELHI | 110064 | L5 | Rejected-Finance Rejected due highest rate quoted |
Tender Value
₹48.5 L
EMD Value
₹97,000
Closing Date
3 Feb 2024, 6:00 pmClosed
GE (AF) GURGAON
GE (AF) GURGAON
SPECIAL REPAIR TO LT OVERHEAD DISTRIBUTION SYSTEM INCLUDING REPLACEMENT OF LT PANELS AND ALLIED WORKS AT SMQs AREA AT AF STN ARJANGARH UNDER GE AF GURGAON
2024_MES_636148_1
GE/GUR-/NIT-61/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
GE (AF) GURGAON
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) GURGAON
₹97,000
1 Apr 2024
6 Jan 2024
5 Feb 2024
6 Jan 2024
3 Feb 2024
20 Jan 2024
Amount
Dismantling of ACSR or AAC conductor of any description or size complete all as specified and as directed.
Dismantling cross arms of MS channel or angle sections etc complete and setting/stacking for reuse or to be issued under credit complete all as specified and as directed.
Disamntling insulators any type any size complete all as specified and as directed.
Dismatling earth wire or copper conductor , service feedre or distribution span complete all as specified and as directed.
Supply, installation, testing and commissioning of CPRI approved Outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , floor mounted weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame,with 3.15 mm thick CRCA sheet load bearing members and load bearing members such as door partitions etc of thick not less than 2.0 mm thick , with gland paltes at bottom with suitable Brass chromium plated glands, with locking arrangements complete, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -06 nos on incoming side and ON/OFF/TRIP indications on outgoing side of breaker, interconnections from bus bars to MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and as directed and comprising of the following :- (Panel No. 1)
(a) Bus bar Aluminium - 1200 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves.
(b) MCCB 630 Amps, 50 Hz, 415 V with rupturing capacity 50 KA, Adjustable Thermal Mangnetic range -01 No Main incomer
(c) MCCB 200 Amps 3 pole 36 KA, with adjustable thermal magnetic range as out going- 05 Nos. (for panel No. 2, 3 , 4, 5 & 6)
(d) MCCB 125 Amps 3 pole 16 KA with adjustable thermal magnetic range as out going- 02 Nos. (for spare)
(e) MCCB 100 Amps 3 pole 16 KA with adjustable thermal magnetic range as out going- 01 No. (Spare)
(f) MCCB 63 Amps 3 pole 16 KA with adjustable thermal magnetic range as out going- 03 Nos. (Spare)
(g) MCB TP 63 Amps, 10 KA, 'C Series- 03 Nos
(h) MCB SPN 40 Amps, 10 KA, 'B' Series - 03 Nos
(j) Digital multifuctional meter (Make : L&T), 4410 Series, Cat No. WL441010OOOO- 01 No or equivalent out of makes spd in list of makes.
(k) ON/OFF indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 9 Set of three
Supply, installation, testing and commissioning of CPRI approved Outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , floor mounted weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame,with 3.15 mm thick CRCA sheet load bearing members and load bearing members such as door partitions etc of thick not less than 2.0 mm thick , with gland paltes at bottom with suitable Brass chromium plated glands, with locking arrangements complete, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -06 nos on incoming side and ON/OFF/TRIP indications on outgoing side of breaker, interconnections from bus bars to MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and as directed and comprising of the following :- (Panel No. 3)
(a) Bus bar Aluminium - 500 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves.
(b) MCCB 200 Amps 4 pole 36 KA, with adjustable thermal magnetic range as out going- 01 No.(Main incomer)
(c) MCCB 63 Amps 3 pole 16 KA with adjustable thermal magnetic range as out going- 05 Nos. (For Block No. 54 to 57 and 01 No Spare)
(d) MCB TP 63 Amps, 10 KA, 'C Series- 03 Nos
(e) MCB SPN 40 Amps, 10 KA, 'B' Series - 03 Nos
(f) Digital multifuctional meter (Make : L&T), 4410 Series, Cat No. WL441010OOOO- 01 No or equivalent out of makes spd in list of makes.
(g) ON/OFF indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 6 Set of three
Supply, installation, testing and commissioning of CPRI approved Outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , floor mounted weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame,with 3.15 mm thick CRCA sheet load bearing members and load bearing members such as door partitions etc of thick not less than 2.0 mm thick , with gland paltes at bottom with suitable Brass chromium plated glands, with locking arrangements complete, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -06 nos on incoming side and ON/OFF/TRIP indications on outgoing side of breaker, interconnections from bus bars to MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and as directed and comprising of the following :- (Panel No. 4)
(a) Bus bar Aluminium - 500 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves.
(b) MCCB 200 Amps 4 pole 36 KA, with adjustable thermal magnetic range as out going- 01 No.(Main incomer)
(c) MCCB 63 Amps 3 pole 16 KA with adjustable thermal magnetic range as out going- 08 Nos. (For Block No. 59 to 65 and 01 No Spare)
(d) MCB TP 63 Amps, 10 KA, 'C Series -03 Nos
(e) MCB SPN 40 Amps, 10 KA, 'B' Series - 03 Nos
(f) Digital multifuctional meter (Make : L&T), 4410 Series, Cat No. WL441010OOOO- 01 No or equivalent out of makes spd in list of makes.
(g) ON/OFF indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 9 Set of three
Supply, installation, testing and commissioning of CPRI approved Outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , floor mounted weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame,with 3.15 mm thick CRCA sheet load bearing members and load bearing members such as door partitions etc of thick not less than 2.0 mm thick , with gland paltes at bottom with suitable Brass chromium plated glands, with locking arrangements complete, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -06 nos on incoming side and ON/OFF/TRIP indications on outgoing side of breaker, interconnections from bus bars to MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and as directed and comprising of the following :- (Panel No. 5)
(a) Bus bar Aluminium - 500 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves.
(b) MCCB 200 Amps 4 pole 36 KA, with adjustable thermal magnetic range as out going- 01 No.(Main incomer)
(c) MCCB 63 Amps 3 pole 16 KA with adjustable thermal magnetic range as out going- 06 Nos. (For Block No. 42 to 45, T-16 and 01 No Spare)
(d) MCB TP 63 Amps, 10 KA, 'C Series- 03 Nos
(e) MCB SPN 40 Amps, 10 KA, 'B' Series- 03 Nos
(f) Digital multifuctional meter (Make : L&T), 4410 Series, Cat No. WL441010OOOO- 01 No or equivalent out of makes spd in list of makes.
(g) ON/OFF indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 7 Set of three
Supply, installation, testing and commissioning of CPRI approved Outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , floor mounted weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame,with 3.15 mm thick CRCA sheet load bearing members and load bearing members such as door partitions etc of thick not less than 2.0 mm thick , with gland paltes at bottom with suitable Brass chromium plated glands, with locking arrangements complete, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -06 nos on incoming side and ON/OFF/TRIP indications on outgoing side of breaker, interconnections from bus bars to MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and as directed and comprising of the following :- (Panel No. 6)
(a) Bus bar Aluminium - 500 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves.
(b) MCCB 200 Amps 4 pole 36 KA, with adjustable thermal magnetic range as out going- 01 No.(Main incomer)
(c) MCCB 63 Amps 3 pole 16 KA with adjustable thermal magnetic range as out going- 10 Nos. (For Block No. 46 to 53, T-15 and 01 No Spare)
(d) MCB TP 63 Amps, 10 KA, 'C Series- 03 Nos
(e) MCB SPN 40 Amps, 10 KA, 'B' Series- 03 Nos
(f) Digital multifuctional meter (Make : L&T), 4410 Series, Cat No. WL441010OOOO- 01 No or equivalent out of makes spd in list of makes.
(g) ON/OFF indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 11 Set of three
Supply, installation, testing and commissioning of CPRI approved Outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , floor mounted weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame,with 3.15 mm thick CRCA sheet load bearing members and load bearing members such as door partitions etc of thick not less than 2.0 mm thick , with gland paltes at bottom with suitable Brass chromium plated glands, with locking arrangements complete, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -06 nos on incoming side and ON/OFF/TRIP indications on outgoing side of breaker, interconnections from bus bars to MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and as directed and comprising of the following :- (Panel No. 7)
(a) Bus bar Aluminium - 600 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves.
(b) MCCB 315 Amps 4 pole 36 KA, with adjustable thermal magnetic range as out going- 01 No.(Main incomer)
(c) MCCB 160 Amps 3 pole 25 KA with adjustable thermal magnetic range as out going- 01 Nos. (For Panel No. 8)
(d) MCCB 63 Amps 3 pole 16 KA with adjustable thermal magnetic range as out going- 07 Nos. (For Block No. 99 to 103, Beauty parlour and 01 No Spare)
(e) MCB TP 63 Amps, 10 KA, 'C Series- 03 Nos
(f) MCB SPN 40 Amps, 10 KA, 'B' Series- 03 Nos
(g) Digital multifuctional meter (Make : L&T), 4410 Series, Cat No. WL441010OOOO- 01 No or equivalent out of makes spd in list of makes.
(h) ON/OFF indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 9 Set of three
Supply, installation, testing and commissioning of CPRI approved Outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , floor mounted weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame,with 3.15 mm thick CRCA sheet load bearing members and load bearing members such as door partitions etc of thick not less than 2.0 mm thick , with gland paltes at bottom with suitable Brass chromium plated glands, with locking arrangements complete, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -06 nos on incoming side and ON/OFF/TRIP indications on outgoing side of breaker, interconnections from bus bars to MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's complete all as specified and as directed and comprising of the following :- (Panel No. 8)
(a) Bus bar Aluminium -400 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves.
(b) MCCB Amps 160 Amps 4 pole 25 KA, with adjustable thermal magnetic range as out going- 01 No.(Main incomer)
(c) MCCB 63 Amps 3 pole 16 KA with adjustable thermal magnetic range as out going- 07 Nos. (For Block No. 104 to 109 and Play shcool and 01 No Spare)
(d) MCB TP 63 Amps, 10 KA, 'C Series- 03 Nos
(e) MCB SPN 40 Amps, 10 KA, 'B' Series- 03 Nos
(f) Digital multifuctional meter (Make : L&T), 4410 Series, Cat No. WL441010OOOO- 01 No or equivalent out of makes spd in list of makes.
(g) ON/OFF indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 8 Set of three
Supply, installation, testing and commissioning of CPRI approved Outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , floor mounted weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame,with 3.15 mm thick CRCA sheet load bearing members and load bearing members such as door partitions etc of thick not less than 2.0 mm thick , with gland paltes at bottom with suitable Brass chromium plated glands, with locking arrangements complete, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -06 nos on incoming side and ON/OFF/TRIP indications on outgoing side of breaker, interconnections from bus bars to MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's (INCLUDING TAKING DOWN EXISTING PANEL) complete all as specified and as directed and comprising of the following :- (Panel No. 14)
(a) Bus bar Aluminium -800 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves.
(b) MCCB Amps 400 Amps 4 pole 36 KA, with adjustable thermal magnetic range as out going- 01 No.(Main incomer)
(c) MCCB 125 amps 3 pole 25 KA with adjustable thermal magnetic range as out going- 05 Nos. (For Panel No. 13 & 16) and 02 Spare
(d) MCCB 63 Amps 3 pole 16 KA with adjustable thermal magnetic range as out going- 01 Nos. (Spare)
(e) MCB TP 63 Amps, 10 KA, 'C Series- 03 Nos
(f) MCB SPN 40 Amps, 10 KA, 'B' Series- 03 Nos
(g) Digital multifuctional meter (Make : L&T), 4410 Series, Cat No. WL441010OOOO- 01 No or equivalent out of makes spd in list of makes.
(h) ON/OFF indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 8 Set of three
Supply, installation, testing and commissioning of CPRI approved Outdoor type LT panel board suitable for 440 Volt, 3 phase & Neutral , 50Hz supply , floor mounted weather and vermin proof fabricated from MS angle of size 50x50x5 mm as base frame,with 3.15 mm thick CRCA sheet load bearing members and load bearing members such as door partitions etc of thick not less than 2.0 mm thick , with gland paltes at bottom with suitable Brass chromium plated glands, with locking arrangements complete, duly powder coated with siemens grey colour after chemical treatment, including LED RYB indicators -06 nos on incoming side and ON/OFF/TRIP indications on outgoing side of breaker, interconnections from bus bars to MCCB's with suitable size aluminium bus bars, all internal ckt / protection wiring with FRHR 1100 V grade wiring with MCB protection,including terminal adapters, spreader links on incoming and out going sides of MCCB's (INCLUDING TAKING DOWN EXISTING PANEL) complete all as specified and as directed and comprising of the following :-
(a) Bus bar Aluminium - 600 A capacity- 04 Nos high conductivity, suitable for 415 V, 50 Hz supply including interconnection from incoming, and out going feeders with suitable mounting insulators, heat shrinkable colour sleeves.
(b) MCCB 400 Amps 4 pole 36 KA, with adjustable thermal magnetic range as in coming - 01 No.
(c) MCCB 63 Amps 3 pole 16 KA with adjustable thermal setting as out going- 09 Nos.
(d) MCB SP 63 Amps, 10 KA, 'B' Series
(e) Digital multifuctional meter (Make : L&T), 4410 Series, Cat No. WL441010OOOO -01 No or equivalent out of makes spd in list of makes.
(f) ON/OFF indication lamp with toggle switch and three Nos indication lamp (R,Y,B) - 01 Set of three
Supply, laying and testing of XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core 400 sq mm complete all as specified and as directed.
Supply, laying and testing of XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core 300 sq mm complete all as specified and as directed.
Supply, laying and testing of XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core 240 sq mm complete all as specified and as directed.
Supply, laying and testing of XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core 185 sq mm complete all as specified and as directed.
Supply, laying and testing of XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core 150 sq mm complete all as specified and as directed.
Supply, laying and testing of XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core 95 sq mm complete all as specified and as directed.
Supply, laying and testing of XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core 50 sq mm complete all as specified and as directed.
Supply, laying and testing of XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 4 core 16 sq mm (FOR SECURITY LIGHTS) complete all as specified and as directed.
Supply, laying and testing of XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 4 core 10 sq mm complete all as specified and as directed. Note for item No. 14 to 22. 1. The rate quoted by the contractor deemed to be inclusive of suitable size aluminium lugs at any required length at both ends of cable. 2. Suitable size of cable chromium plated stainless steel grands etc. 3. Earth work, 75mm thick PCC 1:4:8 type D-2 in foundation and PCC 1:2:4 type B-1 in foundation block shall be measured and paid seperately.
M&L for Cutting existing road surfaces or hard standing 0.45 mtr depth and 0.3 mtr width (22 CM thick comprising bituminous topping) for laying of pipes/cables and making good to the disturbed surfaces to match with existing with PCC 1:2:4 Type B-1 45cm x 25cm over 10cm thick PCC 1:4:8 Type-D2 sub base of same width complete all as specified and as directed. NOTE : Rate quoted by the contractor deemed to be inclusive of PCC 1:2:4 to be required to making good the disturbed surface to match with existing. This option of road crossing shall only be opted were road crossing by drilling method not feasible and with the approval of Engr-in-charge.
M & L for GI tubing (light grade) with all necessary fitting laid in trenches/under road crossing, or fixed on poles/walls/under floor etc complete all as specified and as directed for the following sizes:-
(a) 40 mm dia bore.
(b) 50 mm dia bore.
(c) 80 mm bore
Excavation in trenches in soft/ loose soil not exc. 1.5 metre wide and n'exc. 1.50m deep for pipes and getting out complete all as specified and as directed.
Returning filling including spreading leveling watering and well ramming in layers not exc 25Cm in soft/ loose soil, complete all as specified and as directed.
Removing excavated material in soft/ loose soil n'exc 50M and depositing where directed at a level n'exc1.5M above the starting point, complete all as specified and as directed.
M&L for sand cushning to U/G cable in layers of 23cm thick( 8 Cm before laying the cable and 15Cm thick after laying the cable) in trenches including watering and consolidation, complete all as specified and as directed.
Supply and lay well burnt brick class B as protection to cable in cable trenches complete all as specified and as directed.
M & L for Horizontal drilling hole at a depth upto 1 mtr below the normal ground level of suitable size to insert pipe upto 40-80 mm dia across the road across the horizontal position at different location complete all as specified and as directed.
Supply and fixing TPN DB's 4 way vertical type 415 V, double door suitable for housing of 100 Amps MCCB as main incoming complete all as specified and as directed.
Supply and fixing MCCB 63 Amps, 3 Pole, 16 KA, fixed type, suitable to be fixed in 4 way TPN DB complete all as specified and as directed.
Suply and fixing 240 V, 10 KA, 'B' curve miniature circuit breaker (MCB) of single pole and current carrying capacity SP 40 Amps in the MCB DB complete with connection testing and commissioning complete all as specified and as directed.
S & F sub main wiring for circuit of size 10 sq mm 2 core (FRLS) alongwith earth wire of 6 sq mm single core of FRLS PVC insulated unsheathed cable, 1100 volts grade with multistranded copper conductor including PVC conduit of suitable size complete all as specified and as directed. (FOR SPN DB's)
M & L for Earthing complete for sub station equipments with galvanized steel earth pole electrod of size 600x600x6.3mm thick burried directly in the ground (earth pit not less than 2.25 metre deep below normal ground level) with top edge of plate not less than 1.5 metre below the ground level, connected to galvanised iron strip 25 x 4 mm by means of nuts, bolts,check nuts and washers of galvanised or steel all as specified or shown in electrical plate No. 3 of SSR-2009( Part-l), including ncessary earth work and excavation in any strata, GI pipe 40mm dia light grade for protection of galvanised iron earthing strip upto 7.5 mtrs, including concrete chamber of PCC (1:4:8) type D-2 (using 40mm graded stone aggregate) having copping in PCC (1:3:6) Type C-1using 20mm graded stonr aggregate. Intemal surface of concrete chamber shall be plastered with 12mm thick cement mortar (1;4) and 50mm thick RCC cover in proportion (1:2:4) type B-1using 20mm graded stone aggregate, reinforced with 8mm dia tor bar@ 80mm c/c both ways and charcoale dust common salt etc.,funnel testing point, 8 mesh per liner inch, including test point , testing, complete all as specified and as directed.
S & F pole box for street light dust and vermin proof with hinged door and locking arrangement make Sintex model GSJB 3020 complete with 4 way connector 2 Nos. of capacity 60 amps incl one MCB SP C series 06 amps 10 KA capacity for Security light connection with flexIble wire 3 core 2.5 sqmm with suitable size of PVC conduit and including suitable clamps & suitable size brass chrome plated glands-02 nos at bottom for cable entry and exit complete all as specified and as directed.
M&L for PCC 1:2:4 Type B-1 using 20mm graded stone aggregate as in foundation of panels of size area of panel in plan x 300mm below GL & 300mm above GL including form work complete all as specified and as directed.
M&L for 75mm thick PCC 1:4:8 Type D-2 using 40mm graded stone aggregate as in foundation of panels of size area of panel in plan and extended 10cm all sides complete all as specified and as directed.
M&L for Cross-arms, Bracings, Supports, Clamps and Back Plates fabricated from Structural Steel Sections including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed and inclusive of one coat of Aluminium Primer one Under Coat and One Finishing Coat of Aluminium Paint, complete all as specified and as directed. (for loop boxes and fixing of GI pipe with pole).
M/S Rohit Enterprises
Ish Engineers and Contractors
DHARAMRAJ BUILDERS & ENGINEERS
M/s Navansh Engineers & Consultants
M/S Anand Enterprises
Commercial Traders
UNITED ENGINEERING CORPORATION
RAVINDRA BROTHERS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .