Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
Tender Value
₹5.7 L
EMD Value
₹11,300
Closing Date
20 Mar 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Mr Bharat Singh Laspal, SE, CWE Bhopal
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
REPAIR AND MAINTENANCE OF 33 KV VCBS AT MRS AND ALLIED WORKS UNDER AGE E/M BAIRAGARH UNDER GE BHOPAL
2023_MES_575334_2
83809/E8
Open Tender
Civil Works
Item Rate
180 days
BHOPAL
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹500
Yes
GE BHOPAL
₹11,300
Yes
25 Apr 2023
20 Feb 2023
22 Mar 2023
20 Feb 2023
20 Mar 2023
27 Feb 2023
20 Feb 2023 - 27 Feb 2023
Amount
Testing of over current & earth fault IDMT relays as per time/ current characteristics by secondary injection test at 50%, 75%, 100 % plug setting and operating time at twice the set value & TMS 1 and calibrating including well cleaning and decarbonizing of relay contacts.
Material and Labour for the followings testing of current transformers of any capacity on the site at different locations under the GE and submission of reports to the Engineer-in-Charge including servicing and calibration of current transformers complete all as specified and as directed. (a) Mechanical Check and Visual Inspection (b) Insulation Resistance Test (c) Polarity Test (d) Secondary / Loop Resistance Test (optional test) (e) Burden Test (optional test) (f) Magnetization Curve Test (optional test) (g) Turns ratio Tests (h) Primary Injection Test (i) High Voltage Test
Material & Labour for insulation resistance test, voltage transfomer ratio test, polarity test and winding resistance test of potential transformer of any capacity on the site at different locations under the GE and submission of reports to the Engineer-in-Charge complete all as specified and as directed.
M & L for testing of battery bank panel using battery life cycle tester and measuring starting voltage, end voltage, starting time, end time, test current, charge in AH, charge in WH, ambient temperature, battery temperature, capacity in AH, capacity in WH, watt-hour efficiency, ampere-hour efficiency, loss of capacity, cyclic efficiency and submission of reports to the Engineer-in-Charge including addition of distilled water, putting white jelly on terminal, checking PCB, circuit and replacing and defective parts complete all as specified and as directed.
Cleaning of complete remote panel, tightening and checking of control wiring, visual inspection of any defects, measuring insulation resistance value and rectifying defects including wires, lugs, ferrule, terminals complete all s specified and as directed.
S & F spring charging gear motor for 33 kV VCB of Areva Make and as per the existing complete all as specified and as directed.
S & F spring charging handle for 33 kV VCB of Areva Make and as per the existing complete all as specified and as directed.
S & F in repairs TNC (Trip Neutral Close) switch suitable for 33 kV VCB panel of battery capacity 12 V, 180 AH, emergency stop button including indication lamp with necessary electrical connections and as per the existing complete all as specified and as directed.
S & F push button (ON & OFF) for control panel of 33 kV VCB and as per the existing complete all as specified and as directed.
S & F indicator lamp for VCB pane of 33 kV VCB and as per the existing complete all as specified and as directed.
S & F buzzer for remote relay for VCB pane of 33 kV VCB and as per the existing complete all as specified and as directed.
S & F auxiliary switch with replacement of complete existing wiring, 8/ 12 way, outdoor type for VCB pane of 33 kV VCB and as per the existing complete all as specified and as directed.
S & F trip coil assembly (30 V DC) for VCB pane of 33 kV VCB and as per the existing complete all as specified and as directed.
S & F tripping mechanism for VCB pane of 33 kV VCB and as per the existing complete all as specified and as directed.
S & F closing coil assembly for VCB pane of 33 kV VCB and as per the existing complete all as specified and as directed.
S & F closing mechanism assembly for VCB pane of 33 kV VCB and as per the existing complete all as specified and as directed.
S & F spring charging mechanism for VCB pane of 33 kV VCB and as per the existing complete all as specified and as directed.
S & F tripping spring for VCB panel of 33 kV VCB and as per the existing complete all as specified and as directed.
S & F closing spring for VCB panel of 33 kV VCB and as per the existing complete all as specified and as directed.
S & F in repairs single core flexible conductor FR-LSH cables, PVC insulation of type D and having PVC sheath of type ST3, 4 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor for CT wiring complete all as specified and as directed.
S & F in repairs two core flexible conductor FR-LSH cables, PVC insulation of type D and having PVC sheath of type ST3, 10 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor for wiring from battery bank to control panel complete all as specified and as directed.
S & F in repairs eight core flexible conductor FR-LSH cables, PVC insulation of type D and having PVC sheath of type ST3, 2.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor for control panel wiring complete all as specified and as directed.
M & L for earthing complete with copper plate earth electrode 600 mm X 600 mm X 3.15 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 20 mm X 3 mm copper strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
S & F in repairs earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20 mm X 3 mm copper strip complete all as specified and as directed.
S &F in repair small and big gear assembly for spring charging mechanism for outdoor type VCB of make CROMPTON GREAVES of rating voltage 36 KV ,breaking capacity 26.3 KA ,current rating 400 Amp,short time current 26.3 KA for 1 sec,frequency 50 Hz complete all as specified and as directed.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .