Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹69.6 LAdmitted-Finance | ₹69.6 L | L1 | Admitted-Finance |
| 2 | L2₹75.5 L+₹5.9 L (8.55%)Admitted-Finance | ₹75.5 L+₹5.9 L (8.55%) | L2 | Admitted-Finance |
| 3 | L3₹81.1 L+₹11.5 L (16.5%)Admitted-Finance | ₹81.1 L+₹11.5 L (16.5%) | L3 | Admitted-Finance |
| 4 | L4₹86.7 L+₹17.1 L (24.6%)Admitted-Finance | ₹86.7 L+₹17.1 L (24.6%) | L4 | Admitted-Finance |
| 5 | L5₹93.6 L+₹24.0 L (34.5%)Admitted-Finance | ₹93.6 L+₹24.0 L (34.5%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | B.K. ELECTRICALS L3 | RAJESH GAWDE L2 | DYNAMIC ENGINEERS AND CONTRACTORS L4 | FLASHCUNSULTANT & CONTRACTOR L5 | SANIDHYA ENTERPRISES L1 |
|---|---|---|---|---|---|---|---|---|
| 1.00Supply, Installation, Testing & Commissioning of energy efficient LED outdoor luminaires suitable for street.perimeter lighting, shall be supplied alongwith necessary accessories, BIS certified potted driver & required fixing/installation hardware, metallic powder coated/G.I. mounting bracket. Specifications to be read in conjuction with detailed description of item and as shall be intalled as per directions from Engineer-in-charge. Note: 1. The design of illumination shall be done by OEM of luminaire @ avg. 15 Lux for the boundary wall/fencing area & same shall be submitted for approval. 2. The performance (Electrical & mechanical) of the luminaires shall be WARRANTEED for a period of minimum 5 Years from the date of commissioning. 3. Additional Security deposit amount @ 10% of total value of this item shall be withheld by the department for a period of 5 years from the date of completion of work. 4. The technical datasheet along with LM-79, LM-80 & LED driver reports issued from NABL accredited lab for all the luminaires shall be submitted for approval. | ||||||||
| 1.10 | LED street light luminaire: The specifications/desired parameters are as follows:
Type of installation: Pole arm mountable
Housing material : High pressure aluminium die cast housing , glass cover
Nominal Lumen output & overall lumen efficacy: 6000 lumen, >130 lumen/watt,
Correlated Colour Tempreture(CCT): 4000/5700K, pf ≥ 0.95 (min),
CoIor Rendering Index(CRI) ≥ 70,
IP: 66, IK: 08,
Surge protection level ≥ 4 kV internal, ≥ 10 kV external,
THD ≤ 10 %
Beam angle ≥ 120°,
Life class: L70B50 @ 50 K hrs or better. | 179 | Nos. | 2,025 ₹3,62,475 Lowest | 2,285 ₹4,09,015 | 3,628 ₹6,49,412 | 2,350 ₹4,20,650 | 4,000 ₹7,16,000 |
| 1.20 | LED Street light luminaire: The specifications/desired parameters are as follows:
Type of installation: Pole arm mountable
Housing material : High pressure aluminium die cast housing , glass cover
Nominal Lumen output & overall lumen efficacy: 9000 lumen, >130 lumen/watt,
Correlated Colour Tempreture(CCT): 4000/5700K, pf ≥ 0.95 (min),
CoIor Rendering Index(CRI) ≥ 70,
IP: 66, IK: 10,
Surge protection level ≥ 4 kV internal, ≥ 10 kV external,
THD ≤ 10 %
Beam angle ≥ 120°,
Life class: L70B50 @ 50 K hrs or better. | 4 | Nos. | 3,450 ₹13,800 Lowest | 4,022 ₹16,088 | 4,891 ₹19,564 | 3,470 ₹13,880 | 4,000 ₹16,000 |
| 1.30 | LED street light luminaire: The specifications/desired parameters are as follows:
Type of installation: Street light pole arm mountable
Housing material : High pressure aluminium die cast housing , glass cover
Nominal Lumen output & overall lumen efficacy: 16000 lumen, >130 lumen/watt,
Correlated Colour Tempreture(CCT): 4000/5700K, pf ≥ 0.95 (min),
CoIor Rendering Index(CRI) ≥ 70,
IP: 66, IK: 10,
Surge protection level ≥ 4 kV internal, ≥ 10 kV external,
THD ≤ 10 %
Beam angle ≥ 120°,
Life class: L70B50 @ 50 K hrs or better. | 8 | Nos. | 5,200 ₹41,600 | 5,308 ₹42,464 | 6,348 ₹50,784 | 5,097 ₹40,776 Lowest | 6,000 ₹48,000 |
| 1.40 | LEDTop Post luminaire: The specifications/desired parameters are as follows:
Type of installation: Pole top post
Mounting: on existing pole
Housing material : High pressure aluminium die cast housing , poly carbonate optical cover
Nominal Lumen output & overall lumen efficacy: 4500 lumen, >100 lumen/watt,
Correlated Colour Tempreture(CCT): 4000/5700K, pf ≥ 0.95 (min),
CoIor Rendering Index(CRI) ≥ 70,
IP: 66, IK: 10,
Surge protection level ≥ 4 kV internal,
THD ≤ 10 %
Symmentry: Asymmetrical,
Life class: L70B50 @ 50 K hrs or better. | 12 | Nos. | 7,500 ₹90,000 | 8,395 ₹1,00,740 | 8,136 ₹97,632 | 7,300 ₹87,600 | 6,000 ₹72,000 Lowest |
| 1.50 | Retrofitting of conventional street light/top post with LED Top post luminaire on existing pole: The specifications/desired parameters are as follows:
Type of installation: Pole top post
Mounting: on existing pole
Housing material : High pressure aluminium die cast.
Nominal Lumen output & overall lumen efficacy: 4500 lumen, >100 lumen/watt,
Correlated Colour Tempreture(CCT): 4000/5700K, pf ≥ 0.95 (min),
CoIor Rendering Index(CRI) ≥ 70,
IP: 66, IK: 08,
Surge protection level ≥ 4 kV internal
THD ≤ 10 %
Symmentry: Asymmetrical,
Life class: L70B50 @ 50 K hrs or better.
Exsiting old luminare shall be removed and shifted to stores at RRCAT. | 50 | Nos. | 7,500 ₹3,75,000 | 8,395 ₹4,19,750 | 8,136 ₹4,06,800 | 7,650 ₹3,82,500 | 6,000 ₹3,00,000 Lowest |
| 2.00Supply, erection and installation of octagonal G.I. pole alongwith welded base plate and foundation bolts for street light: 5 metre length GI Octagonal Pole with overhang arm decorative bracket of following sizes with angle of tilt as per the Luminaire OEM design. The G.I. structure shall be continuously tapered having 3 mm thickness throughout the length of the pole. The bottom diameter shall be 130 mm and top diameter shall be 70 mm. The base plate size shall be 200x200x12 mm and 4 Nos. 16 mm diameter 600 mm long J type anchor bolts. The door for control gear and cable jointing shall be flush with pole external surface and shall provide easy access for electrical connections, earthing of pole shall be done with earth driven rod and GI wire/strip as per detailed specification. The scope includes excavation in groud work, supply of material and preparation of RCC foundation, min two (02) 50 mm dia HDPE pipes inserted for cable entries, 6A, SP (Ics ≥ 10 kA) MCB, heavy duty 16A-4 pole connector for cable end terminations and 3Core x1.5 sqmm FR PVC insulated flexible cables for inside connection are included in the scope of this item. Detailed description of item and direction of engineer in charge shall be referred. | ||||||||
| 2.10 | GI Octagonal pole with 1metre double/differential arm decorative Bracket (single/separate mounting) bracket & complete with foundation, base plate, anchor bolts & all required accessories & G.I. hardware. | 36 | Set | 26,000 ₹9,36,000 | 19,980 ₹7,19,280 | 25,000 ₹9,00,000 | 27,650 ₹9,95,400 | 15,000 ₹5,40,000 Lowest |
| 2.20 | GI Octagonal pole with 1 metre single arm decorative bracket & complete with foundation, base plate, anchor bolts & all required accessories & hardware | 156 | Set | 23,300 ₹36,34,800 | 17,713 ₹27,63,228 | 22,500 ₹35,10,000 | 27,100 ₹42,27,600 | 14,000 ₹21,84,000 Lowest |
| 3.00 | Design, Fabrication, Supply, Installation, Testing & Commissioning of 4 meter Height (from FGL) Street Light Pole (50 mm dia GI pipe) for mounting of top post LED outdoor light Luminaire as per our tender specifications & tender drawing. The design & construction of pole mounting / foundation, Powder coated MS pole box & other required material & hardware for installation of the Street Light Pole are also included in the scope of this item. | 12 | Nos. | 16,500 ₹1,98,000 | 18,920 ₹2,27,040 | 20,000 ₹2,40,000 | 15,200 ₹1,82,400 | 14,500 ₹1,74,000 Lowest |
Tender Value
₹82.4 L
EMD Value
₹1.6 L
Closing Date
4 May 2026, 3:30 pmClosed
Chief Engineer, RRCAT, Indore
Office of Chief Engineer, RRCAT, Indore- 452013
Providing illumination for perimeter at RRCAT, Indore
2026_RRCAT_904939_1
RRCAT/E/2026/01 dated 06.04.2026
Open Tender
Electrical Works
Works
240 days
RRCAT
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹1.6 L
30 Jun 2026
9 Apr 2026
8 May 2026
9 Apr 2026
4 May 2026
13 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Installation, Testing & Commissioning of energy efficient LED outdoor luminaires suitable for street.perimeter lighting, shall be supplied alongwith necessary accessories, BIS certified potted driver & required fixing/installation hardware, metallic powder coated/G.I. mounting bracket. Specifications to be read in conjuction with detailed description of item and as shall be intalled as per directions from Engineer-in-charge. Note: 1. The design of illumination shall be done by OEM of luminaire @ avg. 15 Lux for the boundary wall/fencing area & same shall be submitted for approval. 2. The performance (Electrical & mechanical) of the luminaires shall be WARRANTEED for a period of minimum 5 Years from the date of commissioning. 3. Additional Security deposit amount @ 10% of total value of this item shall be withheld by the department for a period of 5 years from the date of completion of work. 4. The technical datasheet along with LM-79, LM-80 & LED driver reports issued from NABL accredited lab for all the luminaires shall be submitted for approval. | |||||
| 1.1 | LED street light luminaire: The specifications/desired parameters are as follows:
Type of installation: Pole arm mountable
Housing material : High pressure aluminium die cast housing , glass cover
Nominal Lumen output & overall lumen efficacy: 6000 lumen, >130 lumen/watt,
Correlated Colour Tempreture(CCT): 4000/5700K, pf ≥ 0.95 (min),
CoIor Rendering Index(CRI) ≥ 70,
IP: 66, IK: 08,
Surge protection level ≥ 4 kV internal, ≥ 10 kV external,
THD ≤ 10 %
Beam angle ≥ 120°,
Life class: L70B50 @ 50 K hrs or better. | 179 | Nos. | - | - |
| 1.2 | LED Street light luminaire: The specifications/desired parameters are as follows:
Type of installation: Pole arm mountable
Housing material : High pressure aluminium die cast housing , glass cover
Nominal Lumen output & overall lumen efficacy: 9000 lumen, >130 lumen/watt,
Correlated Colour Tempreture(CCT): 4000/5700K, pf ≥ 0.95 (min),
CoIor Rendering Index(CRI) ≥ 70,
IP: 66, IK: 10,
Surge protection level ≥ 4 kV internal, ≥ 10 kV external,
THD ≤ 10 %
Beam angle ≥ 120°,
Life class: L70B50 @ 50 K hrs or better. | 4 | Nos. | - | - |
| 1.3 | LED street light luminaire: The specifications/desired parameters are as follows:
Type of installation: Street light pole arm mountable
Housing material : High pressure aluminium die cast housing , glass cover
Nominal Lumen output & overall lumen efficacy: 16000 lumen, >130 lumen/watt,
Correlated Colour Tempreture(CCT): 4000/5700K, pf ≥ 0.95 (min),
CoIor Rendering Index(CRI) ≥ 70,
IP: 66, IK: 10,
Surge protection level ≥ 4 kV internal, ≥ 10 kV external,
THD ≤ 10 %
Beam angle ≥ 120°,
Life class: L70B50 @ 50 K hrs or better. | 8 | Nos. | - | - |
| 1.4 | LEDTop Post luminaire: The specifications/desired parameters are as follows:
Type of installation: Pole top post
Mounting: on existing pole
Housing material : High pressure aluminium die cast housing , poly carbonate optical cover
Nominal Lumen output & overall lumen efficacy: 4500 lumen, >100 lumen/watt,
Correlated Colour Tempreture(CCT): 4000/5700K, pf ≥ 0.95 (min),
CoIor Rendering Index(CRI) ≥ 70,
IP: 66, IK: 10,
Surge protection level ≥ 4 kV internal,
THD ≤ 10 %
Symmentry: Asymmetrical,
Life class: L70B50 @ 50 K hrs or better. | 12 | Nos. | - | - |
| 1.5 | Retrofitting of conventional street light/top post with LED Top post luminaire on existing pole: The specifications/desired parameters are as follows:
Type of installation: Pole top post
Mounting: on existing pole
Housing material : High pressure aluminium die cast.
Nominal Lumen output & overall lumen efficacy: 4500 lumen, >100 lumen/watt,
Correlated Colour Tempreture(CCT): 4000/5700K, pf ≥ 0.95 (min),
CoIor Rendering Index(CRI) ≥ 70,
IP: 66, IK: 08,
Surge protection level ≥ 4 kV internal
THD ≤ 10 %
Symmentry: Asymmetrical,
Life class: L70B50 @ 50 K hrs or better.
Exsiting old luminare shall be removed and shifted to stores at RRCAT. | 50 | Nos. | - | - |
| 2Supply, erection and installation of octagonal G.I. pole alongwith welded base plate and foundation bolts for street light: 5 metre length GI Octagonal Pole with overhang arm decorative bracket of following sizes with angle of tilt as per the Luminaire OEM design. The G.I. structure shall be continuously tapered having 3 mm thickness throughout the length of the pole. The bottom diameter shall be 130 mm and top diameter shall be 70 mm. The base plate size shall be 200x200x12 mm and 4 Nos. 16 mm diameter 600 mm long J type anchor bolts. The door for control gear and cable jointing shall be flush with pole external surface and shall provide easy access for electrical connections, earthing of pole shall be done with earth driven rod and GI wire/strip as per detailed specification. The scope includes excavation in groud work, supply of material and preparation of RCC foundation, min two (02) 50 mm dia HDPE pipes inserted for cable entries, 6A, SP (Ics ≥ 10 kA) MCB, heavy duty 16A-4 pole connector for cable end terminations and 3Core x1.5 sqmm FR PVC insulated flexible cables for inside connection are included in the scope of this item. Detailed description of item and direction of engineer in charge shall be referred. | |||||
| 2.1 | GI Octagonal pole with 1metre double/differential arm decorative Bracket (single/separate mounting) bracket & complete with foundation, base plate, anchor bolts & all required accessories & G.I. hardware. | 36 | Set | - | - |
| 2.2 | GI Octagonal pole with 1 metre single arm decorative bracket & complete with foundation, base plate, anchor bolts & all required accessories & hardware | 156 | Set | - | - |
| 3 | Design, Fabrication, Supply, Installation, Testing & Commissioning of 4 meter Height (from FGL) Street Light Pole (50 mm dia GI pipe) for mounting of top post LED outdoor light Luminaire as per our tender specifications & tender drawing. The design & construction of pole mounting / foundation, Powder coated MS pole box & other required material & hardware for installation of the Street Light Pole are also included in the scope of this item. | 12 | Nos. | - | - |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tendernotice_1.pdf
PDF • 1.11 MB
PosttopPoleDrawings.pdf
Tender Documents • 0.05 MB
5mtrGIPolereferenceDrawingwithfoundation.pdf
Tender Documents • 0.86 MB
BOQ_951175.xls
BOQ • 0.33 MB
GTPformat.pdf
Tender Documents • 0.43 MB
NoticeInvitingTender.pdf
Tender Documents • 1.10 MB
SalientGoverningFeatures.pdf
Tender Documents • 1.89 MB
ScheduleA.pdf
Tender Documents • 0.66 MB
ScheduleB.pdf
Tender Documents • 0.41 MB
ConditionClauseofContract.PDF
Tender Documents • 1.64 MB
TenderSpecifications.pdf
Tender Documents • 0.74 MB
PreferredmakesofMaterial.pdf
Tender Documents • 0.60 MB
SpecialConditionsforWork.pdf
Tender Documents • 0.61 MB
BiddingCapacityFormat.pdf
Tender Documents • 0.25 MB
BidderBankDetailsFormat.pdf
Tender Documents • 0.49 MB
Corrigendumdated24042026.pdf
PDF • 0.05 MB
Corrigendumdated24042026.pdf
PDF • 0.05 MB
Corrigendum1.pdf
PDF • 0.08 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .