| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹74.7 LAccepted-AOC B 56 LANE NO 4A SECTOR 7 VASHNAVI ENCLAVE CHANNI HIMAT JAMMU 180015 | JAMMU | JAMMU AND KASHMIR | 180015 | ₹74.7 L | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹77.6 LRejected-Finance | ₹77.6 L | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 3 | L3₹77.9 LRejected-Finance 135 CHAKRANA TIWARI CHAKA NAINI PRAYAGRAJ 211008 UTTAR PRADESH | PRAYAGRAJ | UTTAR PRADESH | 211008 | ₹77.9 L | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| Sl No | Description | Qty | Unit | vijay builders L3 | KULBHUSHAN AGGARWAL L2 | ANIKET TRADERS L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of step down ,transformer 11KV/433 volts 3 Phase 50 hz 100 KVA New Level-3 outdoor type,with off load tap changing arrangement on HT side to vary secondary voltage upto +5% to -5% in step of 2.5% including suitable cable entry boxes both on HT to upto 120 sqmm 3 core XLPE cable and on low voltage side to acomodate XLPE cable of size upto 120 sqmm 3.5 core complete in all respect with standard accesories and fitment confirming to IS-1180 Part -1 of 2014 amended upto date primary side delta (HT) and secondary side star with neutral (LT) i.e vactor diagram Dyn11.The salient features of transformers are as follows:-
(a) Transformer shall be oil immerse, ON AN cooled , double copper wound , core type with radiator cooled tank complete with first fill of transformer oil as per IS 335 amended upto date and di electric strength more than 60 KV with cooling system.The temperature more than 55 degree centigrade to ambient temp when measured by thermometer for top oil & 40 degree centigrade to ambient for winding when measured with resistance method, when tested in accordance with IS 2026(part 2).transformers shall be painted with PU paint as per relevant IS standards. | 1 | Each | 3,50,000 ₹3,50,000 | 5,00,000 ₹5,00,000 | 3,60,000 ₹3,60,000 |
| 1.01(b) (i)rating and diagram plate will contain all terminal specifications as per IS 1180 (part 1) (ii) earthing terminals 02 nos (ii) Lifting lugs (iv) thermometer pocket (v) air releasing device (vi) tap changer with locking provision (vii) Oil and winding temperature indicator (viii) dehyadration breather fitted with silica gel (ix) Drain cum simpling valve 3"/4 nominl size thread IS 554 steel with plug (x) Pressure relief device on explosion (xi) conservator vent (xii) Bucholtz relay (xiii) Cable entry boxes both primary and secondary side alongwith glands. (c) energy efficiency shall be level III as per IS-1180 amended upto date Note:- Drawing of transformer shall be got approved from GE. | ||||||
| 2.00 | Supply, installation, testing and commissioning of step down ,transformer 11KV/433 volts 3 Phase 50 hz 160 KVA New Level-3 outdoor type,with off load tap changing arrangement on HT side to vary secondary voltage upto +5% to -5% in step of 2.5% including suitable cable entry boxes both on HT to upto 120 sqmm 3 core XLPE cable and on low voltage side to acomodate XLPE cable of size upto 120 sqmm 3.5 core complete in all respect with standard accesories and fitment confirming to IS-1180 Part -1 of 2014 amended upto date primary side delta (HT) and secondary side star with neutral (LT) i.e vactor diagram Dyn11.The salient features of transformers are as follows:- | 1 | Each | 6,50,000 ₹6,50,000 | 7,45,000 ₹7,45,000 | 6,80,000 ₹6,80,000 |
| 2.01(a) Transformer shall be oil immerse, ON AN cooled , double copper wound , core type with radiator cooled tank complete with first fill of transformer oil as per IS 335 amended upto date and di electric strenght more than 60 KV with colling system.The temperature more than 55 degree centigrade to ambient temp when measured by thermometer for top oil & 40 degree centigrade to ambient for winding when measured with resistance method, when tested in accordance with IS 2026 (part 2). transformers shall be painted with PU paint as per relevant IS standards. (b) (i)rating and diagram plate will contain all terminal specifications as per IS 1180 (part 1) (ii) earthing terminals 02 nos (ii) Lifting lugs (iv) thermometer pocket (v) air releasing device (vi) tap changer with locking provision (vii) Oil and winding temperature indicator (viii) dehyadration breather fitted with silica gel (ix) Drain cum simpling valve 3"/4 nominl size thread IS 554 steel with plug (x) Pressure relief device on explosion (xi) conservator vent (xii) Bucholtz relay (xiii) Cable entry boxes both primary and secondary side alongwith glands. (c) energy efficiency shall be level III as per IS-1180 amended upto date Note:- Drawing of transformer shall be got approved from GE. | ||||||
| 3.00 | Supply, installation, testing and commissioning of 250 KVA Compact sub station along with all accessories complete all as specified and directed.
A. HT Section
11KV 630A Three way RMU Non extensible outdoor type (21KA, 3Sec) with 02 Nos Load Break Switch & 1 No SF6 VCB complete with all accesories single core CT ratio 50/1A
RMU ,11KV, 2 No. Load Break Switch + 1No Vaccumm Circuit Breaker (L) altitude upto 1000 meter position Disconnector and Earth Switch
1. Operation of LBS- Manual
2. Load Break switch Rating-11 KV 630A 21 KA
3. External cone threaded M 16 bolted bushings C Type, for cable ends , T Type
4. Cable box provided
5.Capacitor dividers and plug in voltage presence lamps with phase concor dance predisposition.
6. with supply of touch proof termination Kit suitable for CSS having incoming and lopping cable IR*3C*300 sqmm
Function type: 3 position Vacuum circuit breaker in series with 3 positions independent operation disconnector-*outgoing feeder
1.Operation of Vaccum circuit breaker - Motorised
2.Vaccum circuit breaker rating-11 KV 630A 21 KA/3 sec
3. self powered series trip Microprocessor based numerical Over current +Earth fault relay (IDMT+ Inst) for protection
4. Tap Wound Protection current transformer of single core (CTR:50/1A, 2.5VA) for protection
5. Capacitor divider and plug in voltage presence lamps with phase concor dance predisposition.
6.1 No Disconnector switch open close earth
7.1 No Emergency push botton
8. Open/close mechanical indication. | 1 | Each | 23,50,000 ₹23,50,000 | 23,50,000 ₹23,50,000 | 24,00,000 ₹24,00,000 |
| 3.01RMU Accesories:- Manual operation Handle-01 No Standard Manometer Auxiliary relay (3 element) 24DC power pack Acknowledge Push botton 96sqmm Hooter DP MCB 10KA for control | ||||||
| 3.02B. Transformer Section 250 KVA Transformer (Manufactured as per IS 1180 New Level -2) Type: ONAN Oil filled 1. Ratio: 11/.433 KV 2. Capacity: 250 KVA 3. Vector group: Dyn 11, 3 Phase 4. Off load Tap link: +5% to -10% in steps of 2.5% 5. Winding copper 6. Corrugated Type Hearmitically sealed type 7. Ambient Temperature- 50 Degree C 8.Average Temperature rise in the winding over ambient temperature 40 deg C measured by resistance method -95 Deg C 9.Bulb Holder 10. Door Limit Switch | ||||||
| 3.03C. LT Section: a. Transformer- Incommer 400A FP Manual fixed type MCCB 50KA Microprocessor Based with OC SC EF Digital Ammeter & Voltmeter Digital Multifunction meter CT s 400/5A Indication Lamps (RYB) Indication Lamps ( ON OFF) Control MCB's Outgoing 100A FP MAnual fixed MCCB 36 KA Indication lamp Control MCB D.Interconnection Interconnection between HT & LT section & Transformer through Al. XLPE 95 cable, Transfromer & LT section through Aluminium Bus Bar. | ||||||
| 4.00 | Supply, install, testing and commissioning of silent type Diesel Engine driven generating set of min 250 KVA capacity 3 phase, 4 wire, 415 V, 1500 RPM conforming to relevant IS Codes, AC power supply with power factor 0.8 coupled directly to alternator mounted on a common ed Plate with sturdy design,Bed plate shall be suitable for mounting on anti viberation mounting system, load factor 0.85, complete with integral acoustic enclosure-sound proof canopy (should have silent features as per latest CPCB IV norms), fuel tank having facility for easy cleaning, Suitable Battery Charging unit incl battery & standard accessories, and at least 2 year warranty. | 1 | Each | 26,50,000 ₹26,50,000 | 24,75,000 ₹24,75,000 | 27,50,000 ₹27,50,000 |
| 4.01(A) ENGINE : Liquid Cooled, electric Self start, 4 Stroke, min 6 cylinders cold starting, Naturaly aspirated /TCI aspirated( as per manufacturer standard), compression ignition, totally enclosed diesel engine , 1500 RPM suitable for 250 KVA alternator under NTP conditions as per ISO 8528 Part-I capable of taking 10% over load for 1 hours in every 12 hours continues running confirming to IS: 10000/10002/ISO 3046/ BS: 649/ BS: 554 amended up to date, the Engine shall consist of the following :- (i) Dynamically balanced fly wheel or as per manufacturer's standard (ii) Coolant cooling system complete (iii) Air cleaner as per manufacturer's standard (iv) Fuel injectors and fuel pump as per manufacturer's standard (v) Electronic governor as per manufacturer's standard to maintain engine speed at all conditions of load (vi) Fuel service tank of suitable capacity fabricated from MS sheet with, inlet outlet connections, air vent tap,drain plug, Caliberated level indiactor(gauge), MS fuel piping from tank to engine with valves, unions, reducers, flexible hose connections, mounting pedestals, fuel filters incl all as per manufacturer's design. (vii) Dry exhaust manifold with suitable exhaust residential grade, Asbestos rope of suitable size shall be provided as per manufacturer desires for silencer to reduce noise level as per CPCB norms. (viii) Static Battery charging unit suitable for 90 Ah battery/battery array 12/24 volt having float, trickle and boost charging feature. Charging should be from utility supply/generator supply as directed by Engr in charge. (b) one/two battery of total capacity 180 Ah connected with copper lugs and minimum 50 sqmm cable placed inside the acoustic enclosure. (ix) Gear driven oil pump for lubricating oil, priming of engine bearing, as well as fuel systems as per manufacturer's recommendation. (x) Natually aspirated/turbo charger as per manufacturer's standard. (xi) Lubricaton oil coolers and filters with replaceable elements as per manufacturer's standard | ||||||
Tender Value
₹73 L
EMD Value
₹1.5 L
Closing Date
18 Mar 2026, 6:00 pmClosed
HQ CWE AF Jammu
HQ CWE (AF) Jammu Air Force Station Jammu
CA NO CWEAFJ-48/2025-26 SPECIAL REPAIR/REPLACEMENT OF BER TRANSFORMER AND DG SETS AT AF STATION UDHAMPUR UNDER GE (AF) UDHAMPUR
2026_MES_751133_1
CA NO CWEAFJ-48/2025-26
Open Tender
Electrical and Maintenance Works
180 days
UDHAMPUR
As per NIT and Tender Document
9 documents required · 9 mandatory
₹1,000
GE (AF) Udhampur
₹1.5 L
Yes
3 Jul 2026
3 Feb 2026
20 Mar 2026
3 Feb 2026
18 Mar 2026
24 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of step down ,transformer 11KV/433 volts 3 Phase 50 hz 100 KVA New Level-2 outdoor type,with off load tap changing arrangement on HT side to vary secondary voltage upto +5% to -5% in step of 2.5% including suitable cable entry boxes both on HT to upto 120 sqmm 3 core XLPE cable and on low voltage side to acomodate XLPE cable of size upto 120 sqmm 3.5 core complete in all respect with standard accesories and fitment confirming to IS-1180 Part -1 of 2014 amended upto date primary side delta (HT) and secondary side star with neutral (LT) i.e vactor diagram Dyn11.The salient features of transformers are as follows:-
(a) Transformer shall be oil immerse, ON AN cooled , double copper wound , core type with radiator cooled tank complete with first fill of transformer oil as per IS 335 amended upto date and di electric strenght more than 60 KV with colling system.The temperature more than 55 degree centigrade to ambient temp when measured by thermometer for top oil & 40 degree centigrade to ambient for winding when measured with resistance method, when tested in accordance with IS 2026(part 2).transformers shall be painted with PU paint as per relevant IS standards. | 1 | Each | 1.25 | ₹1.25 |
| 1.01 | (b) (i)rating and diagram plate will contain all terminal specifications as per IS 1180 (part 1)
(ii) earthing terminals 02 nos
(ii) Lifting lugs
(iv) thermometer pocket
(v) air releasing device
(vi) tap changer with locking provision
(vii) Oil and winding temperature indicator
(viii) dehyadration breather fitted with silica gel
(ix) Drain cum simpling valve 3"/4 nominl size thread IS 554 steel with plug
(x) Pressure relief device on explosion
(xi) conservator vent
(c) energy efficiency shall be level II as per IS-1180 amended upto date
Note:- Drawing of transformer shall be got approved from GE. | - | - | - | - |
| 2 | Supply, installation, testing and commissioning of step down ,transformer 11KV/433 volts 3 Phase 50 hz 160 KVA New Level-2 outdoor type,with off load tap changing arrangement on HT side to vary secondary voltage upto +5% to -5% in step of 2.5% including suitable cable entry boxes both on HT to upto 120 sqmm 3 core XLPE cable and on low voltage side to acomodate XLPE cable of size upto 120 sqmm 3.5 core complete in all respect with standard accesories and fitment confirming to IS-1180 Part -1 of 2014 amended upto date primary side delta (HT) and secondary side star with neutral (LT) i.e vactor diagram Dyn11.The salient features of transformers are as follows:- | 1 | Each | -1.25 | - |
| 2.01 | (a) Transformer shall be oil immerse, ON AN cooled , double copper wound , core type with radiator cooled tank complete with first fill of transformer oil as per IS 335 amended upto date and di electric strenght more than 60 KV with colling system.The temperature more than 55 degree centigrade to ambient temp when measured by thermometer for top oil & 40 degree centigrade to ambient for winding when measured with resistance method, when tested in accordance with IS 2026 (part 2). transformers shall be painted with PU paint as per relevant IS standards.
(b) (i)rating and diagram plate will contain all terminal specifications as per IS 1180 (part 1)
(ii) earthing terminals 02 nos
(ii) Lifting lugs
(iv) thermometer pocket
(v) air releasing device
(vi) tap changer with locking provision
(vii) Oil and winding temperature indicator
(viii) dehyadration breather fitted with silica gel
(ix) Drain cum simpling valve 3"/4 nominl size thread IS 554 steel with plug
(x) Pressure relief device on explosion
(xi) conservator vent
(c) energy efficiency shall be level II as per IS-1180 amended upto date
Note:- Drawing of transformer shall be got approved from GE. | - | - | - | - |
| 3 | Supply, installation, testing and commissioning of 250 KVA Compact sub station along with all accessories complete all as specified and directed.
A. HT Section
11KV 630A Three way RMU Non extensible outdoor type (21KA, 3Sec) with 02 Nos Load Break Switch & 1 No SF6 VCB complete with all accesories single core CT ratio 50/1A
RMU ,11KV, 2 No. Load Break Switch + 1No Vaccumm Circuit Breaker (L) altitude upto 1000 meter position Disconnector and Earth Switch
1. Operation of LBS- Manual
2. Load Break switch Rating-11 KV 630A 21 KA
3. External cone threaded M 16 bolted bushings C Type, for cable ends , T Type
4. Cable box provided
5.Capacitor dividers and plug in voltage presence lamps with phase concor dance predisposition.
6. with supply of touch proof termination Kit suitable for CSS having incoming and lopping cable IR*3C*300 sqmm
Function type: 3 position Vacuum circuit breaker in series with 3 positions independent operation disconnector-*outgoing feeder
1.Operation of Vaccum circuit breaker - Motorised
2.Vaccum circuit breaker rating-11 KV 630A 21 KA/3 sec
3. self powered series trip Microprocessor based numerical Over current +Earth fault relay (IDMT+ Inst) for protection
4. Tap Wound Protection current transformer of single core (CTR:50/1A, 2.5VA) for protection
5. Capacitor divider and plug in voltage presence lamps with phase concor dance predisposition.
6.1 No Disconnector switch open close earth
7.1 No Emergency push botton
8. Open/close mechanical indication. | 1 | Each | -3.75 | - |
| 3.01 | RMU Accesories:-
Manual operation Handle-01 No
Standard Manometer
Auxiliary relay (3 element)
24DC power pack
Acknowledge Push botton
96sqmm Hooter
DP MCB 10KA for control | - | - | - | - |
| 3.02 | B. Transformer Section
250 KVA Transformer (Manufactured as per IS 1180 New Level -2)
Type: ONAN Oil filled
1. Ratio: 11/.433 KV
2. Capacity: 250 KVA
3. Vector group: Dyn 11, 3 Phase
4. Off load Tap link: +5% to -10% in steps of 2.5%
5. Winding copper
6. Corrugated Type Hearmitically sealed type
7. Ambient Temperature- 50 Degree C
8.Average Temperature rise in the winding over ambient temperature 40 deg C measured by resistance method -95 Deg C
9.Bulb Holder
10. Door Limit Switch | - | - | - | - |
| 3.03 | C. LT Section:
a. Transformer- Incommer
400A FP Manual fixed type MCCB 50KA Microprocessor Based with OC SC EF
Digital Ammeter & Voltmeter
Digital Multifunction meter
CT s 400/5A
Indication Lamps (RYB)
Indication Lamps ( ON OFF)
Control MCB's
Outgoing
100A FP MAnual fixed MCCB 36 KA
Indication lamp
Control MCB
D.Interconnection
Interconnection between HT & LT section & Transformer through Al. XLPE 95 cable, Transfromer & LT section through Aluminium Bus Bar. | - | - | - | - |
| 4 | Supply, install, testing and commissioning of silent type Diesel Engine driven generating set of min 250 KVA capacity 3 phase, 4 wire, 415 V, 1500 RPM conforming to relevant IS Codes, AC power supply with power factor 0.8 coupled directly to alternator mounted on a common ed Plate with sturdy design,Bed plate shall be suitable for mounting on anti viberation mounting system, load factor 0.85, complete with integral acoustic enclosure-sound proof canopy (should have silent features as per latest CPCB IV norms), fuel tank having facility for easy cleaning, Suitable Battery Charging unit incl battery & standard accessories, and at least 2 year warranty. | 1 | Each | -8.75 | - |
| 4.01 | (A) ENGINE : Liquid Cooled, electric Self start, 4 Stroke, min 6 cylinders cold starting, Naturaly aspirated /TCI aspirated( as per manufacturer standard), compression ignition, totally enclosed diesel engine , 1500 RPM suitable for 250 KVA alternator under NTP conditions as per ISO 8528 Part-I capable of taking 10% over load for 1 hours in every 12 hours continues running confirming to IS: 10000/10002/ISO 3046/ BS: 649/ BS: 554 amended up to date, the Engine shall consist of the following :-
(i) Dynamically balanced fly wheel or as per manufacturer's standard
(ii) Coolant cooling system complete
(iii) Air cleaner as per manufacturer's standard
(iv) Fuel injectors and fuel pump as per manufacturer's standard
(v) Electronic governor as per manufacturer's standard to maintain engine speed at all conditions of load
(vi) Fuel service tank of suitable capacity fabricated from MS sheet with, inlet outlet connections, air vent tap,drain plug, Caliberated level indiactor(gauge), MS fuel piping from tank to engine with valves, unions, reducers, flexible hose connections, mounting pedestals, fuel filters incl all as per manufacturer's design.
(vii) Dry exhaust manifold with suitable exhaust residential grade, Asbestos rope of suitable size shall be provided as per manufacturer desires for silencer to reduce noise level as per CPCB norms.
(viii) Static Battery charging unit suitable for 90 Ah battery/battery array 12/24 volt having float, trickle and boost charging feature. Charging should be from utility supply/generator supply as directed by Engr in charge. (b) one/two battery of total capacity 180 Ah connected with copper lugs and minimum 50 sqmm cable placed inside the acoustic enclosure.
(ix) Gear driven oil pump for lubricating oil, priming of engine bearing, as well as fuel systems as per manufacturer's recommendation.
(x) Natually aspirated/turbo charger as per manufacturer's standard.
(xi) Lubricaton oil coolers and filters with replaceable elements as per manufacturer's standard | - | - | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.36 MB
48TENDERDOCUMENT.pdf
Tender Documents • 1.11 MB
BOQ_841259.xls
BOQ • 0.77 MB
AMDTPS48.pdf
PDF • 0.32 MB
DATECORR48.pdf
PDF • 0.13 MB
Download all tender documents and submit your bid