| 1 | L1₹2.4 CrAccepted-AOC | ₹2.4 Cr | L1 | Accepted-AOC Lowest bidder. Hence accepted. |
| 2 | L2₹2.6 Cr+₹15.7 L (6.44%)Rejected-AOC | ₹2.6 Cr+₹15.7 L (6.44%) | L2 | Rejected-AOC Other than lowest bidder |
| 3 | L3₹2.6 Cr+₹15.9 L (6.54%)Rejected-AOC | ₹2.6 Cr+₹15.9 L (6.54%) | L3 | Rejected-AOC Other than lowest bidder |
| 4 | L4₹2.9 Cr+₹48.6 L (19.9%)Rejected-AOC C 33 3971 GALI NO 6 JALANDHAR CANTT 144005 | JALANDHAR | JALANDHAR | PUNJAB | 144005 | ₹2.9 Cr+₹48.6 L (19.9%) | L4 | Rejected-AOC Other than lowest bidder |
| 5 | L5₹2.9 Cr+₹50.6 L (20.8%)Rejected-AOC | ₹2.9 Cr+₹50.6 L (20.8%) | L5 | Rejected-AOC Other than lowest bidder |
Tender Value
₹2.3 Cr
EMD Value
₹3.0 L
Closing Date
14 Jun 2025, 6:00 pmClosed
CE Chandigarh Zone
HQ CE Chandigarh Zone N Area, Airport Road Chandigarh-160003
CA No. CE CHZ/CHM/T-01/2025-26 PROVN OF TRANSIT ACCN FOR OFFICERS AT CHANDIMANDIR
2025_MES_704956_1
CE CHZ/CHM/T-01/2025-26
Open Tender
Civil Works
Lump-sum
270 days
CHANDIMANDIR
As per Tender documents/NIT
10 documents required · 10 mandatory
₹3,000
GE Chandimandir
₹3.0 L
Yes
9 Jul 2025
22 Apr 2025
16 Jun 2025
22 Apr 2025
14 Jun 2025
9 Jun 2025
22 Apr 2025 - 3 May 2025
Amount
Total amount of Sch 'A' Sec-I ( BUILDING WORKS ) Lump sum price worked out by the contractor for " BUILDING WORKS " as listed in schedule 'A' Part-I
Total amount of Sch 'A' Sec- II (SITE CLEARANCE, DEMOLITION, & MISC. EARTH WORKS) Lump sum price worked out by the contractor for " SITE CLEARANCE, DEMOLITION, & MISC. EARTH WORKS " as listed in schedule 'A' Part-II
Total amount of Sch 'A' Sec- III ( INTERNAL WATER SUPPLY WORKS ) Lump sum price worked out by the contractor for " INTERNAL WATER SUPPLY WORKS " as listed in schedule 'A' Part-III
Total amount of Sch 'A' Sec- IV (INTERNAL ELECTRIFICATION WORKS) Lump sum price worked out by the contractor for " INTERNAL ELECTRIFICATION WORKS " as listed in schedule 'A' Part-IV
Total amount of Sch 'A' Sec- V (SEWAGE DISPOSAL WORKS) Lump sum price worked out by the contractor for " SEWAGE DISPOSAL WORKS " as listed in schedule 'A' Part-V
Total amount of Sch 'A' Sec- VI (HARDSTANDING WORKS) Lump sum price worked out by the contractor for " HARDSTANDING WORKS " as listed in schedule 'A' Part-VI
Total amount of Sch 'A' Sec- VII (AREA DRAINAGE WORKS) Lump sum price worked out by the contractor for " AREA DRAINAGE WORKS " as listed in schedule 'A' Part-VII
Total amount of Sch 'A' Sec- VIII (EXTERNAL WATER SUPPLY WORKS) Lump sum price worked out by the contractor for " EXTERNAL WATER SUPPLY WORKS " as listed in schedule 'A' Part-VIII
Total amount of Sch 'A' Sec- IX (HOT WATER SUPPLY WORKS) Lump sum price worked out by the contractor for " HOT WATER SUPPLY WORKS " as listed in schedule 'A' Part-IX
Total amount of Sch 'A' Sec - X EXTERNAL ELECTRIC SUPPLY WORKS) Lump sum price worked out by the contractor for " EXTERNAL ELECTRIC SUPPLY WORKS " as listed in schedule 'A' Part-X.
Schedule 'A'Section-XI (Misc Items of Works) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col. 5 siginifies this fact only.
LIST OF WORKS FOR INTERNAL ELECTRIFICATION Concealed point wiring using approved colour coding as per IS, with 1.5 Sqmm (nominal area), single core multistranded copper conductor of 1100 volts grade, ISI 694 marked, PVC insulated and unsheathed FRLS-H, drawn through and including heavy duty PVC conduit of 20 mm dia (2mm wall thickness) and conduit accessories ISI marked, PVC junction boxes etc, concealed in walls/ceiling/floors including 1.5 Sqmm (nominal area), single core multistranded copper conductor of 1100 volts grade, ISI 694 marked, PVC insulated and unsheathed FRLS-H as earth continuity conductor to common earth & connecting to earth dolly for the following :-
One light/bell/fan point (Ceiling/ Wall/ Exhaust) controlled by one number 1-way switch or one number 1-way switch and regulator
One light point conrolled by two numbers 2-way switches
One 5/6 Amp socket outlet on independent board
One 5/6 Amp socket outlet on the same board with other switches
Concealed point wiring using approved colour coding as per IS, for 15 Amp socket outlet on independent board with 2.5 Sqmm (nominal area), single core multistranded copper conductor of 1100 volts grade, ISI 694 marked, PVC insulated and unsheathed FRLS-H, drawn through and including heavy duty PVC conduit of 20 mm dia (2mm wall thickness) and conduit accessories ISI marked, PVC junction boxes etc, concealed in walls/ceiling/floors including 2.5 Sqmm (nominal area), single core multistranded copper conductor of 1100 volts grade, ISI 694 marked, PVC insulated and unsheathed FRLS-H as earth continuity conductor to common earth & connecting to earth dolly. Notes for item Nos. 12 to 13 : (a) Modular GI metal flush/sunken box of thickness not less than 1.20mm, modular base/front cover plate with frame and blank plate are included in the quoted rate of this item. Only switches/sockets shall be measured and paid separately under respective items of Sch 'A'/BOQ. (b) Cost of cutting/chases for concealing of conduit shall be deemed to be included in quoted lump sum of Sch 'A' Section-I.
Concealed point wiring using approved colour coding as per IS, for AC/Geyser with 4 Sqmm (nominal area), single core multistranded copper conductor of 1100 volts grade, ISI 694 marked, PVC insulated and unsheathed FRLS-H, drawn through and including heavy duty PVC conduit of 20 mm dia (2mm wall thickness) and conduit accessories ISI marked, PVC junction boxes etc, concealed in walls/ceiling/floors including 4 Sqmm (nominal area), single core multistranded copper conductor of 1100 volts grade, ISI 694 marked, PVC insulated and unsheathed FRLS-H as earth continuity conductor to common earth & connecting to earth dolly. Notes : (a) Only sheet metal enclosure MCB DBs shall be measured and paid separately under respective items of Sch 'A'/BOQ here-in-after. (b) Cost of cutting/chases for concealing of conduit shall be deemed to be included in quoted lump sum of Sch 'A' Section-I.
Sheet metal enclosure vertical type double door DB TPN 4 way suitable to accomodate MCCB TPN, 415 volts upto 200 Amp & above rating, protection class IP-54 IK-09 made out of CRCA mild steel sheet surface with insulated material like polyester with epoxy powder coated surface mounted as per IEC 61439-3, with copper bus bar of 200 Amp capacity for each phase, with two neutralbars, two Earth bars and cable ties for cable management complete all as specified and directed.
MCB SP, 240 Volt , 50 Hz, 6 to 32 A, 10 KA , "B" curve, complete all as specified and directed.
MCB SPN, 32 Amp, 'B' Curve , 240 volt , 50 Hzs,10 KA, complete all as specified and directed.
MCB SPN 63 Amp, 415 volts, 'B'-curve, rupturing capacity 10KA conforming to IEC-60898, Part-I complete, all as specified & directed.
MCCB TPN 200 Amp, 415 volts, rupturing capacity 36KA conforming to IEC-60947-II adjustable thermal setting type complete, all as specified & directed.
Single pole and neutral enclosure with a two pin and earth plug with socket complete with one double pole MCB 20 Amp, 240 V single phase complete all as specified and directed.
Modular socket outlet for Tele, 1-Module complete all as specified and directed.
Modular socket outlet for TV 1-Module market complete all as specified and directed.
LED 8 watt recessed down light, round type with die-cast aluminium housing white/black powder coated and beam angle as desired, driver efficiency not less than 85 %, LED life span not less than fifty thousand hour complete all as specified and directed. Make Jaquar Cat Part No IRL-WHT-LEMA01R008XW or equivalent.
LED 15 watt recessed down light, round type with die-cast aluminium housing white/black powder coated and beam angle as desired, driver efficiency not less than 85 %, LED life span not less than fifty thousand hour complete all as specified and directed. Make Jaquar Cat Part No IRL-WHT-LEMA01R015XW or equivalent.
LED 12 watt surface mounted down light, round type with die-cast aluminium housing white powder coated and beam angle as desired, driver efficiency not less than 85 %, LED life span not less than fifty thousand hour complete all as specified and directed. Make Jaquar Cat Part No IDL-WHT-LNR002R012SC or equivalent.
Tiltable linear spot light fitting 10 watt (5 x 2 watt) having beam angle as desired with aluminium extrusion black powder coated and CRCA frame with white powder coated, LED life span not less than fifty thousand hour complete all as specified and directed. Make Jaquar Cat Part No IRL-WHT-LRNE01S010XW or equivalent. Notes for item Nos. 23 to 26 : Wire above false ceiling for connection of light fittings shall be provided through flexible conduit of 20 mm dia as required. The cost of the same shall be deemed to be included in the quoted rate.
LED outdoor decorative wall light fitting with glass diffuser and die-cast aluminium housing black powder coated, E27 base cap including LED lamp 10 watt complete all as specified and directed. Make Jaquar Cat Part No OWA-BLK- 30000 or equivalent.
LED indoor decorative wall light fitting with frosted glass, chorme finishing , E 27 base cap including LED lamp 7 watt, complete all as specified and directed. Make Jaquar Cat Part No DWL-CHR-MB160275514A or equivalent.
LED decorative mirror light fitting with 2 light opal glass, chorme finishing , E 14 base cap including LED lamp 4.5 watt x 2 No (09 Watt), complete all as specified and directed. Make Jaquar Cat Part No DBL-CHR-MB12021172A or equivalent
LED indoor decorative bed side light fitting with fabric shade, chorme finishing , E 14 base cap including LED lamp 4 watt and LED 3 watt inbuilt complete all as specified and directed. Make Jaquar Cat Part No DWL-CHR-WLRDFAB150 or equivalent.
Bollard light fitting 6 watt warm white in die-cast aluminium housing with matt grey powder coated, polycarbonate reflector, IP 66 and IK 07 and surge protection of 2 KV in driver complete all as specified and directed. Make Jaquar Cat Part No OBL-GRY-LBLD05R601XW or equivalent.
Brushless Direct Current Motor (BLDC) ceiling fan energy efficient complete with blades, down rods, electronic regulator and accessories, 230 V,1200mm sweep with remote, 100 % rust free blades, anti dust & anti bacterial, with service value 6.00 BEE 5-star rated complete all as specified and directed. Make Havells Cat Part No FHCE25SSLM48 or equivalent.
RCBO 'A' Type (SPN-2M) 32 Amp 30 mA (In accordance with IS 12640-2 & IEC 61009-1) 240 V/415 V 50 Hz, with 10 KA short circuit capacity, complete all as specfied and directed . Make Havells Cat no DHCEACSN2030032 or equivalent in other specified makes.
RCBO 'A' Type (SPN-2M) 63 Amp 100 mA (In accordance with IS 12640-2 & IEC 61009-1) 240 V/415 V 50 Hz, with 10 KA short circuit capacity, complete all as specfied and directed . Make Havells Cat no DHBMACTN8100063 or equivalent in other specified makes.
Exhaust fan 300 mm sweep made of sturdy Engineering plastic body, heavy duty, Single phase AC 230/240V, with energy efficient motor,copper winding, pre lubricated double ball bearing, minimum speed 900 rpm complete with louvers for wall mounting incl grouting holding down bolts, nuts, washers and provision of flexible copper conductor cable 3 core from ceiling rose to exhaust fan , complete all as specified and directed. Note: Cost of cutting of hole of required size for fixing of the exhaust fan shall be deemed to be included in quoted lump sum of Sch 'A' Section-I.
Earthing complete with and including galvanised steel earth plate electrode 600 mm x 600 mm x 6 mm surrounded by a mixture of charcoal and salt in alternate layers burried directly in ground vertically in a pit of depth not less than 2.25 m deep below ground level with top edge of earth plate at a depth of not less than 1.5 m below ground level, connected with and including galvanised iron or steel earth wire, 4mm dia (No. 8 SWG) by means bolts, nuts, check nuts and washers made out of galvanised iron, 15 mm bore (medium grade) GI pipe for protection of earthing lead, 20 mm bore (medium grade) GI pipe for watering with funnel, wire mesh and including necessary excavation and earth work, PCC 1:2:4 type B-1 pit and 50 mm thick RCC 1:1.5:3 type A-1 reinforced with XPM (weight not less than 3 kg/sq m) pit cover, C.I frame, charcoal and common salt filling in alternate layers, complete all as shown in electrical plate No. 3 of SSR Part I (2009), specified and directed. NOTE : The unit rate includes for protecton pipe 15mm and GI earth wire 4mm from top of earth plate upto 7.50 metre above ground level.
INTERNAL WATER SUPPLY 15mm angle valve with wall flange having water flow of 42.44 LPM @ 3 Bar having water tightness of min 16 Bar and pressure resistance of min 25 bar Nickle plating minimum 10.0 micron and Chromium plating minimum 0.3 micron complete, all as specified & directed.
Shiny finish shower panel of size 1600 x 23Omm incl 2 movable ABS Each body massage jets, Head shower, Hand shower, Cascade shower and having minimum water pressure 2 bar incl fitting, all accessories complete all as specified and directed. (Cat Part No./Make : Cat Part No. JSHP-SSF-ST8896 of Make Jaquar or equivalent model of makes listed in List of makes)
Corner entry shower enclosure to fit in L shaped walls with door sliding to both sides (4 Parts) having glass thickness 6mm chrome finished of size Height 1950mm, Width : 1500mm x 1500mm incl fitting, all accessories complete all as specified and directed. (Cat Part No./Make : Cat Part No. JSE-CHR-ENNA1515X of Make Jaquar or equivalent model of makes listed in List of makes)
Wall to wall shower enclosure with two fixed glass and one openable door in betwwen the square hardware and profile glass thickness 8mm black finished of size Height 2000mm, Width : 2401 to 2800mm incl fitting, all accessories complete all as specified and directed. (Cat Part No./Make : Cat Part No. JSE-BLM-S830G2428H20X of Make Jaquar or equivalent model of makes listed in List of makes)
SEWAGE DISPOSAL/AREA DRAINAGE WORKS H.D.P.E Double wall corrugated (DWC) pipes (ISI Marked) 150mm SN-8 Class as per IS 16098 Part-II for non pressure underground drainage and sewage applications with specials including cost of special O rubber ring couplers etc, laid in trenches on concrete bed to level/gradient, jointing with appropriate class fittings as per manufacturer’s instructions including jointing accessories and fittings complete all as specified and directed.
Pre-cast factory made RCC manhole and drain covers/slab of size 600 mm x 1200 mm x 100 mm thick for normal duty, using 20 mm graded crushed stone aggregate in M-25 concrete including RCC ring/frame, reinforcement and MS frame as in man hole covers, set in cement mortar 1 :4 complete all as specified and directed.
HARDSTANDING WORKS Precast (factory casted) kerb stone casted in M-25 grade cement concrete with plain or interlocking joints (as directed), placing in erect position in edging and set and jointed in cement mortar 1:3, thickness of joint not more than 5 mm except at sharp curve including making drainage openings where required complete all as specified and directed.
EXTERNAL ELECTRIC SUPPLY WORKS Supply/Laying / fixing, jointing, testing and commissioning LT under ground cable 1100 volts grade XLPE insulated & PVC sheathed cable heavy duty armoured, with multistranded aluminium conductor laid in trenches/ ducts/ pipes/fixed on walls/poles complete all as specified and directed of following sizes:-. Notes:- 1. Excavation & earth work and pipe for laying of cable shall be measured and paid for seprately under respective items of the schedule. 2. Cable shall be tested in the presence of Engr-in Charge after laying in the trench before returning filling in the trench.
2 Core 4 Sqmm
3.5 Core 120 Sqmm
Double Wall Corrugated (DWC) pipe of HDPE, 40 mm outer dia, ISI marked, including suitable size couplers for jointing of pipe, laid in floors/trenches/crossing of roads for protection of cable complete all as specified and directed.
Double Wall Corrugated (DWC) pipe of HDPE, 75 mm outer dia, ISI marked, including suitable size couplers for jointing of pipe, laid in floors/trenches/crossing of roads for protection of cable complete all as specified and directed.
SUMMER APPLIANCES Supply installation commissioning and testing hi wall split units indoor/outdoor complete with cordless remote control unit and with in built Heating and Cooling arrangement and Digital Inverter twin rotary of capacity 1.5 TR with minimum 3 star rating and as per latest EER complete all as specified and directed. Note :- Contractor's quoted rates shall be deemed to include for cost of pair of mounting bracket heavy duty for outdoor unit, additional copper pipe as required beyond standard supply with AC, additional insulation material for copper pipe as required beyond standard supply with AC, drainout pipe from indoor unit to outside building as directed.
All as per Srl item No 45.00 above but of capacity 2 TR.
Supply, installation,testing and commissioning voltage stablizer for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170 V to 290 V with output voltage stablized at 230 V with accuracy of +/- 2.5% and of capacity 5.0 KVA complete all as specified and as directed.
M/S KAPIL KUMAR KHATTAR (BID ID -3322969)
Laxmi Builders (BID ID -3321849)
M/S Mukesh Kumar Gupta (BID ID -3322635)
Buildtech India (BID ID -3320533)
Saru Enterprises Pvt Ltd (BID ID -3322117)
aggarwal traders (BID ID -3319844)
H.P. CONSTRUCTION CO. (BID ID -3320693)
V r traders (BID ID -3323292)
DES RAJ AND SONS BUILDERS PVT LTD (BID ID -3321113)
SAR AGENCIES (BID ID -3322634)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .