Tender Value
₹47.2 L
EMD Value
₹94,400
Closing Date
29 Sept 2022, 6:00 pmClosed
ARJUN PATRO,IDSE
GE U ELECTRIC SUPPLY,DELHI CANTT-10
Repair maintenance and replacement of LT Panels, MCCB, ACB, change over switch, earthing at CVD, Piru Vihar, DIPAC, HQ TG, Vikram Batra Vihar, CMP Line, Chitral Line, Basantar Line, EME Unit Line, Kabul Line, Baird Place, Kotwali Line, CEDZ Office, A
2022_MES_542136_1
GE ELECT/D-56/2022-2023
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE U ELECTRIC SUPPLY
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹94,400
Yes
12 Dec 2022
1 Sept 2022
1 Oct 2022
1 Sept 2022
29 Sept 2022
17 Sept 2022
Amount
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 m deep in soft/loose soil) for laying of cables or GI pipe and getting out including levelling of bottom suface to required level complete all as specified and directed.
All as per Serial item No 1.00 here in before but depth exceeding 1.5 mtr and not exceeding 3.00 mtr.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables and in substation ducts for cushioning of cables etc, complete all as specified. (Measurement should be after punning down)
S & F sub class B bricks having minimum compressive strength 75 Kg/ Sq cm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.
Returning filling in,. including spreading, levelling, watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material (ie soil) from site to a distance n. exc 50 m away and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed.
Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 40 to 100 mm bore and making good both ends all specified and directed.
Supply and lay GI pipe light grade in replacement as cable protection laid on trench/floor, fixed on pole/wall etc of size 80 mm dia complete all as specified. .
All as per item No 8.0 here in before but of size 50 mm dia complete all as specified and directed.
All as per item No 8.0 here in before but of size 40 mm dia complete all as specified and directed.
Material and labour for laying in replacement of Rubber Mat 2 mtr x 1 mtr Length, 02 mm thick, 1.1 kV Grade conforming to IS-15652-2006 complete all as specified.
Supply, install, testing and commissioning in replacement of factory made tested LT panel board of size not less than 0.9 mtr x 0.55 mtr x 1.4 mtr cubical double door compartment outdoor type leg mounted suitable for , 415 volts 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated Aluminium bus bar of rating not less than 1.5 times of Incomer/ Outgoings MCCBs, installed on proceline/ SMC insulator. The panel shall be dust and vermin proof IP -65 class protection and made of 3.15 mm CRCA MS sheet and inner compartment 2.0 mm, 40X40X6 mm thick MS angle iron frame work, fixing of double doors shall be on MS hinges with anti-theft provision (the door can’t be removed from enclosure without cutting enclosure), powder coated finished over one coat of red oxide on out side surface and painted in side with two coats of red oxide primer and rear opening type with apran for cable entery closing locking arrangement including internal wiring with PVC insulated multisranded copper conductor FRLS cable IS 694 marked , 1100 volts grade of appropriate size (but not less than 2.5 sqmm) and comprising of the following including necessary brick work for platform of suitable size:-
All as item no-12.00 here in before but as followings:- Panel size should not be less than 1.25 mtr x 0.55 mtr x 1.5 mtr INCOMING:- (i) MCCB 4 pole, 320 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos OUTGOINGS:- (i) MCCB 4 pole, 160 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 2 Nos (ii) MCCB 4 pole, 63-100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Fixed Magnetic setting - 2 No
All as item no-12.00 here in before but as followings:- Panel size should not be less than 1.6 mtr x 0.45 mtr x 1.1 mtr INCOMING:- (i) MCCB 4 pole, 315-400 Amps Thermal Magnetic and Adjustable type, 50 Hz, 415 Volts, 36 KA -1 No OUTGOINGS:- (i) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25KA Adjustable Thermal and Adjustable Magnetic setting- 6 Nos (ii) MCCB 4 pole, 63 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermo and Fixed Magnetic setting - 4 No .
All as item no-12.00 here in before but as followings:- Panel size should not be less than 1.4 mtr x 0.55 mtr x 1.6 mtr INCOMING:- (i) On Load Change Over switch of Cap 630 Amp, 4 pole, 415 Volt-01 No (ii) MCCB 4 pole, 630 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos OUTGOINGS:- (i) MCCB 4 pole, 400 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos (ii) MCCB 4 pole, 250 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Fixed Magnetic setting - 1 No (iii) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Fixed Magnetic setting - 1 No (iv) MCCB 4 pole, 63 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Fixed Magnetic setting - 3 No
All as item no-12.00 here in before but as followings:- Panel size should not be less than 0.9 mtr x 0.45 mtr x 1.25 mtr INCOMING:- (i) MCCB 4 pole, 200 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 No OUTGOINGS:- (i) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 4 Nos
All as item no-12.00 here in before but as followings:- Panel size should not be less than 1.1 mtr x 0.5 mtr x 1.4 mtr INCOMING:- (i) MCCB 4 pole, 400 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos OUTGOINGS:- (i) MCCB 4 pole, 250 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 2 Nos (ii) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Fixed Magnetic setting - 2 Nos
All as item no-12.00 above here in before but mounted on medium channel 75 mm x 40 mm welded with panel with 04 Nos foundation bolt of size not less than 20 mm dia and 300 mm long and as followings:- Panel size should not be less than 1.6 mtr x 0.6 mtr x 1.9 mtr INCOMING:- (i) On Load Change Over switch of Cap 400 Amp, 4 pole, 415 Volt-01 No (ii) MCCB 4 pole, 400 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 No OUTGOINGS:- (i) MCCB 4 pole, 200 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos (ii) MCCB 4 pole, 125 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Fixed Magnetic setting - 6 Nos
All as item no-12.00 here in before but mounted on channel 75 mm x 40 mm welded with panel of SS 316 with 04 Nos foundation bolt of size not less than 20 mm dia and 300 mm long and as followings:- Panel size should not be less than 1.6 mtr x 0.6 mtr x 1.9 mtr. INCOMING:- (i) On Load Change Over switch of Cap 400 Amp, 4 pole, 415 Volt-01 No (ii) MCCB 4 pole, 400 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 No OUTGOINGS:- (i) MCCB 4 pole, 250 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos (ii) MCCB 4 pole, 125 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Fixed Magnetic setting - 1 Nos (iii) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Fixed Magnetic setting - 5 Nos
All as item no-12.00 here in before but as followings:- Panel size should not be less than 1.6 mtr x 0.5 mtr x 1.3 mtr INCOMING:- (i) MCCB 4 pole, 400 Amps , 50 Hz, 415 Volts, 36 KA, Adjustable Thermal and Fixed Magnetic setting -1 No OUTGOINGS:- (i) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA , Adjustable Thermal and Fixed Magnetic setting -7 Nos. (ii) Space for MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, - 1 No
All as item no-12.00 here in before but as followings:- Panel size should not be less than 1.9 mtr x 0.6 mtr x 1.5 mtr INCOMING:- (i) MCCB 4 pole, 400 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos OUTGOINGS:- (i) MCCB 4 pole, 63-100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 7 Nos (ii) MCCB 4 pole, 63 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Fixed Magnetic setting - 1 No
Supply, installation, commissioning in replacement old MS Panel , outdoor type stainless steel (SS 316) cubical enclosure compartmentalized, of size not less than 1.2 mtr x 0.55 mtr x 1.5 mtr exterior and interior mirror type brushed suitable for highly corrosive environment, high creep resistance, better mechanical properties like ductility, yield strength, hardness etc.The enclosure shall be made of 2 mm thick SS 316 sheet. The fixing of double doors shall be on SS hinges with anti-theft provision (the door can’t be removed from enclosure without cutting enclosure). All fabrication/welding shall be done with TIG/MIG or as approved by Engineer in charge suitable for SS 316. Sliding handle and locking arrangement front and rear both side . Enclosure shall be suitable for AC supply system 415 volts 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated Aluminium bus bar installed on proceline/ SMC insulator of rating not less than 1.5 times of incoming/ outgoing ACB/MCCBs , IP-65 class protection and mounted on channel 75 mm x 40 mm welded with panel of SS 316 with 04 Nos foundation bolt of size not less than 20 mm dia and 300 mm long. The enclosure shall have provision of cable alley . Cable entry from bottom side including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm).
INCOMING:- (i) On load Change over switch of capacity 630 Amp 4 pole-01 No (ii) MCCB 4 pole, 630 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 No (iii) Voltmeter digital type - 01 No (iv) Ammeter digital type - 01 No (v) Indicating LED lamp one set of three (vi) CT ratio should be equal to the rated current carrying of incomer. OUTGOINGS:- (i) MCCB 4 pole, 400 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos (ii) MCCB 4 pole, 200 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos (iii) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 3 Nos (iv) Space free for one compartment.
All as item no-22.00 above here in before but as followings:- Panel size should not be less than 1.5 mtr x 0.6 mtr x 1.6 mtr INCOMING:- (i) On load Change over switch of capacity 400 Amp 4 pole-01 No (ii) MCCB 4 pole, 400 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 No OUTGOINGS:- (i) MCCB 4 pole, 160 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 3 Nos (ii) MCCB 4 pole, 125 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos (iii) MCCB 4 pole, 63 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 1 Nos (iv) Space free for one compartment.
All as item no-22.00 above here in before but as followings:- Panel size should not be less than 1.6 mtr x 0.6 mtr x 1.9 mtr INCOMING:- (i) On load Change over switch of capacity 400 Amp 4 pole-01 No (i) MCCB 4 pole, 400 Amps, 50 Hz, 415 Volts, 36 KA Adjustable Thermal and Adjustable Magnetic setting- 1 No OUTGOINGS:- (i) MCCB 4 pole, 200 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 1 No (ii) MCCB 4 pole, 160 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 2 Nos (iii) MCCB 4 pole, 125 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 2 Nos (iv) MCCB 4 pole, 63 Amps, 50 Hz, 415 Volts, 25 KA Adjustable Thermal and Adjustable Magnetic setting- 2 Nos (vi) Space free for one compartment.
Note for item No 12.0.0 to 24.0 :- (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & Lugs. (ii) The cubical Incomer ACB/MCCB/ Change over switch as well as outgoings shall have Aluminium TPN extension links of current carrying capacity not less than 1.5 times the rated capacity of individual feeders. The extension links shall not be less than 300 mm long supported on suitable size 'F' class insulators . (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture. (iv) The feeder piller/panel should have louvers for natural flow of air. (v) All MCCBs should have barrier. Danger plate should be fixed on both side of the panel. (vi) A detachable gland plate of thickness 3.15 mm power coated should be used at the bottom. (vii) Costruction of Foundation & taking out of the old connected cables and reconnection of the same with new thimbles, gland of suitable size are deemed to the above quoted rate. (viii) The above quoted rate should be included for taking down of old LT cables and refixing the same after installation of new panel.
Supply & fixing in replacement of Air circuit breaker 4 pole 1000 Amps 50 KA with Microprocessor release manual drawout Adjustable type including dismantling & taking out old unserviceable ACB from panels & fabrication works to MS sheet / cutting the BUS bar for proper fitting .
Supply & fixing in replacement of Air circuit breaker 4 pole 800 Amps 50 KA withwith Microprocessor release manual drawout Adjustable type including dismantling & taking out old unserviceable ACB from panels & fabrication works to BUS bar for proper fitting .
S&F in replacement of UNSV MCCBs of capacity 630 Amps, TP, 50 KA, 415 Volts 50 Hz, AC, with adjustable thermal and magnetic release including spreader link fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable MCCB from panels etc complete all as directed
All as per ser item No 27 here in before but rating of MCCB 400 Amp, 36 KA
All as per ser item No 27 here in before, but rating of MCCB 250 Amp, 36 KA
All as per ser item No 27 here in before but rating of MCCB 200 Amp, 25 KA
All as per ser item No 27here in before, but rating of MCCB 160 Amp, 25 KA
All as per ser item No 27 here in before, but rating of MCCB 125 Amp, 25 KA
All as per ser item No 27 here in before but rating of MCCB 100 Amp,25KA
All as per ser item No 27 here in before but rating of MCCB 63 Amp, 25 KA
S&F in replacement of UNSV MCCBs of capacity 630 Amps, FP, 50 KA, 415 Volts 50 Hz, AC, with adjustable thermal and magnetic release including spreader link fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable MCCB from panels etc complete all as directed.
All as per ser item No 28 here in before but rating of MCCB 400 Amp, 36 KA
All as per ser item No 28 here in before but rating of MCCB 320 Amp, 36 KA
All as per ser item No 28 here in before but rating of MCCB 250 Amp, 36 KA
All as per ser item No 28 here in before but rating of MCCB 200 Amp, 25 KA
All as per ser item No 28 here in before but rating of MCCB 160 Amp, 25 KA
All as per ser item No 28 here in before but rating of MCCB 125 Amp, 25 KA
All as per ser item No 28 here in before but rating of MCCB 100 Amp, 25 KA
All as per ser item No 28 here in before but rating of MCCB 63 Amp, 25 KA
Supply and fixing in the existing LT panel, On load change over switch in replacement of capacity 400 Amps, four pole, 415 volts, AC, 50 Hz alongwith connected bus bars also complete all as specified and directed .
Supply and fixing in the existing LT panel, On load change over switch in replacement of capacity 630 Amps, four pole, 415 volts, AC, 50 Hz alongwith connected bus bars also complete all as specified and directed .
Material and Labour for disconnecting burnt end or portion of cable removing the cable from loop including necessary excavation & earth work in soft/loose soil relaying and reconnecting the cable by removing burnt portion of cable and preparing fresh terminals( set of 4 x terminals) including fixing of new lugs for 50 Sqmm 3½ / 4 to 400 Sqmm of LT cable to main switch /panel including taping of XLPE cables complete all as specified and directed.
Material and labour in replacement of Voltmeter 0-500 V digital type as per existing size complete all as per specified and directed.
Material and labour in replacement of Ammeter 0-400/800 Amp digital type as per existing size complete all as per specified and directed.
Supply and fixing in replacement of indicator lamp for RYB phases complete all as specified and directed.
Supply and fixing in replacement LT current transformer having ratio 800/5 Amp , 15 VA, Class 0.5. Complete all as specified and directed by Engr-in-Charge
All as per Srl item No.36 here in before but CT ratio 400/5 Amp Complete all as specified and directed by Engr-in-Charge
All as per Srl item No 36 here in before but CT ratio 250/5 Amp Complete all as specified and directed by Engr-in-Charge
Supplying and fixing in replacement Mild steel sliding door bolts 200 mm long ,plate type, stove enamelled black, with bright bolt not less than 12mm dia with and including a minimum of 6 bolts and nuts, four on bolt plate and two on staple plate .
Supply and fixing in replacement of cable gland for LT panel/feeder pilar up to 50 to 70 Sqmm cable complete all as specified and directed.
Supply and fixing in replacement of cable gland for LT panel/feeder pilar for 120 to 185 Sqmm cable complete all as specified and directed.
Supply and fixing in replacement of cable gland for LT panel for 240 sqmm cable to 400 Sqmm cable complete all as specified and directed.
Earthing complete in replacement with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth wire 25 X 6 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in soft/loose soil and testing complete all as specified and directed and shown in electrical plate number 3 of MES SSR part-I(2009) (a) Excavation and earth work for drilling hole for electrode in soft/loose Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter.(c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed. (d) 40 mm nominal bore medium grade GI protection pipe for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing.
Supply and fixing in replacement of galvanised iron strip 25 X 6 mm for additional earthing lead beyond 7.5 meter complete all as specified and directed.
Material and labour for painting of LT panel boards out door/in door of size here in before 8.00 Sqmm floor/leg mounted installed at different locations including preparation of exposed surface by removing old paint from the body, cleaning the surface with thinner and applying two coats of synthetic enamelled smoke grey paint complete all as specified and directed.
All as per srl item No 45.0 here-in-before but of size 5.0-8.0 Sqmm complete all as specified and directed. .
All as per srl item No 45.0 here-in-before but of size below 5.00 Sqmm complete all as specified and directed..
M & L for cutting and removing grass, vegetation bushes etc from surrounding of installation/LT Panel/Four Pole structure/Sub Stations and removing all rubbish to a distance not exceeding 50 m as directed.
Material and labour in replacement for CRCA MS sheet of thickness 3.15 mm powder coated finish over one coat of red oxide on out side surface and painted in side with two coats of red oxide primer with apran for cable entry closing locking arrangement including all fixing acessories i.e. suitable size of hinge, nuts, bolts, washers, cutting and welding works etc complete all as specified and directed.
Supply, laying, jointing, testing and commissioning in replacement of LT underground cables of following sizes, 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-7098, Part-II marked, laid in trenches/ duct/ under road/ footpath/ etc or against re-routing / diversion from residential buildings/ road/ footpath etc complete all as specified and directed by Engr In Charge.
All as per srl item No 50.0 here-in-before but of size 25 Sqmm 4 core .
All as per srl item No 50.0 here-in-before but of size 35 Sqmm 3.5 core .
All as per srl item No 50.0 here-in-before but of size 50 Sq mm 3.5 core.
All as per srl item No 50.0 here-in-before but of size 70 Sq mm 3.5 core.
All as per srl item No 50.0 here-in-before but of size 95 Sqmm 3.5 core .
All as per srl item No 50.0 here-in-before but of size 120 Sqmm 3.5 core.
All as per srl item No 50.0 here-in-before but of size 185 Sqmm 3.5 core.
All as per srl item No 50.0 here-in-before but of size 240 Sqmm 3.5 core .
Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armoured heavy duty aluminium conductor 1100 Volts grade complete all as directed for the size 25 to 50 Sqmm x 3.5 core/ 4 core
All as per item No 51.0 here in before but size 70 to 150 Sqmm x 3.5 core
All as per item No 51.0 here in before but size 185 to 240 Sqmm x 3.5 core
Supply & fixing in replacement KIOSK Box weather proof made up of one piece mounted on SMC base and door pole mounted hinged door of size 333 x233x 120 mm outside and 300 x 200 x105 mm inside dimension comprising of aluminum bus bar 4 strips for 3 phase and neutral 63 Amp and 6 Amp fuse grip with base for controlling the steet light fitting and FI clamps 25x4mm with necessary MS nuts bolts and washers and including applying two coasts of synthetic enamel paint over a coat of red oxide zinc chrome primer on new steel surface and including embassing/painting of Danger notice of size not less than 10 cm x 7.5cm with letters, figures and conventional skull and bones in signal red colour on front face of KIOSK box body complete all as directed.
Supplying and fixing in replacement 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections twin core cable of size 16 Sqmm flat complete all as specified ad directed.
All as per Sr item No 55.0 here in before but of size 10 Sqmm.
All as per Sr item No 55.0 here in before but of size 6 Sqmm.
Material & labour for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate . in mass concrete and filling complete for foundation of pad of pole all as specified & directed by Enge-in- Charge
Material & labour for PCC 1:3:6 type C-1 using 20 mm graded stone aggregate . in mass concrete and filling complete for foundation of Panel & Transformer yeard, pole/stay/ of pole all as specified & directed by Enge-in- Charge
Material & labour for PCC 1:2:4 type B-1 using 20 mm graded stone aggregate in coping for replacement of new pole and breaking old existing coping and like including weather slightly rounded or chamfered angles and throaty and necessary form work complete for pole ,all as specified and directed by Engr-in-charge.
Demolition of path /concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) complete all as specified and as directed.
Material and labour for Cement Concrete type C-1 mix, 1:3:6 (20mm graded aggregate) 150 mm thick, finishing the top surfaces fair and even complete all as specified and as directed.
Dismantling the existing unserviceable (damaged/broken) PCC electric pole of any type and size, from ground after necessary excavation & breaking of concrete foundation & encasing the pole including making good the disturbed surfaces complete all as specified and directed.
Supplying & Erecting Steel Tubular Pole 410 SP-31 (9 metres long) in replacement complete with cast iron base plate all as specified in IS 2713 of 1980 (Part I & II) including painting of Poles with one coat of red oxide primer and one coat of aluminum paint before fixing and one coat of aluminum paint after fixing. The complete embedded portion shall be painted with two coats of black bituminus paint. (Note:- The necessary earth work and PCC work will be measured and paid separately under respective items.)
Material and labour for preparation of painted surface of LT Panel of any size for fixing of FLOURCENT REFELCTIVE LETTERING as follows of approved colours all as specified and directed . (a) Re-write the details (as given by the Engr In Charge) of Incoming & outgoing circuits (not more than-8 Nos), on the LT panels in capital letters of size not less than 30 mm width and 40 mm height and works not exceeding 80 letters per panel. (b) "LT PANEL" should be re-write on both front and back side of the LT Panel size not less than 50 mm width and 60 mm height.
Supplying and fixing in replacement of factory made and tested, Bus bar chamber, outdoor pedestal type, suitable for LT 415 volts 3 phase 4 wire, 50 Hz, AC supply system, having duly insulated four Nos aluminum bus bars (having Multiple holes), of rating 600 Amps , installed on epoxy / SMC type insulator The panel shall be dust and vermin proof, IP-65 Protection class and made of 3.15 mm CRCA MS sheet and 40x40x5mm thick angle iron base frame work, suitable for connection of multiple LT cables of diff size, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door shutter and locking arrangement of minimum size 50 cm x 50cm x 45 cm ( box size excluding legs) and mounted on angle iron pedstal 45 cms above groungd level all as specified including taking out old feeder pillar and taking out LT cable from loop for connecting in new panel and necessary excavation etc incl necessary Brick work for foundation as directed.
Supply and fixing in the existing LT panel, OFF load change over switch in replacement of capacity 400 Amps, four pole, 415 volts, AC, 50 Hz alongwith connected of existing cables complete all as specified and directed .
Supply and fixing in the existing LT panel, OFF load change over switch in replacement of capacity 250 Amps, four pole, 415 volts, AC, 50 Hz alongwith connected of existing cables complete all as specified and directed .
Supplying and fixing of LED street light fittings, 70 Watt, IP-65 , in replacement of old street light fitting any type complete complete all as specified and as directed.
Material and labour for sprading of stone aggregate of size 25 mm surounding area of outdoor LT Panel manually without damaging any equipments, cable or parts , spreading & levelling of finished gravel uniformaly in layers n. ecc. 15 cm thick watered and rammed to true surface all as specified and directed
Material and labour in replacement for ATS 4 pole of capacity 400 Amps alongwith controller and factory made enclosure complete including fixing arrangement with wall/ LT panel ,suitable size of MS flat, nuts, bolts, washer, fixing of existing LT cables of any size with suitable size of lugs all as specified and directed.
Note : contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge
Ish Engineers and Contractors
Vijay Electricals
R.P. Enterprises
MV Engineers And Contractors
Microsys Controls India
mayur enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .