Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹17.6 LAccepted-AOC | L-1 | Accepted-AOC Being lowest bidder | |
| 2 | L-2₹27.1 L+₹8.1 L (42.8%)Rejected-Finance | L-2 | Rejected-Finance Other than lowest bidder | |
| 3 | L-3₹30.9 L+₹11.9 L (63.1%)Rejected-Finance 201 GANAPATI SANKUL AGASHIVNAGAR MALKAPUR KARAD SATARA MAHARASHTRA 415539 | SATARA | MAHARASHTRA | 415539 | L-3 | Rejected-Finance Other than lowest bidder |
Tender Value
Refer Docs
EMD Value
₹52,000
Closing Date
20 Jul 2022, 6:00 pmClosed
GE Jammu
GE Jammu c/o 56 APO Pin-900277
REPAIR/MAINT OF ELECTRIC AND WATER SUPPLY INSTALLATION, UG CABLES, ACSR CONDUCTOR, POLES, LT DISTRIBUTION SYSTEM, SECURITY/STREET LIGHTS, SOLAR LIGHTS AND OTHER CONNECTED WORKS/ALLIED WORKS AT SUNJUWAN, BALIDAN STAMBH, SAINIK ARAM GRAH UNDER GE JAMMU
2022_MES_528338_1
GEJC-21/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AoR of GE Jammu
Please refer Tender Documents
9 documents required · 9 mandatory
₹500
GE Jammu
₹52,000
Yes
7 Oct 2022
3 Jun 2022
22 Jul 2022
3 Jun 2022
20 Jul 2022
17 Jun 2022
Amount
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre deep in any type of soil, getting out and levelling of bottom surface to required level for poles / stay assembly / cable complete all as specified and as directed.
Description same as per Ser Item No 1.00 here-in-before but exceeding 1.5 metre deep but not exceeding 3.0 metre deep complete all as specified and as directed.
Material and labour for road cutting, PCC hard standing as per site requirement including excavation for laying of GI pipe and making good the disturbed surfaces all as per existing surface complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 m thick all as specified and directed.
Removing excavated material from site to a distance not exceeding 50 metre away and depositing where directed not exceeding 1.5 metre from the starting point complete all as specified and as directed.
Material and labour in replacement of GI pipe light grade 80 mm bore for cable protection as a guard pipe complete all as specified and as directed.
Material and labour in replacment of GI pipe light grade 50 mm bore for cable protection as a guard pipe complete all as specified and as directed.
Supply and laying well burnt old size sub class 'B' bricks laid flat with width equal to length of brick perpendicular to the direction of cable, adjacent / abutting each other complete all as specified and as directed by Engineer-in-Charge in trenches over the cable for protection.
Supplying and laying in trenches clear sand for cushioning underground cable 8 cm below and 15 cm above complete in level all as specified and as directed.
Material and labour for PCC (1:4:8) type D-2 (using 40mm graded crushed stone aggregate) as in foundation of electric poles, struts, PCC blocks etc including necessary form work complete all as specified and as directed.
Material and labour for PCC (1:3:6) type C-2 (using 40mm graded crushed stone aggregate) as in foundation of assembly, bed concrete including necessary form work and fair finish to exposed surfaces without using extra cement, struts, PCC blocks etc including necessary form work complete all as specified and as directed.
Material and labour for PCC (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) as in coping of poles and similar work including necessary form work and fair finish to exposed surfaces without using extra cement complete all as specified and as directed.
Taking out old / unserviceable underground LT cables and connections including pipes, bricks or precast concrete cable cover etc from trenches / walls / poles of any cross sectional area and keeping serviceable materials in safe custody for reuse and unserviceable materials removing from site complete all as specified and directed.
Material and labour for underground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 Volts (earthed) grade cross sectional area 10 Sqmm, 2 core laid in trenches / pipes / ducts / wall / boardings with necessary cable lugs and glands, nuts, bolts and washers etc and testing including disconnecting and taking out of existing LT cable of any type and size complete all as specified and as directed. Note: - (i) Wherever cable fixing / connection, suitable thimble should be used as per site situation. (ii) Excavation and earth, sand cushioning and protection for cable work shall be measured and paid separately.
Material and labour for underground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 Volts (earthed) grade cross sectional area 16 Sqmm, 2 core laid in trenches / pipes / ducts / wall / boardings with necessary cable lugs and glands, nuts, bolts and washers etc and testing including disconnecting and taking out of existing LT cable of any type and size complete all as specified and as directed. Note: - (i) Wherever cable fixing / connection, suitable thimble should be used as per site situation. (ii) Excavation and earth, sand cushioning and protection for cable work shall be measured and paid separately.
Material and labour for underground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 Volts (earthed) grade cross sectional area 25 Sqmm, 3.5 core laid in trenches / pipes / ducts / wall / boardings with necessary cable lugs and glands, nuts, bolts and washers etc and testing including disconnecting and taking out of existing LT cable of any type and size complete all as specified and as directed. Note: - (i) Wherever cable fixing / connection, suitable thimble should be used as per site situation. (ii) Excavation and earth, sand cushioning and protection for cable work shall be measured and paid separately.
Material and labour for underground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 Volts (earthed) grade cross sectional area 35 Sqmm, 3.5 core laid in trenches / pipes / ducts / wall / boardings with necessary cable lugs and glands, nuts, bolts and washers etc and testing including disconnecting and taking out of existing LT cable of any type and size complete all as specified and as directed. Note: - (i) Wherever cable fixing / connection, suitable thimble should be used as per site situation. (ii) Excavation and earth, sand cushioning and protection for cable work shall be measured and paid separately.
Material and labour for underground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 Volts (earthed) grade cross sectional area 50 Sqmm, 3.5 core laid in trenches / pipes / ducts / wall / boardings with necessary cable lugs and glands, nuts, bolts and washers etc and testing including disconnecting and taking out of existing LT cable of any type and size complete all as specified and as directed. Note: - (i) Wherever cable fixing / connection, suitable thimble should be used as per site situation. (ii) Excavation and earth, sand cushioning and protection for cable work shall be measured and paid separately.
Material and labour for underground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 Volts (earthed) grade cross sectional area 70 Sqmm, 3.5 core laid in trenches / pipes / ducts / wall / boardings with necessary cable lugs and glands, nuts, bolts and washers etc and testing including disconnecting and taking out of existing LT cable of any type and size complete all as specified and as directed. Note: - (i) Wherever cable fixing / connection, suitable thimble should be used as per site situation. (ii) Excavation and earth, sand cushioning and protection for cable work shall be measured and paid separately.
Material and labour for underground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 Volts (earthed) grade cross sectional area 95 Sqmm, 3.5 core laid in trenches / pipes / ducts / wall / boardings with necessary cable lugs and glands, nuts, bolts and washers etc and testing including disconnecting and taking out of existing LT cable of any type and size complete all as specified and as directed. Note: - (i) Wherever cable fixing / connection, suitable thimble should be used as per site situation. (ii) Excavation and earth, sand cushioning and protection for cable work shall be measured and paid separately.
Material and labour for underground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 Volts (earthed) grade cross sectional area 16 Sqmm, 4 core laid in trenches / pipes / ducts / wall / boardings with necessary cable lugs and glands, nuts, bolts and washers etc and testing including disconnecting and taking out of existing LT cable of any type and size complete all as specified and as directed. Note: - (i) Wherever cable fixing / connection, suitable thimble should be used as per site situation. (ii) Excavation and earth, sand cushioning and protection for cable work shall be measured and paid separately.
Material and labour for underground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 1100 Volts (earthed) grade cross sectional area 25 Sqmm, 4 core laid in trenches / pipes / ducts / wall / boardings with necessary cable lugs and glands, nuts, bolts and washers etc and testing including disconnecting and taking out of existing LT cable of any type and size complete all as specified and as directed. Note: - (i) Wherever cable fixing / connection, suitable thimble should be used as per site situation. (ii) Excavation and earth, sand cushioning and protection for cable work shall be measured and paid separately.
Supply and fixing in replacement of 1100 Volt Arial bunched conductor having phase conductor of multistranded compacted circular aluminium conductor screen of extruded semi conducting compound extruded XLPE insulated, insulation screen of extruded semi conducting compound over all metallic screen of copper tape extruded PVC type ST-2 sheathed twisted around bare aluminium alloy messenger generally as per IS-7098 Part-II of size 3 x 50 Sqmm + 1 x 50 Sqmm, 1 X 35 Sqmm and 1 X 16 Sqmm complete with dead end clamp, suspension clamp, Eye Hook, welding and cable jointing kit as per site requirement with the existing LT disribution system complete all as specified and as directed.
Dismantling / taking up of LT unserviceable pre-stressed concrete / steel poles of any size and shape and including taking out dismantled portion of poles embedded in ground after necessary demolition of concrete foundation and making good disturbed ground surface properly and disposal thereof complete all as specified and as directed by Engineer-in-Charge. Note: - Earth work for taking out of poles shall be measured and paid separately under relevant item of this Schedule.
Material and labour for steel tubular swagged pole complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-31 (9.0 meters long) including two coats of silver paint over one coat of red oxide paint complete with strip of black and white strips having 30 cm of width upto 1.5 meter height from top of coping including taking out old unserviceale PCC pole complete all as specified and as directed by Engineer-in-Charge. Note: - Excavation, foundation concrete, preservative treatment etc shall be measured and paid separately.
Material and labour for pre stressed concrete pole 9.0 meter long 102mm X 172 mm at top and 12 mm and 279 mm at bottom class 10 with strip of black and white strips having 30 cm of width upto 1.5 metre height from top of coping including taking out old unserviceale PCC pole complete all as specified and as directed by Engineer-in-Charge.
Dismantling of ACSR conductors or disturbed span including line spacer and keeping serviceable materials in safe custody for re-use and unserviceable materials, removing from the site(s) complete all as specified and as directed.
Labour for rectification of fault related ACSR jumpers, insulators binding wire by removing old one and replacement with new wire binding or rejumper as required etc complete all as specified and as directed. Note: - Material shall be measured and paid separately under supply only.
Supply and fixing in replacment of ACSR conductor of any size and type from overhead HT / LT poles including binding at site to insulator with suitable size of binding wire etc including taking down existing worn out old broken ACSR conductor of any size and type and length at any position from LT / HT poles complete all as specified and as directed.
Fixing only by re-straining, tightening of ACSR conductors of any size / type on HT / LT poles including necessary new aluminium binding wire for fixing with insulator / PVC sleeves for jumper etc as required complete all as specified and as directed. Note: - Serviceable ACSR conductors shall be obtained from Ser item No. 27.00 here-in-before.
Material and labour in replacement of galvanised steel wire 4.0 mm dia for continuous earth wire and craddles hexagonal / rectangular shall be provided and securely fastened to each pole and connected with earth ordinarily and craddle guarding where required complete including dismantling existing GI wire all as specified and directed.
Dismantling cross arms of mild steel channel or angle sections etc. and keeping serviceable materials in safe custody for re-use and / or unserviceable materials removing from the site(s) complete all as specified and directed.
Material and labour in replacement of cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections i.e. mild steel channel or angle sections etc. including new nuts, bolts, washers as required dia / length in size, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat of red oxide, one under coat and one finishing coat of silver paint (1st quality) as required complete as specified and as directed.
Fixing only serviceable cross arm, mild steel channel, angle section obtained from Ser item No 32.00 here-in-before as ordered and inclusive of one coat of aluminium paint including preparation of old steel surfaces complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs / thimble of size 120 Sqmm complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs / thimble of size 70 / 95 Sqmm complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs / thimble of size 50 Sqmm complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs / thimble of size 35 Sqmm complete all as specified and directed.
Supply and fix in replacement unserviceable aluminium lugs / thimble of size 25 Sqmm complete all as specified and directed.
Supply and fix in replacement of onload changeover switch AC-23 (side handle) in sheet metal enclosure of capacity 200 Amp, 415 volts, 3 phase, four pole complete all as specified and as directed.
Dismantling LT stay assembly, of any size and unserviceable materials removing from the site(s) complete all as specified and as directed. Note: - (a) Unserviceable stay assembly shall be taken off / dismantled at ground level and making good disturbed ground surface. (b) Earthwork for demolition of cement concrete shall be included in quoted rate.
Material and labour for stay assembly with accessories and GI stay rod 16 mm dia 1900 mm long, stay wire 7/4 mm stranded galvanised including mild steel stay plate 300 mm x 300 mm x 6 mm and galvanised thimble, galvanised steel 14 mm dia 400 mm long stay bow and GI nuts, washers including loop type insulator vitreous porcelain white, brown or green big size with overall dimensions 90 mm x 140 mm clearance of hole 25.5 mm complete all as specified and shown in electrical plate No 01 of SSR Part - I including taking down old unserviceable stay assembly all as directed. Note: - Excavation, stay clamps and concrete work etc shall be measured and paid separately.
Dismantling insulators, any type, any size and keeping serviceable materials in safe custody for re-use and / or unserviceable materials removing from the site complete all as specified and as directed.
Material and labour insulator pin type, porcelain, vitreous, white, brown or green including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade complete all as specified and as directed.
Material and labour insulator pin type, polymer composit material including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade complete all as specified and as directed.
Fixing only serviceable pin type porcelain, vitreous, (white / brown or green) insulator for 1100 volts grade of any type obtained from Ser item No 43.00 here-in-before complete all as specified and as directed.
Material and labour insulator shackle type, porcelain, vitreous, white, brown or green, shall be in one piece and shall have a groove on the side and a hole for a cotter pin and two galvanised bolts 12 mm dia and nuts with or without a pair of straps in size 31 x 3 mm as indicated size height 75 mm and dia 90 mm, for working pressure 1100 volts complete as specified and as directed.
Material and labour for Earthing complete with galvanised mild steel earth plate electrode of size 600 x 600 x 6mm thick buried directly in ground earth (in vertical) earth pit not less than 2.25 metre deep below normal ground level with top edge of the earth plate not less than 1.5 metre below ground level connected to galvanised iron or earth lead wire 4mm dia (8 SWG) by means of nut, bolt, check nuts and washer of galvanised iron including PCC pit in PCC (1:2:4) type B-1 pre-cast RCC cover slab using reinforcement with suitable handle made of round bar, including necessary excavation and earth work in any type of soil, 20mm dia medium grade galvanised steel tube for watering with one end fixed with cast iron funnel and wire mesh 15mm dia bore light grade galvanised steel tubing upto 5 m length for drawing earth lead wire protection, common salt, charcoal etc complete all as shown in electrical plate No 3 of SSR Part-I and including dismantling and taking down old unserviceable complete all as specified and as directed.
Supply and fix outdoor / indoor end termination joint heat shrinkable 1.1 KV grade cable complete with jointing material (Epoxy Based) and accessories suitable for 3½ or 4 core XLPE armoured aluminium conductor cable of size 10 to 50 Sqmm complete all as specified and as directed.
Supply and fix outdoor / indoor end termination joint heat shrinkable 1.1 KV grade cable complete with jointing material (Epoxy Based) and accessories suitable for 3½ or 4 core XLPE armoured aluminium conductor cable of size 70 to 150 Sqmm complete all as specified and as directed.
Supply and fix outdoor / indoor end termination joint heat shrinkable 1.1 KV grade cable complete with jointing material (Epoxy Based) and accessories suitable for 3½ or 4 core XLPE armoured aluminium conductor cable of size 185 to 300 Sqmm complete all as specified and as directed.
Supply and fix outdoor / indoor end termination joint heat shrinkable 1.1 KV grade cable complete with jointing material (Epoxy Based) and accessories suitable for 3½ or 4 core XLPE armoured aluminium conductor cable of size 400 Sqmm complete all as specified and as directed.
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material (Epoxy Based) and accessories suitable for 3½ or 4 core XLPE armoured aluminium conductor cable of size 25 to 50 Sqmm complete all as specified and as directed.
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material (Epoxy Based) and accessories suitable for 3½ or 4 core XLPE armoured aluminium conductor cable of size 70 to 90 Sqmm complete all as specified and as directed.
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material (Epoxy Based) and accessories suitable for 3½ or 4 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm complete all as specified and as directed.
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material (Epoxy Based) and accessories suitable for 3½ or 4 core XLPE armoured aluminium conductor cable of size 240 to 400 Sqmm complete all as specified and as directed.
Supply and fix PVC flat fibre separator for LT line 1100 volt overhead conductor 3 / 4 / 5 wire system for maintaining horizontal spacing of conductor complete with nut and bolt in a span all as specified and directed.
Supply and fixing in replacement insulation rubber matting sheet of size 1 meter x 2 meter x 10 mm conforming to ISI electric shock proof 1100 Volt grade complete all as specified and as directed.
Taking out existing old unserviceable STS poles (09 and 11) meters long of any type from the PCC foundation, couping and including carefully taking down existing ACSR conductor, cables, street light, security light fitting, GI brackets, looping boxes, stay assembly of any type and pattern etc, after disconnection of electric supply by using necessary T&P / Crane / any mechanical method will be applied and disposal of debris upto distance not exceeding 100 m complete all as specified and directed. Note: - Hire charges of T&P / crane / hydra / JCB etc for disconnection of electric supply and cost of disposal of debris shall be deemed to be included in the unit quoted rate.
Supply, fixing and erection of steel tubular swagged pole 09 m long, type 410 SP-32, weight not less than 154 kgs, pole should be in one piece only and smooth finishing, ISI marked conforming to IS : 2713-1980, complete with all accessories, such as cast iron base plate, finial taper plug, bolts, nuts, screws, washers and drilling of holes for continuous GI earth wire as specified including applying two coats of aluminium paint over one coat of red oxide zinc chrome primer and embedded portion shall be painted with two coats of black japan paint after preparation of surface complete all as specified and directed. Note: - Excavation and earth work shall be measured and paid separately.
Material and labour for sand cushioning for protection of underground cable consolidated and compacted with clean dry sand all as specified and as directed. Note: - Compacted thickness shall only be measured and paid.
Supply, install and testing including replacement of moulded case circuit breaker (MCCB), adjustable thermal and fixed magnetic type, 4 Pole, 415 volts, 50Hz, breaking capacity 25 KA, rating 63 Amp capacity, complete as per OEM standard design, all as specified and as directed by Engineer-in-Charge.
Supply, install and testing including replacement of moulded case circuit breaker (MCCB), adjustable thermal and fixed magnetic type, 4 Pole, 415 volts, 50Hz, breaking capacity 25 KA, rating 100 Amp capacity, complete as per OEM standard design, all as specified and as directed by Engineer-in-Charge.
Supply, install and testing including replacement of moulded case circuit breaker (MCCB), adjustable thermal and fixed magnetic type, 4 Pole, 415 volts, 50Hz, breaking capacity 25 KA, rating 125 Amp capacity, complete as per OEM standard design, all as specified and as directed by Engineer-in-Charge.
Supply, install and testing including replacement of moulded case circuit breaker (MCCB), adjustable thermal and fixed magnetic type, 4 Pole, 415 volts, 50Hz, breaking capacity 25 KA, rating 160 Amp capacity, complete as per OEM standard design, all as specified and as directed by Engineer-in-Charge.
Supply, install and testing including replacement of moulded case circuit breaker (MCCB), adjustable thermal and fixed magnetic type, 4 Pole, 415 volts, 50Hz, breaking capacity 25 KA, rating 200 Amp capacity, complete as per OEM standard design, all as specified and as directed by Engineer-in-Charge.
Supply, install and testing including replacement of moulded case circuit breaker (MCCB), adjustable thermal and fixed magnetic type, 4 Pole, 415 volts, 50Hz, breaking capacity 25 KA, rating 250 Amp capacity, complete as per OEM standard design, all as specified and as directed by Engineer-in-Charge.
Supply, install and testing including replacement of moulded case circuit breaker (MCCB), adjustable thermal and fixed magnetic type, 4 Pole, 415 volts, 50Hz, breaking capacity 25 KA, rating 315 Amp capacity, complete as per OEM standard design, all as specified and as directed by Engineer-in-Charge.
Supply, install and testing including replacement of moulded case circuit breaker (MCCB), adjustable thermal and fixed magnetic type, 4 Pole, 415 volts, 50Hz, breaking capacity 25 KA, rating 400 Amp capacity, complete as per OEM standard design, all as specified and as directed by Engineer-in-Charge.
Supply, install and testing including replacement of moulded case circuit breaker (MCCB), adjustable thermal and fixed magnetic type, 4 Pole, 415 volts, 50Hz, breaking capacity 25 KA, rating 600 Amp capacity, complete as per OEM standard design, all as specified and as directed by Engineer-in-Charge.
Cutting, trimming and vending tree branches along HT overhead lines, after arranging electrical shutdown, including taking all precautions while working on lines using own T&P by the contractor complete all as specified and directed by Engineer-in-Charge. Note: - (i) Branches of trees shall be cut upto 3 metre from the outer conductor of overhead line. (ii) Cutting / trimming of branches shall be done after obtaining necessary shut down in writing by the Engineer-in-Charge to avoid any casuality.
Supply and fixing in replacement of aluminium socket and lugs of appropriate size after disconnecting the cable of any size 1100 volt grade from panel and de-reeling the loop, including cutting out and removing the burnt portion of the cable end and relaying the serviceable portion in the existing position / layout including necessary earthwork, chases cutting in PCC work, taking out and relaying bricks and making good the disturbed surfaces and testing complete all as specified and as directed.
Material and labour for carrying out repairs to the repairable APFC Panels including servicing / replacing wornout nuts, bolts, cable lugs, connecting wires, markers, insulating sleeves, repairs to PCC foundation etc and replacement of power capacitors with equal or higher capacities, capacitor switching duty contactor, suitable APFC relay, HRC fuse links etc including reinstallation at original or at a new location all as specified and as directed. Note: - Replacement of power capacitor, capacitor switching duty contactor and APFC relay, HRC fuse links will be measured separately but cost for the the rest items required to make the APFC controller functional to achieve best result should deem to be included in the rate.
Supply and fixing in replacement of power capacitor MPP Dry type heavy duty (THDI 20%) of following capacities: -
10 KVAR, make of capacitor as per existing one in the APFC.
20 KVAR, make of capacitor as per existing one in the APFC.
05 KVAR, make of capacitor as per existing one in the APFC.
Supply and fixing in replacement of APFC relay suitable for banks upto 8 steps complete all as specified and as directed.
Supply and fixing in replacement of 3 Ø 415 V, 50 Hz type MO C 20 capacitor switching duty contactor suitable upto 25 KVAR rating complete all as specified and as directed.
Digital Panel Meter 96 X 96 mm suitable for measuring Alternating Current 5 A class I.
Digital Panel Meter 96 X 96 mm suitable for measuring AC Voltage class I.
CT for measuring AC on LT 3 phase system, 6.6 KV grade, single burden, general purpose, of CT ratio as per site requirement.
LED indicator lamps for phases flicker type including holders and of colours red / yellow / green / blue etc.
Bakellite kit kat fuse base with fuse holder complete all as specified and as directed upto 32A rating.
Supply and fix in replacement of underground cable route indicator made out of PCC (1:3:6) of size 45 X 30 X 10 cm blocks writing MES, direction of cable, class / voltage rating for LT / HT complete all as specified and as directed.
Supply and fix in replacement of danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolt and nut approved size for LT poles, 20 x 15cm size including taking out old unserviceable danger notice plate complete all as specified and as directed.
Supply and fixing in replacement of PVC line separator suitable for 2 conductor complete all as specified and as directed.
Supply and fixing in replacement of PVC line separator suitable for 4 conductor complete all as specified and as directed.
Cutting and removing grass and wild growth including bushes and shrubs from the roots at various E&M installations including removing the wastage materials including broken bricks, stones, boulders etc and depositing where directed and levelling the entire cleaned area to even finish complete all as specified and directed at site.
Taking out old / unserviceable underground LT cables and connections including pipes, bricks or precast concrete cable cover etc of any from trenches / walls / poles of any cross-sectional area and removing from site all as specified and directed.
Supply only for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply only for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 150 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply only for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 185 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply only for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 240 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 400 Sqmm complete all as specified and directed.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 300 Sqmm complete all as specified and directed.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 240 Sqmm complete all as specified and directed.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 185 Sqmm complete all as specified and directed.
Labour for taking out all incoming / outgoing electric connection from LT panel / starter / motor / voltage stabilizer carefully for repair to cable / rectification the fault and re-connecting in position after repair and preparation the cable and fixing complete with nut, bolts, washers for cable size 120 to 400 Sqmm including preparation of 3.5 core cable, 4 wire each along with connected items like thimble, insulation tape and will be considerable in this job complete all as specified and as directed.
Supply and fixing in replacement unserviceable indicators LED set of three pieces as per existing size and sample complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement Ampere meter analog type 0-400 Amp CT with suitable set of size 96 Sqmm square type flush panel mounted complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement Volt meter analog type 0-500 Volt 96 Sqmm square type flush panel mounted complete all as specified and as directed by Engineer-in-Charge.
Material and labour for replacement of MCCB 3 pole, current rating 100 Amp, thermal setting adjustable type 70%-100% rapturing capacity 16 KA at 415 V, 50 Hz complete all as specified and as directed.
Material and labour for replacement of MCCB 3 pole, current rating 125 Amp, thermal setting adjustable 70%-100% rapturing capacity 16 KA at 415 V, 50 Hz complete all as specified and as directed.
Material and labour for replacement of MCCB 4 pole, current rating 160 Amp, thermal setting adjustable 70%-100% rapturing capacity 36 KA at 415 V, 50 Hz complete all as specified and as directed.
Material and labour for replacement of MCCB 4 pole, current rating 200 Amp, thermal setting adjustable 70%-100% rapturing capacity 36 KA at 415 V, 50 Hz complete all as specified and as directed.
Material and labour for replacement of MCCB 4 pole, current rating 250 Amp, thermal setting adjustable 70%-100% rapturing capacity 36 KA at 415 V, 50 Hz complete all as specified and as directed.
Material and labour for replacement of MCCB 4 pole, current rating 400 Amp, thermal setting adjustable 70%-100% rapturing capacity 36 KA at 415 V, 50 Hz complete all as specified and as directed.
Material and labour for replacement of MCCB 4 pole, current rating 630 Amp, thermal setting adjustable 70%-100% rapturing capacity 50 KA at 415 V, 50 Hz complete all as specified and as directed.
Supply and fixing in replacement of onload changeover switch AC-23 (side handle) in sheet metal enclosure of capacity 100 Amp, 415 Volts, 3 phase, four pole complete all as specified and as directed.
Supply and fixing in replacement of onload changeover switch AC-23 (side handle) in sheet metal enclosure of capacity 200 Amp, 415 Volts, 3 phase, four pole complete all as specified and as directed.
Taking down unserviceable street / security light fitting of any type from the pole / building after disconnecting electric connection carefully complete all as specified and directed. Note: - Repair / replacement of spares shall be measured separately.
Supply and fixing in replacement distribution board including fix timer switches astro type (having longitude and latitude of Indian cities in memory) 250 V single phase of 20 Amp rating with contactor fitted inside steel enclosure complete all as specified and as directed.
Supply and fixing LED street light fitting 45 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP-65/66 protection complete all as specified and as directed.
Supply and fixing LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP-65/66 protection complete all as specified and as directed.
Supply and fixing LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP-65/66 protection complete all as specified and as directed.
Supply and fixing LED street light fitting 120 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP-65/66 protection complete all as specified and as directed.
Supply and fixing LED flood light fitting of capacity 200 watt including inbuilt surge protection as per requirement LED flood light fittngs along with IP-65/66 protection complete all as specified and as directed.
Labour charges for repair / maint to old / unserviceable LED security / Street / flood light / High mast light of any capacity including taking down existing fitting from pole / building for replacement of unserviceable driver, cable terminal block and connection wire and refixing the same in position after repair including testing all as specified and directed by Engineer-in-Charge. Notes: - (i) Spares shall be measured and paid separately under respective item. (ii) Sufficient Electrician and Helper shall be deputed daily to concerned sub division during office hours to ascertain the repairs to be carried out for lights under his AOR. (iii) Electronic drivers, if required to be replaced shall be measured and paid separately as under relevant items of this BOQ as SUPPLY ONLY. (iv) Necessary arrangements for carrying out repairs shall be undertaken by the contractor.
Supply and fixing in replacement of electronic driver of capacity 45 watt of existing make for LED street light fitting complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement of electronic driver of capacity 60 watt of existing make for LED street light fitting complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement of electronic driver of capacity 90 watt of existing make for LED street light fitting complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement of electronic driver of capacity 120 watt of existing make for LED street light fitting complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement of electronic driver of capacity 200 watt of existing make for LED flood light fitting complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in repair servicing solar street light including cleaning of solar panels, checking and cleaning battery and all connection terminals, distilled water topup, solar battery charging controller, LED driver complete all as specified and directed.
Supply and fixing solar street light lead acid battery 12 V 75 AH, fixed as in repairs complete all as specified and directed.
Supply and fixing MPPT solar PWM controller suitable for battery sizes 12 / 24 / 36 / 48 V, 40 / 60 A including connection and testing, fixed as in repairs complete all as specified and directed.
Supply and fixing in replacement of PVC insulated and sheathed cable of size 1.5 Sqmm 3 core aluminium conductor multistranded 1100 volt grade 230 volts complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement Monocrystalline solar photo voltaic 12 V, 180 W panel suitable for solar street light including fixing on existing mounting brackets with appropriate angle 45˚ to 60˚ to attain maximum efficency including connecting and testing, fixed as in repairs complete all as specified and directed.
Supply and fixing in replacement fabrication bracket made out of GI tubing suitable for 45 / 60 / 90 watt LED light grade upto 1.2 metre length, bend to shape suitable for security light fitting with necessary mild steel clamps with one coat of red oxide and two coats of aluminium paint including nut, bolt, washers etc and including taking out unserviceable bracket and removing from site of work complete all as specified and as directed.
Supply and fixing in replacement SMC pole mounted box of size 250 X 200 X 100 mm with hinged door including clamp, nuts, bolts and washers complete all as specified and directed and including following accessories: - (a) MCB SP 10 Amp, 10 KA 'C' series mounted on din rail - 1 No. (b) Connector block suitable for 3 ph, 4 wire min 10 Sqmm cable - 1 No.
Supply and fixing in replacement of LED water proof, fancy modern unbreakable outdoor type 230 V, 50 Hz AC garden light fitting including 7 watt LED bulb, fixed in galvanized steel pipe / pillar complete all as specified and directed.
Supply and fixing in replacement LED solar street light fitting 12 watt including galvanized steel pole in built, lithium ion battery, solar panel, charge controller with dusk down sensor complete all as specified and as directed. Note: - Excavation and earth work shall be measured separately.
NOTE NO 1: - Samples of materials as approved will be kept in GE's sample room. NOTE NO 2: - All fittings and fixtures mentioned above will be fixed to the satisfaction of Engr-in-Charge and GE. NOTE NO 3: - Warranty certificate to the Engineer-in-Charge where ever applicable shall be submitted by the Contractor at the time of fittings.
M/s. Aggarwal Engineers
Prakash Trading Corporation
Bidder Name
Prakash Trading Corporation
Sarbat Construction Co
M/s. Aggarwal Engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .