Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.2 LAccepted-AOC R O H NO 55 SEC D BHARAT NAGAR TALAB TILLO JAMMU 180002 | JAMMU | JAMMU AND KASHMIR | 180002 | L1 | Accepted-AOC Being lowest bidder. | |
| 2 | L2₹32.8 L+₹3.6 L (12.2%)Rejected-Finance NOT SPECIFIED | L2 | Rejected-Finance Being other than lowest bidder. |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
24 Jul 2025, 6:00 pmClosed
GE 873 EWS
Garrison Engineer 873 Engineer Works Section PIN 913 873 C/O 56 APO
SPECIAL REPAIR (E/M) TO BLDG NO T-286 AT SKAMPUK, T-10 AT BASE CAMP, SPL REPAIR (E/M) AND REPLACEMENT OF OLD UNSERVICEABLE UG CABLE AND LT POLE AT SKAMPUK, SPL REPAIR OF PROVIDE EXTERNAL ELECTRIFICATION UNDERGROUND CABLE, LT PANEL AND ALLIED INFRA A
2025_MES_718353_1
GE/873/EWS-49/2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 873 EWS
Please refer NIT and Tender Documents
8 documents required · 8 mandatory
₹500
GE 873 EWS
₹70,000
Yes
4 Aug 2025
3 Jul 2025
26 Jul 2025
3 Jul 2025
24 Jul 2025
17 Jul 2025
5 Jul 2025 - 12 Jul 2025
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as perconditions separately) and making good disturbed surfaces of walls, floors, etc. complete all as specified and directed.
Taking down of MCB DB /TPN 8 way /12 way including MCB SP and SPN and making good of wall complete all as specified and directed.
M&L Point wiring with 1.5 Sqmm (nominal area) copper conductor FRLS cable (multi-stranded) PVC insulated and unsheathed electric cable 1100 volts drawn through PVC casing and caping of suitable size (as per conductor run) with all fittings and accessories and including PVC insulated unsheathed electric cable 1100 volts 1.5 Sqmm (multi-stranded) copper conductor single core (green colour) as continuous earth wire connected to common earth dolly including 50mm deep box made out of 2nd class hard wood board of suitable size and shape and other boxes for mounting light fittings etc covered with 3mm thick plastic laminated Hylum ISI marked for following complete all as specified and directed. Note:- Screw used for fixing TW baords, casing and caping ceiling rose, square blocks etc should be nickel cadmium screws.
(a) One light/fan point controlled by one 5 Amps one way switch
(b) One 3 pin socket outlet 5 Amps on independent board
(c) One 3 pin socket outlet 5 Amps on same board
M&L point wiring for power point with 4.0 sqmm (nominal area) copper conductor FRLS cable ( multi-stranded) PVC insulated and unsheathed cable conductor 1100 Volts drawn through PVC casing capping of suitable size(as per conductor run) with all fittings and accessories and including PVC insulated unsheathed electric cable 1100 volts 2.5 Sqmm (multi-stranded) copper conductor single core (green colour) as continuous earth wire connected to common earth dolly including 50mm deep box made out of 2nd class hard wood board of suitable size and shape and other boxes for mounting light fittings etc covered with 3mm thick plastic laminated Hylum ISI marked for following complete all as specified and directed by Engr-in-Charge. Note:- Screw used for fixing TW baords, casing and caping ceiling rose, square blocks etc should be nickel cadmium screws.
S&F Switch piano flush button single pole one way 5 Amps, 240 Volts complete all as specfied and directed.
S&F socket outlet 2 in 1, 3pin, 6A(multipurpose) sutable for 3 pin/5 pin plug flush type complete all as specified and directed.
S&F switch socket combination 3 pin, 5 Amps, 2in1, flush type (multipurpose) 2 pin / 3 pin plug Complete all as specified and directed.
S&F switch socket combination 2 in 1, 3 pin, 5/15 Amps, flush type (multipurpose). Complete all as specified and directed.
S&F Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and directed.
Supply and fixing Rechargeable LED Bulb energy saver 9 W, B22(220-240 V) 50 hz, 6500k fast charging 2200mAH battery including, white color all as specified and as directed. Make:- CG/Phillips/Havells
S&F surface and wall mounted LED batten with polycarbonate housing and integrated electronic driver tube light fitting 20W, 4 ft long, 220 Volts, and connecting to ceiling rose with three core twisted flexible copper cable of suitable size complete all as specified and directed.Make:- CG/Phillips/Havells
S&F surface and wall mounted LED batten with polycarbonate housing and integrated electronic driver tube light fitting 22W, 4 ft long, 220 Volts, and connecting to ceiling rose with three core twisted flexible copper cable of suitable size complete all as specified and directed.Make:- CG/Phillips/Wipro
S&F Ceiling rose surface backelite ISI marked with 3 terminal including connecting and testing complete all as specified and directed.
Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed.CG/Phillips/Havells
Supply and fixing LED luminaire 300 mm x 300 mm, 22/25 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed.CG/Phillips/Havells
S & F 3 Watt spot light , focus light, colour- warm white spot light ceilling lamp
Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed by Engr-in-Charge.
S&F MCB DB sheet enclosure, Double door type, single pole and neutral 240V with 200 Amp rated bus bar suitable size plate and common neutral link all enclosed in standard steel sheet flush mounting type factory fabricated complete confirming to IP 42/43 without MCB and with enclosure blank plates for unused way suitable for 8 way complete all as specified and directed. Make: Havells , L & T or equivalent
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning all as specified and directed. Make: Legrand/Havells or equivalent
Supply and fixing MCB SPN 240V, 10KA 'C' curve(40- 63 )Amp current carrying capacity in the MCB DB complete with connection testing and commissioning all as specified and directed.Make: Legrand/Havells or equivalent
Supply & fixing LED light fitting 1x10W bulkhead luminaires including LED light and driver holder connecting up with three core flexible copper conductor cable of suitable size all as specified and directed. Make Havells/Wipro/CG/Phillips or equivalent.
M&L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6mm thick burried directly in ground not less than 2.25m deep below normal ground level (with the top edge of the plate not less than 1.50 m below the normal ground level) connected to GI earth wire 4 mm by means of GI bolts, nuts, check nuts and washers of GI all as shown in electrical plate No.3 of SSR Part-I connected to earthing test point with and including necessary excavation and earth work in any strata PCC pit 1:3:6 type C-1, 20mm bore medium grade GI pipe for watering 15mm bore light grade pipe for GI wire protection and funnel including 40mm thick RCC slab cover and testing on completion all as specified and as directed.
M & L GI GI pipe (medium grade, ISI marked) 32mm dia, 1.5 long, bend to shape for street light fitting bracket with 2xpairs of MS clamps of suitablelength of size 40x5 mm of MS flat iron with nuts bolts and washer and taking out old one including connection with street light complete all as directed.
Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete making all necessary connection with suitable capacity of 3 core circular cable complete all as specified and directed. Make Havells/Wipro/CG/Phillips or equivalent.
Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 HZ, RPM 1200, Copper winding of sweep 250mm (Make- Havells ventiar DX or equivalent) all as specified and directed.
Taking out un-serviceable/faulty cable/service connection cable of any grade / type / class of any size for repair / replacement from pole / wall / cable duct under ground trench etc for re-use or removal from site of work all as specified and as directed. (Note- Excavation and earth work shall be measured and paid separately)
Supply, laying, fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 10 sqmm 2 core complete all as specified and directed.
M & L for GI Pipe (medium grade, ISI Marked) 25 mm dia laying and fixing on ground and wall for cable protection as specified and directed by Engr in Charge.
Supply, laying, fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 25 sqmm 3.50 core complete all as specified and directed.
Supply, laying, fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 35 sqmm 3.50 core complete all as specified and directed.
Supply, laying, fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 35 sqmm 4 core complete all as specified and directed.
Supply, laying, fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 25 sqmm 4 core complete all as specified and directed.
Supply, laying, fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 16 sqmm 4 core complete all as specified and directed.
Supply, laying, fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 50 sqmm 3.50 core complete all as specified and directed.
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtrs in depth for laying of cable, fixing of stay etc 10 Sqm 2 core/25sqmm 4 core/50 sqmm 4 core on plan and exc 1.5 in depth and getting out in hard/dence soil complete all as specified and directed.
Returing, filling in incl spreading, levelling watering and well remming in layers n.exc 25cm width, Complete all as specified and directed.
Removing excavated material to a distance not exc 50m and depositing where directed at level not exc 1.5m above the starting point all as specified and directed
M&L for sand cushioning to underground cables using new dry river sand laid in trenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete, punned to 18cm, complete all as specified and directed. Note : Punned thickness of 18cms shall be measured for payment.
M&L Un-reinforced precast factory made concreate cable covers, class LV type-I, with flat size 250x150x40 mm Complete all as specified and directed.
Supply and laying/fixing, GI pipe medium grade 40 mm bore (dia)including all type fittings fixed on walls/to poles with clamps /laid in trenches as cable protection all as specified and directed.
Supply and erecting and fixing in proper positing steel tubular swaged poles complete with cast iron base plate, final taper plug, bolts, nuts and screws as specified type 410 SP-31 (9.00 meters long). Make; Advance steel tube, Natinal tubing co, Mahindra industries, Sohan lal and sons, Sidhartha all as specified and as directed (Note: (i) Excavation, earth work and PCC shall be measured and paid separately. (ii) Painting will be measured and paid seperately under relevent item
M & L for PCC (1:4:8) type D2 using 40mm graded stone aggreagate of pit for bed concrete in foundation of poles/stay complete all as specified
Materail & Labour for PCC (1:3:6) type C-2 using 40 mm graded aggreagate as in foundation pole/stay and filling of mass concrete includding providing necessary form work complete all as specified and as directed.
Material and Labour for PCC (1:2:4) type B-1 using 20mm graded aggreagate as in coping of pole including providing necessary from work complete all as specified and as directed
M & L for bracket made out of GI tubing 25mm dia, light grade 1.5 mtr long including fixing with MS clamps-2 Nos made out of 25mm wide 3mm thick flat iron with M.S nuts bolts 75mm long 12 mm dia - 4 Nos with flat washer (3 mm thick)-02 No for each including painting with aluminium paint over one coat of red oxide to the M. S clams & bracket etc complete.
Supply & fix junction box of size 280x170x130 mm cat No GS-JB-2817 Hinged (L) with 2 way connector mounted on epoxy insulators for looping of cable for 1 phase and 1 neutral fixed on pole with the help of MS nuts bolts and MS clamps-2 Nos of size 40mmx4mm thick with one No MCB SP 6 Amp capacity mounted on din rail inside box. work also includes making suitable hole in to take out connections to fitting if required at site and provisioning of 1.0 sqmm 3.0 core flexible PVC insulated copper cable from junction box to conector of street light.
Supply and fixing of bus bar panel factory made dust proof and vermine proof outdoor type made of 3.15mm thick CRCA sheet size 80cm x 40cm x 40cm with leg of 45cm height from the ground level and o4 nos of aluminium bus bar with colour code i.e. R, Y, B and neutral complete all as specified and directed by Engr-in-Charge.
Supply and fixing 1.5 Sqmm (nominal area) copper conductor FRLS cable (multi-stranded) PVC insulated and unsheathed electric cable 1100 volts drawn through PVC casing and caping of suitable size ( as epr conductor run) will all fittings and accessories and including PVC insulated unsheathed electric cable 1100 volts 1.5 Sqmm (multi-stranded) copper conductor single core (green colour) as continuous earth wire connected to common earth dolly including 50mm deep box made out of 2nd class hard wood board of suitable size and shape and other boxes for mouting light fittings etc covered with 3mm thick plastic laminated Hylum ISI marked
Supply, Install Testing & Commissioning of self supporting totally enclosed double door at front, LT feeder piller compartmentalised design, dust and varmin proof of size 800 mm(Height) x 400 mm(Length) x 400 mm(Width) suitable for 440 Volt 3 phase 4 wire system made out of 3.15 mm thick CRCA sheet and built upon regid frame work having front and rear hinged doors with neoprence rubber gasket including danger plate, earthing strip point and, ventilation louvers at the rear side, bottom detachable gland plate complete with suitable size of Zinc/Cromium plated and nuts, bolts ;and washers etc. The pannel shall be synthetic enamelled painted and the control circuit diagram shall be with colour code solid conductor copper 1.5 sqmm cable for easy identification including incomming/outgoing cable holes at the bottom, complete after taking down the old unserviceable one. The Panel shall be emmbeded with 75 x 6 mm MS Angle Iron frame and to be grouted with PCC foundation (1:2:4) type B2 upto a height of 50 cm from normal ground level complete all as specified, directed and comprising of the following.
Item no. 50 Contd... (a) Aluminium bus bar 200 amps - 04 Nos, supported with suitable size of heavy duty porcelin stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCB of SPN of 4 pole, 63 amps, 10 KA, with breaking capacity of 25 KA, (Make: L & T/Havells) - 01 No (c) MCB of SP 06 to 32 A, 10 KA (Make: L & T/Havells) - 02 No INDICATING DEVICES (a) LED Indicating lamps for Main Supply indicating R', Y' B' - 01 Set of 3 (b) Digital Voltmeter (Make AE/L&T) - 01 No (c) Current Transformer having Ratio 400/5, 15 VA - 01 Set of 3 (d) Digital Ammeter ( Make(AE/L&T) - 01 N0
S & F DB sheet enclosure, Double door type, single pole and neutral 240V with 200 Amp rated bus bar suitable size plate and common neutral link all enclosed in standard steel sheet flush mounting type factory fabricated complete confirming to IP 42/43 without MCB and with enclosure blank plates for unused way suitable for 12 way complete all as specified and directed . Note:- Havells, L & T or equivalent
M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground not less than 2.25m deep below normal ground level (with the top edge of the plate not less than 1.50 m below the normal ground level) connected to GI strip 32x6 mm by means of GI bolts, nuts, check nuts and washers of GI all as shown in electrical plate No 3 of SSR Part-I connected to earthing test point wit and including necessary excavation and earth work in any strata PCC pit 1:3:6 type C-1, 20mm bore medium grade GI pipe for watering 15mm bore light grade pipe for GI wire protection and funnel including 40mm thick RCC slab cover and testing on completion all as specified and directed
Excavation in trenches not exceeding 1.5 mtr wide and above exceeding 1.5 mtrs in depth for laying of cable, pole, fixing of stay etc 10 Sqm 2 core/25 Sqmm 4 core/50 Sqmm 4 core on plan and above exc 1.5 in depth and getting out in hard/dence soil complete all as specified and directed.
Deduct Schedule of Credit of Rs (-) 99,6 91.00 (Minus) as listed in Schedule 'A' Part-II. Contract Sum shall be arrived after deducting the credit amount. Note :- Tenderers will not quote against this item being a firm amount.
M/S R P SINGH & COMPANY (BID ID -3369820)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .