Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.1 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹23.3 L+₹6.1 L (35.7%)Rejected-Finance | L2 | Rejected-Finance Highest |
Tender Value
₹23.9 L
EMD Value
₹23,930
Closing Date
3 Nov 2021, 11:00 amClosed
RE Electrical RHB
Resident Engineer Division Electrical Rajasthan Housing Board Jaipur
Repair and maintenance of 33 0.4 KV sub station DG Sets with External Electrification at Dwarka Appartment Mansarovar Jaipur
2021_RHBCE_245173_1
RE_Electrical_01/2021-22
Open Tender
Repair and Maintenance Works
Item Rate
365 days
Jaipur
As per NIT
2 documents required · 2 mandatory
₹1,180
As per NIT
₹23,930
Yes
11 Dec 2023
25 Oct 2021
3 Nov 2021
25 Oct 2021
3 Nov 2021
25 Oct 2021
Amount
Part -A (Repairing work)
Carry out one time general inspection, ON/OFF operation, cleaning and lubrication of operating mechanism wherever required, checking of earth value of all earth electrodes, identify shortcoming/fault, repairing, tightness of all connections, testing and commissioning of following HT/LT equipment outdoor Services of etc as required. (NOTE: In this item any faulty item required to replace, consuable items for routine servicing are not included and shall be paid separately.)
1600 KVA, 33 KV/0.433KV Oil cooled Tansformer Out door type Sub staion with 36KV 1250 Amp VCB Panels (3 Nos), 33 KV CR panel (1 No Feeder type & 2 Nos. Transformer type), Oil filled CT & PT, Lightening Arrestors, Double brake without EB Isolators, Jumpering & Bus bar strainging by ACSR panther conductor, PG Clamps/T Clamps, Dry type maintenance free 110V DC 120 AH battery with battery charger, Earthings with earthing lead etc. - 2 Sets
75/80KVA, 1500 RPM, 0.8 PF, 415 Volts Air Cooled silent DG Sets with control panel having Microprocessor based Genset monitoring & control system, MCCB etc including AMP Panel Electro-Mechanical Relay based with control & power contactors, timmers, visual & Alarm indication for faults, UPS, operating interface panel etc , LT cables with terminatios, Earthing and earthing lead etc. - 4 Sets
LT Cubicle panel operating on 440 Volt, 50 Hz AC supply comprise Main Panel having 2 Nos. incommer & 1 No Bus coupller drawout type ACBs with Outgoing MCCBs/MCBs, In each block Common distribution panel and metering panels (Upto supply point), Different sizes LT XLPE Cables for distribution with end terminations, Earthing & earthing lead etc. - 1 Set
Compound Lighting comprise with 7 Meter single/double arm Octagonal MS poles, controlgear box, Feeder Pillers, under ground XLPE cable, earthing and earthing lead etc - 50 Nos.
150 Watt HPSV Street light luminaire with copper bllast, electronic ignitor, capacitor, holder etc - 60 Nos.
carry out one time general inspection of feeder cable with 12.8 Mt long lattice towers, ON/OFF operation, identify shortcoming/fault, repairing, tightness of all connections, testing and commissioning of 33KV 3 core 300 sqmm feeder cable (3-4 Km of each feeder) from GSS to incommer of Sub station etc as required. (NOTE: In this item any faulty item required to replace are not included and shall be paid separately.)
Replacement of following faulty items/providing following consumeable items of the Electro-Mechanical services against Item no. 1 & 2
Oil filter of 75/80 KVA DG set
Diesel filter of 75/80 KVA DG set
Lub Oil 20W40/25W50
180 AH Lead Acid Battery
Transformer Oil for toping
110 volt battery Charger
Coolent
diesel
SITC of dry type battery set Maintenance free
SITC of 110 volt 120 AH Battery charger
Replacement of earth fault and overcurrent relay relay suitable for 33KV 1600KVA transformer Sub station (Main feeder/Transformer) including rectification of fault, testing etc as required. Details of relay make: C&S ELECTRIC TYPE: CSENEX-I 101
Replacement of burnt control wiring from Tr-1 with suitable size PVC insulated copper conducter 1.1KV cable including testing etc as required.
Repairing/replacement of spring charging motor of 33KV VCB including testing etc as required.
Providing and making heat shrinkable type indoor/outdoor /straight through terminations/joint kit of Grour1 and approved make suitable for XLPE insulated 11 KV/ 33 KV cable, with required component, prepration of cable ends, testing etc as required of following sizes.
3 core 300 sqmm outdoor type
3 core 300 sqmm straight through type
Calibration of all the safety devices like relays and fuses, tripping system of VCBs of 33KV Outdoor Sub Station etc as required
Checking and setting up all controls of AMF panel and all safeties of DG set etc as required
Part -B
OPERATION & MAINTENANCE WORK
Providing one number SKILLED Manpower in one shift of 8 hour on all days including sundays & holidays for ONE MONTH for operation & maintenance of electrical installations at
1st Year
Providing one number SEMI-SKILLED Manpower in one shift of 8 hour on all days including sundays & holidays for ONE MONTH for operation & maintenance of electrical installations at
1st Year
B-check servicing of 75/80 KVA DG set (Kirloskar make) at Site i/c supply & replacing of mobile oil (Koel Care Super Genuine ) for B-check servicing as per manufacturer's recommendation (servicing is to be carried out through authorised dealer only).
Annual comprehensive maintenance of 1600 KVA, 33 KV/0.433KV Out door type Sub staion with 33 KV CR panel, Oil filled CT & PT, Lightening Arrestors, Double brake without EB Isolators, Jumpering & Bus bar strainging by ACSR panther conductor, PG Clamps/T Clamps, Dry type maintenance free 110V DC 120 AH battery with battery charger, Earthings with earthing lead etc.
Annual comprehensive maintenance of 75/80KVA, 1500 RPM, 0.8 PF, 415 Volts Air Cooled silent DG Sets with control panel having Microprocessor based Genset monitoring & control system, MCCB etc including AMP Panel Electro-Mechanical Relay based with control & power contactors, timmers, visual & Alarm indication for faults, UPS, operating interface panel etc , LT cables with terminatios, Earthing and earthing lead etc
Annual comprehensive maintenance of LT Cubicle panel operating on 440 Volt, 50 Hz AC supply comprise with 2 Nos. incommer & 1 No Bus coupller drawout type ACBs, Outgoing MCCBs/MCBs, Common distribution panel and metering panels (Upto supply point) in each blocks LT Cable for interconnection with terminations, Earthing & earthing lead etc.
Annual comprehensive maintenance of Compound Lighting comprise with 7 Meter single/double arm Octagonal MS poles, Feeder Pillers, under ground XLPE cable, earthing and earthing lead etc
Annual comprehensive maintenance of 150 Watt HPSV Street light luminaire with copper bllast, electronic ignitor, capacitor, holder etc
M/S Jindal Electricals
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .