Loading…
New: tenders and results on WhatsApp
New: Find tenders, results and companies on WhatsApp, by text or voice note
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.4 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹9.4 L+₹4,367 (0.46%)Rejected-Finance 49 1 ISWAR GUPTA ROAD KOLKATA 700 028 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700028 | L2 | Rejected-Finance L2 | |
| 3 | L3₹9.5 L+₹9,782 (1.04%)Rejected-Finance 10 6 NABIN SENAPATI LANE HOWRAH 711 101 | HOWRAH | HOWRAH | WEST BENGAL | 711101 | L3 | Rejected-Finance L3 |
Tender Value
Refer Docs
EMD Value
₹19,000
Closing Date
20 Jan 2025, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
The Executive Engineer, Kolkata Electrical Div
The Executive Engineer Kolkata Electrical Division P.W.Dte. BlockI (1st Floor) Writers Buildings, Kolkata 700 001
Electrical Renovation work at Reserve Force of Kolkata Police at Standard Building 2nd Floor ---Supply and Fixing of Distribution Boards and allied Electrical Works etc.
2025_WBPWD_795970_1
WBPWD/EE-KED/eNIQ-51Q/24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
21 days
Writers Buildings
Please refer Tender documents.
5 documents required · 5 mandatory
₹19,000
O/O The Executive Engineer Kolkata Electrical Divi
21 May 2025
7 Jan 2025
22 Jan 2025
7 Jan 2025
20 Jan 2025
14 Jan 2025
13 Jan 2025
Amount
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Make- Legrand/Schneider/ABB) up to 160A
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Make- Legrand/Schneider/ABB)
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make- Legrand/Schneider/ABB)
ii) 2+10 way
S&F Wire way box suitable for 2+8-way SPN MCB DB
S&F Wire way box suitable for 2+10-way SPN MCB DB
Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works with bakelite / perspex top cover 300 mm x 200 mm x 65 mm
Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection (Make- Legrand/Schneider/ABB)
Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment(Make- Legrand/Schneider/ABB)
12/6 way VTPN
S&F IP-42/43 wire way box for 4 way TPN
S&F 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Make- Legrand/Schneider/ABB)
63 A TP MCB
6-32A SP MCB
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection(Make- Legrand/Schneider/ABB)
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20/25mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required
4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECCin 2x25 mmpvc rigid conduit
2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC
2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC
2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC
2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
Supply & Fixing 240 V,2nos 6 A, 5 pin Modular type plug socket (Brand approved by EIC) with 2 nos 6A Modular type switch, without plug top on 6 Module GI Modular type switch board with 6 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support With 25x25x3mm angle iron support
150x50x1.25mm (18SWG)
200x50x1.25mm (18SWG)
300x50x1.25mm (18SWG)
S & delivery of 240V,90W, minimum rpm 1325rpm, 3-blades, AC Full body metal wall bracket fan (motor housing canopy should be metalic and inbuild thermostate protection )450 mm or 18 inch on wall by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) on 150mmX300mm best quality vernished wood or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length Make orient, Model :- Tornado Wall - II/ crompton/EPC
Supply & Laying 1.1 KV Gr. XLPE/ PVC Armoured Al Cable with 2x10 SWG GI wire Conceal in wall / laying on Surface
4 core 16 sq. mm.
S & F compression type brass cable gland complete with brass gland, brassring & rubber ring for dust & moisture proof entryof XLPE/PVC armoured cable.
4 core 16 sq. mm.
Finishing the end of the XLPE/PVC armoured cableas by crimping method incl. S&F solderless socket (Dowels make), tapes, anticorrosive paste & joiting materials.
4 core 16 sq. mm.
Supply and fixing of 40A timer controlling starter 3 phase AC in SS double door 16 way SPNDB enclosure with IP-43 protection with front door locking arrangement with all connection and comprising with following accessories including necessary connections and earthing attachment on angel iron frame on wall/embedding in wall as per instruction of EIC. a) 40A FP RCBO,100mA-1 no.(Make-L&T cat no-(AUF3C2)-/equivalent of Legrand,Simens) b) 63A Three Pole Contactor-1 no.(Make-L&T,MCX type/equivalent of Simens) c) 32-40A Over load Relay-1 no.(Make-L&T,Mn2 type/equivalent of Simens) d) Daily & weekly programmable basis digital time switch,min switching time 1 min,25 ON/OFF programs,6 yrs.Battery backup,settable DST & key pad lock features-1no.(Cat no-67DDTO,-L & T-GIC make/equivalent Legrand make) e) Start/Stop push button-1+1 No.(L & T/Simens) f) RYB/Amber LED indication Lamp,240V AC-1+1 Nos.(L & T/Simens)
S & f syntex Waterproof box with IP 66 for installation o f Isolator for AC outdoor unit as per direction of EIC ibcl S & F 4P 63A Isolator(Make : Legrand/L&T) including necessary connection
S&F sweep A.C Exhaust fan incl. making hole on wall with nuts & bolts of required with S&F of louver shutter. (Make-EPC)
230mm Heavy Duty(metal body with Front guard)
12" Heavy Duty
Electromech Engineers Co-Operative Society Ltd. (BID ID -6010401)
SREEKRISHNA ENGINEERING ENTERPRISE (BID ID -6019519)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .