| 1 | L1₹71,170Accepted-AOC | ₹71,170 | L1 | Accepted-AOC L1 |
| 2 | L2₹76,780+₹5,610 (7.88%)Rejected-AOC | ₹76,780+₹5,610 (7.88%) | L2 | Rejected-AOC L2 |
| 3 | L3₹85,737+₹14,567 (20.5%)Rejected-AOC | ₹85,737+₹14,567 (20.5%) | L3 | Rejected-AOC L3 |
| 4 | L4₹1.0 L+₹32,140 (45.2%)Rejected-AOC | ₹1.0 L+₹32,140 (45.2%) | L4 | Rejected-AOC L4 |
Tender Value
₹1.4 L
EMD Value
₹2,717
Closing Date
28 Oct 2022, 9:30 amClosed
Executive Engineer
EE, EandM, Division, APWD, Prothrapur, Port Blair
Repair and Renovation of Anganwadi Building at Alipur Mathura NGO SW Providing IEI
2022_APWD_7656_1
DB-WO/EandM/DIV/PP/22-23/2056
Open Tender
Electrical Works
Item Rate
30 days
South Andaman
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
₹2,717
10 Nov 2022
17 Oct 2022
28 Oct 2022
17 Oct 2022
28 Oct 2022
21 Oct 2022
18 Oct 2022 - 20 Oct 2022
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. a) Group C
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
b) 4 X 6 sq. mm + 2 X 6 sq. mm earth wire
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required a) 5/6 A switch
b) 3 pin 5/6 A socket outlet
c) 15/16 A switch
d) 6 pin 15/16 A socket outlet
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. a) 6 Module
b) 3 Module
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator a) 12 way , Double Door
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required a) Single Pole
Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required a) 40 A
Supplying and fixing of surface mounted LED Batten Fitting for 20 Watt T-8 Lamp similar to Crompton Cat No. DMLN1LT8 - 16 with 20W retro fit LED Lamp Crompton Cat No. LT8-20-865-2 or its equivalent etc., as required.
Supplying and fixing Bakelite batten/ angel holder including connection etc., as required
Supplying of 12Watt LED Lamp in the existing Batten Holder Similar to C&S Cat No. LTHPLED LAMP12W/ B22 or its equivalent etc as required
Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
Supplying of A.C Ceiling fan (1200 mm) sweep without regulator with all accessories etc as required. Similar to make Bajaj Code No. 250467 Kassels 50 ISI Marked (White BR) or its equivalent
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Providing earthing with safe earthing electrode of galvanization 80 to 100 microns, length 2 mtr, outer dia 50 mm, inner dia 19 mm and inner space be filled with crystalline conductive mixture including filling -up with electrolite (Back fill compound) as required for safe earth electrode and providing masonary enclosure with cover plate having locking arrangement etc. as required. (Ashlok)
Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15 mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required.
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
Providing and fixing hot press moulded sintex single phase SMC meter box Hinged (L) of 250 x 250 x 155 mm (inside) for accommodating and LT 3 Phase KWh meter with cut out similar Cat No. GSJB 2525 or its equivalent etc., as required.
M/s G K Construction
M K ENGINEERING
JOY GURU ENTERPRISES
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .