Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.5 LAccepted-AOC 1 6 MOITRI SARANI RABINDRA NAGAR KOLKATA 700 065 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700065 | L1 | Accepted-AOC AOC Issued | |
| 2 | L2₹16.9 L+₹1.3 L (8.59%)Rejected-Finance 46 S P MUKHERJEE ROAD KOLKATA 700026 | KOLKATA | KOLKATA | WEST BENGAL | 700026 | L2 | Rejected-Finance that the bid is not L1 | |
| 3 | L3₹18.5 L+₹3.0 L (19.1%)Rejected-Finance 24C GOABAGAN LANE KOLKATA 700 006 | KOLKATA | KOLKATA | WEST BENGAL | 700006 | L3 | Rejected-Finance that the bid is not L1 | |
| 4 | L4₹18.7 L+₹3.2 L (20.8%)Rejected-Finance 49 1 ISWAR GUPTA ROAD KOLKATA 700 028 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700028 | L4 | Rejected-Finance that the bid is not L1 | |
| 5 | L5₹17.9 L+₹2.4 L (15.3%)Rejected-Finance 3 C DR JAGABANDHU LANE KOLKATA 700012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L5 | Rejected-Finance that the bid is not L1 |
Tender Value
Refer Docs
EMD Value
₹19,000
Closing Date
29 Feb 2020, 11:30 amClosed
EE NKHED PW Dte
KIT Building Annex, 4th Floor,P-16, India Exch. Place Extn., Kolkata -700073
Renovation of existing sub station at B C Roy PGIPS Phool Bagan Kolkata SITC of LT PANEL
2020_WBPWD_272311_1
WBPWD/EE/NKHED/NIQ-80/19-20
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Kolkata
Please refer Tender documents.
5 documents required · 5 mandatory
₹19,000
19 Mar 2020
14 Feb 2020
2 Mar 2020
16 Feb 2020
29 Feb 2020
16 Feb 2020
Amount
SITC of floor mounting cubicle type indoor compartmentalized 415 Volt. 50 Hz. dust & moisture proof L.T. distribution panel (CPRI tested) board fabricated from 16 SWG CRCA sheet. The panel should have adequate strength and space to accommodate the incoming & outgoing switches and bus bars with all inter connections in between the switches & bus bars with solid copper rod / flexible wire of suitable capacity. The panel should be provided with cable alley for facilitating connection of all the incoming & outgoing XLPE cables with termination arrangements by supply & fixing copper terminal bar / bolt of required sizes.
The 2 nos. G.I earth bus bar should run along the full length of the panel board. The incoming terminals of ACB & MCCB as well as out going terminals of MCCB should be provided with Extra copper bar of suitable capacity for smooth termination of double feeders. All incoming / outgoing ACB / MCCB / SFU units should have identification as directed by the E.I.C. The panel board should be painted by powder coated paint & the layout diagram of the panel board should be approved by the E.I.C before manufacturing. The panel board should comprise with the followings :
Incoming :- a) S/F of 415 Volts 1600 A Breaking capacity 50KA 4 pole EDO type with Microprocessor Based LSIG release ACB but with castle locking arrangement, as incomer for 2 nos. 2000KVA Transformer, including electrical connection with both the bus-bars. (Make – L & T cat no U power MTX4.5/Siemens 3WL 45B/ABB cat no EMAX PR122 /Schnider cat no MVS mic 6.0A) - 2 nos. b) S/F of 415 Volts 1600 A Breaking capacity 50KA 4 pole EDO type with Microprocessor Based LSIG release ACB but with castle locking arrangement, as Bus Coupler, including electrical connection with both the bus-bars. (Make – L & T cat no U power MTX4.5/Siemens 3WL 45B/ABB cat no EMAX PR122 /Schnider cat no MVS mic 6.0A) - 1 No.
Bus bar chamber :- do-do 2000 A capacity 4 bar electrolytic tinned copper bus bar mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification and segregated in two (2) equal length by keeping space for suitable accommodation of bus-coupler in the center of BBC. - 1 set
Buscoupler:- S/F of 415 Volts 1600 A Breaking capacity 50KA 4 pole EDO type with Microprocessor Based LSIG release ACB for two Nos. Rising Main (Make – L & T cat no U power MTX4.5/Siemens 3WL 45B/ABB cat no EMAX PR122 /Schnider cat no MVS mic 6.0A)- 1 no with mechanical castle key
Out-Going :- a) S/F of 415 Volts 1600 A Breaking capacity 50KA 4 pole EDO type with Microprocessor Based LSIG release ACB for two Nos. Rising Main (Make -L&T/Siemens/ABB /Schnider) (Department Supply) on cubical panel- 1 no b) S & Fixing only 415V, 400A TPN, SFU with HRC fuses on (Make – Siemens/Schneider/L&T) on cubical panel - 1 nos c)Supply and Fixing 415V, 315A TPN, SFU with 3nos. HRC fuses on 315A fuses. (Make – Siemens/Schneider) - 2 nos. d) Supply and Fixing 415V, 200 TPN, SFU with 3nos. HRC fuses on 200A fuses. (Make – Siemens/Schneider/L&T) - 3 nos e) Supply and Fixing 415V, 160 TPN, SFU with 3nos. HRC fuses on 200A fuses. (Make –Siemens/Schneider/L&T ) - 2 nos
f) Supply and Fixing 415V, 100A TPN, SFU with 3nos. HRC fuses on 100A fuses. (Make – Siemens/Schneider/L&T) - 2 nos g) Supply and Fixing 415V, 63A TPN, SFU with 3nos. HRC fuses on 100A fuses. (Make – Siemens/Schneider/L&T) - 2 nos h) Supply and Fixing 415V, 32A TPN, SFU with 3nos. HRC fuses on 100A fuses. (Make – Siemens/Schneider/L&T) - 1 no
Metering :- a) Digital Multifunction meter 1no. Make Conserve Cat no. EM6400NG c) 3000/5 Amp ratio C.T (Kappa) - 6 nos. d) 250 Volts L.E.D (RYB) source indicating lamps with sliding fuses and switches. - 6 sets e) E.I danger board . - 2 nos
Special Terms & Conditions :- i) The Agency must procure the materials from the Manufacturer / OEM or from their authorized. Sales channel so that the standard warranty / Support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. ii) Documents that authenticates such procurement form the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM /authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work/submission of bill. iii) If any refurbished material is supplied and installed, panel action will be taken as per existing rules. iv) After completation of work Agency Supervisor has to certify fittness af all Electrical Installations done under this Tender. This is mandatory before peparations of Final Bill. v) Defect libilities period for 01(one) year from the date of completation of work.
(Rate should be quotated including all taxes and duties)
C. CHOWDHURY AND CO
S. A. ENTERPRISE
ALPHA ELECTRICALS
Electromech Engineers Co-Operative Society Ltd.
T.D.K. ENTERPRISE
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .