Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.7 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹27.3 L+₹29,625 (1.10%)Rejected-AOC 37 222 BUNDU KATRA AGRA UP | AGRA | UP | L2 | Rejected-AOC L2 | |
| 3 | L3₹29.4 L+₹2.4 L (8.84%)Rejected-AOC | L3 | Rejected-AOC L3 | |
| 4 | L4₹36.5 L+₹9.5 L (35.2%)Rejected-AOC NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | L4 | Rejected-AOC L4 | |
| 5 | L5₹36.5 L+₹9.5 L (35.3%)Rejected-AOC | L5 | Rejected-AOC L5 |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
8 Jul 2023, 6:00 pmClosed
GE Bharatpur
Kanjoli line Bharatpur
Repair to LT cables Lt OH lines, LT panels and connected work at sewar fort and parade ground under GE Bharatpur
2023_MES_600908_1
8251/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Bharatpur
As per NIT
6 documents required · 6 mandatory
₹500
GE Bharatpur
₹70,000
Yes
24 Jul 2023
3 Jun 2023
10 Jul 2023
3 Jun 2023
8 Jul 2023
26 Jun 2023
5 Jun 2023 - 18 Jun 2023
Amount
M & L for 01 coats of painting with approved colour of synthetic enamelled paint over a coat of red oxide primer for size of Panel boxes from all in & out side incl angle iron frame work min 04 Sqm area of sheets including angles canopy and legs etc including complete removal of paint from existing panel box surface complete all as specified and directed. Note: Permission to shutdown of electric supply to the panel to be taken from MES before commencement of work.
M&L for LT cable fault rectification upto 240 sqmm X 3.5/4 core by using Fault locator machine to detect fault and rectify the same incl T&P & items ie lugs,tape etc complete all as specified and directed by Engr-in-charge.
M&L for cable jointing kit for 1.1 KV grade for straight through joint complete with jointing material and accessaries suitable for 3.5/4 core XLPE armourd aluminium conductor cable of following size after detaction of fault location complete all as specified and directed. Note: Earth work and returning filling which is require in the item will be measured and paid seperataly.
25 Sqmm to 50 Sqmm
70 Sqmm to 120 Sqmm
150 Sqmm to 240 Sqmm
Excavation in trenches, n. exc 1.5 Mtr wide and n. exc 1.5 Mtr in depth for foundation/laying of cable and getting out in soft/loose soil complete all as specified and directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers n. Exc 25 cm thick complete all as specified and directed.
Removing of excavated soil to a distance n. Exc 50 Mtr and depositing where directed at a level n. Exc 1.5 Mtr above the starting point complete all as specified and directed.
Supply & spread unwashed dry river sand for sand cushioning for covering the under ground cable in trenches (08 CM thick layer of sand before laying of cable and 15cm thick layer of sand after laying of cables and punned after laying) complete all as specified and directed. (Note :- Punning thickness shall be measured.)
M&L for cable protection cover with sub Class`B` bricks old size laid dry, flat perpendicular across the cable in trenches complete all as specified and directed.
Boring of holes under road, pavement, hard standing by trenchless technology using suitable tools and machinery for laying of pipe upto 150mm bore complete all as specified and as directed . Note :- GI pipe shall be measured and paid in respective item of BOQ.
S & F or laying galvanised steel tubing of size 50mm bore light grade (ISI marked) for protection of under ground cable on poles/walls under road crossing complete all as specified and directed.
S & F or laying galvanixed steel tubing of size 100mm bore light grade (ISI marked) for protection of under ground cable on poles/walls under road crossing complete all as specified and directed.
Taking out Unsv U/G cable PVC insulated armoured PVC sheathed Al. Conductor, LT cable of any size complete all as specified and directed.
Supply, laying, testing & commissioning LT XLPE insulated armoured (heavy duty) electric cable with stranded aluminium conductor 1100 volts grade (ISI marked) & laid in trenches/pipes or fixed on pole of the following sizes:-
185 Sqmm 3.5 core
120 Sqmm 3.5 core
95 Sqmm 3.5 core
70 Sqmm 3.5 core
50 Sqmm 3.5 core
25 Sqmm 4 core
16 Sqmm 4 core
10 Sqmm 2 core
Supply, laying, testing & commissioning LT XLPE insulated armoured (heavy duty) electric cable of single core 95 Sqmm with stranded copper conductor 1100 volts grade (ISI marked) & laid in trenches/pipes or fixed on pole complete all as specified and directed.
S&F in repair of MCCBs thermal magnetic, adjustable type of following capacity on existing location:-
MCCB 415 volts 400 Amps 04 pole 50KA
MCCB 415 volts 250 Amps 04 pole 36 KA
MCCB 415 volts 200 Amps 04 pole 36 KA
MCCB 415 volts 160 Amps 04 pole 36 KA
MCCB 415 volts 100 Amps 04 pole 25 KA
MCCB 415 volts 63 Amps 04 pole 25 KA
M& L for Earthing complete with galvanised mild steel plate electrode 600x600x6 mm thick buried directly in ground vertically (earth pit not less than 2.25 m deep below normal ground level) with the top edge of the earth plate electrode at a depth not less than 1.5m below normal ground level and including GI earth strip 32x6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate electrode at one end connected to metallic bodies of HT/LT equipment etc at the other and earth strip encased in and including 40mm bore GI light grade pipe with all fittings from top of earth plate electrode to body of equipment fixed with and including 25x6 mm flat iron clamps bolts, nuts and washers and including providing watering pipe 20mm bore GI Pipe electrode complete all as specified and shown in elctrical plate No 3 of MES SSR Part-I. the scope of work includes necessary excavation and earth work in any type of soil. removal of soil upto 50 metre PCC pit with precast RCC cover, charcoal/salt funnel, CI frame etc complete all as specified & directed.
NOTE: (i) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.50 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover. Reinforcement in cover shall be of 8mm dia TMT bars @ 150mm c/c both ways. (ii) Item includes the cost of 7.5 metre GI pipe for protection of earth strip. Any variation in length shall be adjusted through deviation order (iii) Item includes cost of 7.5 metre earth lead strip .Any variation in length shall be adjusted through deviation order. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thinkness of 15 cm on all sides.
M&L for electrical rubber chequred mat, size 2 m x 1 m x 19 mm complete all as specified and directed.
Supply and fixing in replacement of Lithium base Energy efficient integrated Solar street light of 36 watt in single FRP body duly polyurethane coating (Camouflage color), encases with monocrystalline solar PV panel of 65-67Wp,lithium battery 11.1/12.8V,33.0 AH with inbuilt BMS,IP 65, High brightness W-LED(160-180lm/watt) lamp with Aluminium reflector for better light distribution ,CRI>70, color temp 5700K-6500K Microcontroller based charge controller cum driver,automaticdimming function(First 04 hrs at full brightness & rest of the time at lower light level with PIR motion sensor), Dusk to dawn operation,suitable to working temp (-) 10C to (+) 55C ,weight not more thatn 16-18 Kg with adjustable MS clamp suitable for pole/wall mounting etc complete all as specified and directed. Make: AXXON/HAVELLS/PHILLIPS/CG Protections: Short circuit, overload,Reserve polarity and battery protection.Firm should provide vital parametres Test report from NABL accredited lab and should be of made in India with CE & ROHS complaint. (Excavation & earth work shall be measured separately)
M & L for servicing of existing APFC Panel of cap upto 200 KVAR including carrying out minor maintenance/repairs as required to make functional the systems incl providing 03 Nos CT's of suitable rating in existing LT panel alongwith 6 sqmm copper wire to get result of current in existing panel etc complete all as specified and directed.
Supply, installing, testing and commissioning, factory made and tested, automatic power factor control panel (APFC Panel) cap-40KVAR out door type, cubical front opening type, The panel shall be of protection class IP-54 and made out of 3.15 mm CRCA MS sheet ineer & outer (both) and MS angle 40x40x6 mm thick frame, power coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of synthetic enamel paint over one coat of red oxide primer,copper bus bar 4P 200Amp rating including internal wiring from bus bar to capacitor shall be carried out by 16 sqmm FRLSH copper conductor wire and 2.5 sqmm for other items ie fan,indicator etc.
Outgoing: (a) MCCB TP 63A 25KA ,415V rating - 01Nos. (b) MCCB TP 40A 10KA ,415V rating - 03No. (c) MCCB TP 16A 25KA ,415V rating - 04No. (d) Cap duty contactor for 20KVAR -01Ns. (e) Cap duty contactor for 10KVAR -03No. (f) Cap duty contactor for 5KVAR -01No. (g) Cap duty contactor for 2KVAR -02No. (h) Cap duty contactor for 1KVAR -01No. (j) Capacitors type MPP-H as per IS 13585/hot I/1994/IS 13340/1993, for 60 (20x1+10x3+5x1+2x2+1x1) KVAR. (k) Star/Stop push button-08Nos.(l) ON indication Lamp-08Nos. Note: (i) Drawings of LT panel shall be got approved by GE before Manufacture. (ii) Panel stand shall be made out of 50X50X5mm ISA angle of 60cm height and appropriate size as per panel. The same should be fixed in PCC 1:2:4 below ground level embedded in block of size 30X30X45cm.
S&F in repair Capacitors duty contacor as per existing make and type of following capacity
S & F in repair power factor APFC relay 8 stge 415VAC,3CT confirming to IS 13340 complete all as specified and directed by Engr-in-charge.
M&L for cement concrete 1:4:8 type D2 (using 40 mm graded crushed stone aggregate) as in foudation, filling and mass concrete including demolition existing old PCC complete all as specified and directed
M&L for cement concrete (1:2:4) type B-1 using 20mm graded crushed stone aggregate for pedestal of poles/ coping including necessary formwork, fair finishing to exposed surfaces using extra cement including demolition existing old PCC complete all as specified and directed.
M&L for disconnection of LT panel incl LT cables of size upto 240Sqmm X 3.5/4core from existing foundation and reconnection with same panel after taking necessary corrective action to lift the panel height incl excavation and taking down existing cable with loop, providing new AL lugs and cable gland of appropriate size,insulation tape etc to restore electric supply incl necessary iron work to modify height of existing LT panel upto 1.2 Mtrs above existing level incl necessary welding work,nuts & bolts and 2 coat of paint with existing color over one coat of primer and required necessary PCC work complete all as specified and directed by Engr-in-charge. Note: PCC shall be measured & paid separately under respective item.
Supply, fabricate and Install as in replacement of double sided glow sign board of size 1.5 mtr x 1.2 mtr x 40 cm, made out of 25 mm bore MS pipe 'H' frame, covered with PGI sheet 24SWG gauge on all sides except front side, front side with flex sheet duly digital print embossing as directed by Engineer-in charge showing location /details of power house /tech area as directed and writing of letters (Block, Roman, Italic), in two or three rows, the same letters should be printed on both sides of the sign board, fixed with aluminium equal angle 25 x 25 x 3 mm thick fixed with screws and providing inside LED tube light fittings 1 x 9 Watt - 4 Nos for glowing the sign board at night with necessary internal electrical connections fixed on wall/pole and the sign board shall be fixed with MS channel 40 x 40 x 4 mm thick by means of nuts, bolts and grouted in ground up to 1.5 Mtr above GL and 0.45 belew GL with 50 mm dia GI pipe stand embedded in PCC bed block of size 300x300x450mm with PCC 1:3:6 type C1 using 20 mm graded stone aggregate and the MS frames/pipes shall be given two coats of synthetic enemal paint over a coat of red oxide primer complete all as specified and directed
S&F in replacement new generation energy saving and environmental friendly long life varsatile pressure die cast aluminium IP66 road way light fitting with high power LED as light source of capacity 60 watts (Surge protection of the light should be 10 KV )with suitable drivers etc and connecting with 4.0 sqmm aluminium solid conductor PVC insulated twin core weather proof cable etc, fixing to wall / pole with and including bracket made out of GI pipe of 40mm dia light grade not less than 1.5 mtr long, bent to shape, fixed to Pole/Wall in any position with flat iron clamps of size 30 x 4mm complete all as specified and directed. Make:- Crompton / Philips/Bajaj/Havells.
S & F in replacement low intensity twin type LED Aviation obstruction light fixed on OHT of cast aluminium ,Red in lighting color ,50 Hz, 230V AC operation range, IP 65 standard,power consumption 18 watt min Lux level 32 Lux at 1 Mtr required incl fastners/nut,bolts/clamp for fixing complete all as specified and directed by Engr-in-charge. Make: CG/Bajaj/Phillips
PD GUPTA AND COMPANY
KISHORE ENTERPRISES
Vijay Electricals
krishna Associate
SHREE RAM BUILD TECH
M/S MAMTA CONSTRUCTIONS
Rahul Enterprises
imran construction company
Ayushmat Contractors
NAVEEN TRADERS
M/s M M BAHL
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .