| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.9 LAccepted-AOC NAGPADA MUMBAI 10TH LANE KAMATHIPURA S P ROAD TELANG BLDG NO 23 ROOM NO 5 10TH LANE MUMBAI 400008 | MUMBAI | MUMBAI | MAHARASHTRA | 400008 | L1 | Accepted-AOC L1 | |
| 2 | L2₹41.9 L+₹10.6 L (34.0%)Rejected-Finance E 84 OF HQ CWE NW MUMBAI AGE 87 1 3 GEETA NAGAR NAVY NAGAR COLABA MUMBAI 400 005 | MUMBAI | MAHARASHTRA | 400005 | L2 | Rejected-Finance Not Reasonable | |
| 3 | L3₹44.9 L+₹13.6 L (43.5%)Rejected-Finance | L3 | Rejected-Finance Not Reasonable | |
| 4 | L4₹48.8 L+₹17.6 L (56.2%)Rejected-Finance | L4 | Rejected-Finance Not Reasonable |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
28 Jul 2022, 6:00 pmClosed
Saurabh Gupta, EE
GE (W) Colaba, Mumbai
REPAIR / MAINTENANCE OF UNSERVICABLE LT PANEL / FEEDER PILLAR BOXES INCLUDING CONNECTED ITEMS INSTALLED AT ARMY AREA UNDER GE (WEST) COLABA, MUMBAI.
2022_MES_531470_1
8654/E8
Open Tender
Civil Works
Item Rate
180 days
GE (W) Colaba
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (W) Colaba, Mumbai
₹80,000
Yes
18 Aug 2022
16 Jun 2022
30 Jul 2022
16 Jun 2022
28 Jul 2022
30 Jun 2022
Amount
Excavating in trenches, not exc1.5 m wide and not exc 1.5 m in depth for foundation, and not exc 10 sq m on plan and getting out in soft loose soil all as specified and directed.
All as per sl. item No.01 above but in hard/dense soil.
Excavation in trenches not exc. 1.5 m wide and not exc. 1.5 in depth for foundation and getting out in hard rock/road cutting/RCC/PCC all as specified and directed.
Supply and providing sand for sand cushioning for cable protection or filling in trenches of sand in cable ducts after cleaning of ducts all as specified and directed. Note:. for the purpose of payment only punned thickness will be measured.
Returning, filling in soil including spreading, levelling, watering ,well ramming in layers not exc 25 cm all as specified and directed.
Removing of excavated material not exc. 50m away from starting point and depositing where directed at a level not exc. 1.5m above the starting point in soil all as specified and directed.
Removing of excavated material from the site of work and transporting out of MD land to a distance upto 5.00 kM away from the site all as specified and directed.
Supply and providing unreinforced pre cast cement concrete cable cover for cable protection (Ready made Covers) of sizes Class LV type I, flat size 250x150x40 mm putting adjecent to each other all as specified and directed.
Supply and laying High density poly-ethylene pipes (HDPE) of pressure 6 kgf/cm2 pipe, 90mm dia for laying of cable protection complete to walls/ trenches/floor/ceilings all as specified and directed by Engineer-in-Charge.
Supply and laying tubes light grade, galvanized, 100 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable all as specified and directed.
Supply and laying tubes light grade, galvanized, 80 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable all as specified and directed.
Supply and laying tubes light grade, galvanized, 50 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable all as specified and directed.
M&L PCC 1:2:4 type B1 using 20mm graded crushed stone aggregate in width for foundatuion/road filling including including rafts, footings, foundation beams plinth beams; bases for columns, etc.; basement slabs, under-reamed piles and mass concrete all as specified and directed.
Taking down old cable and rerouting , relaying the same after checking , meggaring complete LT underground cables, 1100 Volts grade, XLPE insulated, PVC sheathed heavy duty of size 10 sqmm X 2 Core to 50 sqmm X 3.5 Core including connecting up electric power to panel/feeder box all as specified and directed.
Supplying, laying, commissioning & testing LT underground cables 240 Sqmm X 3.5 Core, 1100 Volts grade, XLPE insulated, PVC sheathed heavy duty, armoured with multi-stranded aluminium conductor all as per IS 7098 (Part -1) laid in trenches, ducts, drawn through pipes or fixed on poles, as and when required on ground all as specified and directed.
All as per item No 15 here in before but of size 185 Sqmm X 3.5 Core
All as per item No 15 here in before but of size 120 Sqmm X 3.5 Core
All as per item No 15 here in before but of size 95 Sqmm X 3.5 Core
All as per item No 15 here in before but of size 70 Sqmm X 3.5 Core
All as per item No 15 here in before but of size 50 Sqmm X 3.5 Core
All as per item No 15 here in before but of size 35 Sqmm X 3.5 Core
Material & Labour for cable fault detection at various locations by all T & P , Equipments for HT/LT CABLE XLPE aluminium conductor including testing and commissioning all as specified and directed
Material & Labour for cable jointing kit, in repairs for LT CABLE XLPE aluminium conductor including testing and commissioning complete for the size of 50sqmm X 3.5 Core all as specified and directed
All as per item No 24 here in before but of size 70sqmm X 3.5 Core all as specified and directed
All as per item No 24 here in before but of size 95sqmm X 3.5 Core all as specified and directed
All as per item No 24 here in before but of size 120sqmm X 3.5 Core all as specified and directed
All as per item No 24 here in before but of size 240sqmm X 3.5 Core all as specified and directed
Taking down for old cable and rerouting, relaying the same after checking, meggaring complete LT underground cables, 1100 Volts grade, XLPE insulated, PVC sheathed heavy duty of size 10 sqmm X 2 Core to 50sqmm X 3.5 Core including connecting up electric power to panel/feeder box all as specified and directed.
Taking down for old cable and rerouting, relaying the same after checking ,meggaring complete LT underground cables, 1100 Volts grade, XLPE insulated, PVC sheathed heavy duty of size 70 sqmm X 3.5 Core to 240 sqmm X 3.5 Core including connecting up electric power to panel/feeder box all as specified and directed.
Dismantling of damaged/burnt MCCB and supply & fixing of MCCB, 4Pole, 320 Amps, 35/36kA, 415 Volts, 50Hz AC s with enclosure of 2.00 mm thick for indoor S/S fixing on wall all as specified and directed by Engr-in-charge. MAKE: As per previous.
Dismantling of damaged/burnt MCCB and supply & fixing of MCCB, 4Pole, 320 Amps, 35/36kA, 415 Volts, 50Hz ACs all as specified and directed by Engr-in-charge. MAKE: As per previous.
Dismantling of damaged/burnt MCCB and supply & fixing of MCCB, 3Pole, 200 Amps, 35/36kA, 415 Volts, 50Hz ACs all as specified and directed by Engr-in-charge. MAKE: As per previous.
Dismantling of damaged/burnt MCCB and supply & fixing of MCCB, 3Pole, 160 Amps, 36kA, 415 Volts, 50Hz ACs all as specified and directed by Engr-in-charge. MAKE: As per previous.
Dismantling of damaged/burnt MCCB and supply & fixing of MCCB, 3Pole, 100 Amps, 10kA, 415Volts, 50Hz ACs all as specified and directed by Engr-in-charge. MAKE: As per previous.
Dismantling of damaged/burnt change over switch and supply & fixing of Change Over switch, 4 Pole, 250 Amps, Open execution, ON LOAD type 415 Volts, 50Hz ACs all as specified aod directed by Engr-in-charge.
M&L for dismantling of damaged APFC panel power contactor and supply and fixing in repair power contactor 3 pole 32 Amp to 55 Amp (MNX 32) 240 volts suitable for 5 KVAR capacitor to 20 KVAR capacitor to automatically correct the power factor for indoor type transformer all as specified and directed by Engineer -in -Charge. Make:- L&T Cat No. CS94111 or equivalent.
M&L for dismantling of damaged TP from APFC panel and supply and fixing in repair TP 40 amp MCB 440 Volts suitable for 5 KVAR capacitor to 20 KVAR Capacitor to automatically correct the power factor for indoor type transformer all as specified and directed by Engineer -in -Charge. Make:- L&T , Leegrand or equivalent.
M&L for dismantling of damaged relay of any stage from APFC panel and supply and fixing in repair APFC relay of 8 to 12 stage as per requirement 1A or 5A for load with class 2 accuracy 440 volts suitable for 5 KVAR capacitor to 20 KVAR capacitor to automatically correct the power factor for indoor type transformer all as specified and directed by Engineer -in -Charge. Make:- L&T , Leegrand or equivalent.
M&L for dismantling of damaged APFC panel capacitor and supply and fixing in repair heavy duty square type 5KVAR capacitor 440 volts, 6.56 Amp Ir, 3 × 27.4 µF capacitor suitable 100 to 300 KVAR APFC panel to automatically correct the power factor for indoor type transformer all as specified and directed by Engineer -in -Charge. Make:- Epcos, or Havells or Equivalent
M&L for dismantling of damaged APFC panel capacitor and supply and fixing in repair heavy duty square type 10 KVAR capacitor 440 Volts, 13.12 Amp Ir, 3 × 54.8 µF capacitor suitable 100 to 300 KVAR APFC panel to automatically correct the power factor for indoor type transformer all as specified and directed by Engineer -in -Charge. Make:- Epcos, or Havells or Equivalent
Supply & fix in repair , install, testing and commissioning of LT Panel outdoor meter cabin panel mounted on angle iron frame 40x40x5 mm grouted on floor, cubical indoor type for 415V, 3 phase, made of 3.15 mm thick CRCA sheet weather, vermin proof factroy fabricated, CPRI approved, front open hinged door with locking arrangement powder coated, individual compartment for MCCBs and 200 Amps rated bus bar, top and bottom cable entry including disconnecting cable connections and electronic meters from old meter cabin panel and fixing/connecting in new insalled panel with provisions of thimble/lugs and necessary farmwork and PCC foundation including shifting of existing panel if any making arrengement for fixing of panel and making good to disturbed surface as directed comprising of the following :- Location:- P-96 (a) MCCB, FP, 63-80 Amps 25 kA- 02 Nos. Make-Legrand / Schneider / L&T (b) MCB 40 Amps, 10KA, C series - 13 No . Make-Legrand / Schneider / L&T (c) Sheet metal enclosure 2 way without bus bar - 11 No, Make-Legrand / Schneider / L&T (d ) Copper Bus bar, 200 Amps Rated - R,Y,B & N (e)Digital Ammeter-01 No, Make-HPL ,SP CL-1.0/AE (f)Digital Voltmeter-01 No Make-HPL ,SP CL-1.0/AE (g) Making provision for fixing of digital electronic meters removed from old panel including fixing and providing vision glasses - 13 Nos. (h) Phase indicator lamp R,Y & B (j) Material and labour for 2 core 16 Sqmm multistranded copper conductor cable 1100V form bus bar to electronic energy meters using suitable size copper thimbles/glads. (k) Fixing of submain cable 2 core 16 Sqmm copper conductor with outgoing of energy meter all as directed.
Supply & fix in repair , install, testing and commissioning of LT Panel outdoor meter cabin panel mounted on angle iron frame 40x40x5 mm grouted on floor, cubical indoor type for 415V, 3 phase, made of 3.15 mm thick CRCA sheet weather, vermin proof factroy fabricated, CPRI approved, front open hinged door with locking arrangement powder coated, individual compartment for MCCBs and 250 Amps rated bus bar, top and bottom cable entry including disconnecting cable connections and electronic meters from old meter cabin panel and fixing/connecting in new installed panel with provisions of thimble/lugs and necessary farmwork and PCC foundation including shifting of existing panel if any making arrengement for fixing of panel and making good to disturbed surface as directed comprising of the following :- Location:- P-92, P-93 (a) MCCB, FP, 125 Amps 25 kA- 01 Nos. Make-Legrand / Schneider / L&T (a) MCCB, FP, 63-80 Amps 25 kA- 01 Nos.(I/O) Make-Legrand / Schneider / L&T (b) MCB 40 Amps, 10KA, C series - 25 No . Make-Legrand / Schneider / L&T (c) Sheet metal enclosure 2 way without bus bar - 11 No, Make-Legrand / Schneider / L&T (d ) Copper Bus bar, 250 Amps Rated - R,Y,B & N (e) Digital Ammeter-01 No, Make-HPL ,SP CL-1.0/AE (f) Digital Voltmeter-01 No Make-HPL ,SP CL-1.0/AE (g) Phase indicator lamp R,Y & B (h) Making provision for fixing of digital electronic meters removed from old panel including fixing and providing vision glasses - 25 Nos. (j) Material and labour for 2 core 16 Sqmm multistranded copper conductor cable 1100V form bus bar to electronic energy meters using suitable size copper thimbles/glads. (k) Fixing of submain cable 2 core 16 Sqmm copper conductor with outgoing of energy meter all as directed.
M & L for Earthing complete with GI earth plate electrode 60 cm X 60 cm X 6 mm thick, burried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.50 mtr deep below normal ground level connected to GI earth lead strip 25 x 4 mm dia by means of GI bolts, nuts, check nuts, washers made out of GI/steel, all as shown on electrical plate No 3 of MES Schedule part-I, earth lead strip connected to indicated position including concrete pit in PCC (1:3:6), type C1, Precast RCC cover slab 55 cm x 55 cm x 5 cm with reinforcement of 8 mm dia bar @ 100 mm c/c bothways including one handle made of 12 mm dia MS bar embedded in pre cast slab and 20 mm bore galvanised iron pipe "medium grade" for watering and 50 mm GI protection pipe with GI funnel and wire mess including charcoal and salt in alternate layers of 15 cm including necessary excavation and earth work in any type of soil all as specified and as directed and testing on completion.
Supply & Fix earth continuty conductor fixed to wall/surface or recess or burried in ground or any situation for loop earthing by 25 X 4 mm GI strip all as specified and directed by Engineer-in-Charge.
shree arihant constrution
E M CONSTROL SYSTEM
NOEL ENGINEERS
Bidder Name
NOEL ENGINEERS
shree arihant constrution
E M CONSTROL SYSTEM
SHREE SHIV ELECTRICAL
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .