Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹5.5 LAccepted-AOC | L-1 | Accepted-AOC L- 1 | |
| 2 | L-2₹5.5 L+₹5,605 (1.03%)Rejected-Finance | L-2 | Rejected-Finance L-2 | |
| 3 | L-3₹6.2 L+₹75,505 (13.8%)Rejected-Finance C O BABA GULKARI FLAT NO C 57 SHANKARRAO PADHYE APARTMENT WARDHA ROAD SAVITRI VIHAR SOMALWADA NAGPUR 440025 MH | NAGPUR | MAHARASHTRA | 440025 | L-3 | Rejected-Finance L-3 |
Tender Value
Refer Docs
EMD Value
₹12,380
Closing Date
1 Feb 2021, 6:00 pmClosed
Dadan Singh, AGM (E-E)-II
O/o of Airports Authority of India, Raja Bhoj Airport, Bhopal - 462036
Installation of weather observation system (AWOS) / RVR equipment at Bhopal Airport. SH Electrical Works
2020_AAI_65104_1
AAI/BPL/ENGG(E)/NIT-07/2020-21
Open Tender
Miscellaneous Works
Works
90 days
Raja Bhoj Airport
Please refer Tender documents.
18 documents required · 18 mandatory
₹1,120
₹12,380
16 Dec 2021
6 Jan 2021
3 Feb 2021
6 Jan 2021
1 Feb 2021
6 Jan 2021
6 Jan 2021 - 15 Jan 2021
Amount
Supply, installation, testing and commissioning of dust, damp and vermin proof cubicle free floor, double door outdoor type factory built sheet steel enclosed modular bolted construction, with IP-66 protection, suitable for operation on 415 ±10% volts, 50 Hz AC 3 phase 4 wire supply system fabricated out of CRCA sheet steel of 2.0 mm thick for frame work and 2.0 mm thick for doors/ covers, 3mm thick for gland plates i/c a seperate compartment to occupy one number 2 KVA, single phase UPS with battery (for 15 min backup), cleaning & finishing complete with cable gland plates, danger notice plates, etc. as required with following accessories & suitable size of aluminium bus bar. INCOMER i) 32Amps. 4P , MCCB '18ka, (Ics = Icu= 18 Ka) with thermal magnetic release having O/L & S/C protection -1 No OUTGOING i) 32 Amps C- curve DP MCB-2 No. ii)5-32 Amps. C- curve SP MCB-5 No.
Supply of 3.5 x 35 sq.mm XLPE insulated & PVC sheathed armoured Aluminium power cable of 1.1 KV grade confirming to IS : 7098 (Part-I) 1988 with upto date ammendement as req.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade upto 35 sq. mm size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade upto 35 sq. mm size in the existing RCC/ HUME/ METAL pipe/HDPE Pipe as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade upto 35 sq. mm size in the existing masonry open duct as required.
Supplying and making end termination with brass compression gland and aluminium lugs for 3½ X 35 sq. mm (32 mm) size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 grade as required.
Supply, installation, testing & commissioning of CPRI tested, fully autonomous Early Streamer Emission Lightning Conductor (ESELC) having Δt (gain in triggering time) of minimum 60 µs and radius of protection 60 meters in level - 1 protection zone, at 10 meter mast (2 meter FRP mast (OD 68 mm, ID 60 mm, wall thickness 4 mm and 8 meter length G.I. pipe of suitable size and also provide guying wire, clamp and with all accessories to protect lightning arrestor completed etc as required.
Providing & creating of earth pits using CPRI tested advanced chemical earth rod (ISOROD) made of three nos of copper tubes of 3 inch dia, 8 feet long, 0.12 inch thick interconnected by copper strips of 25mm X 3mm size installed vertically or horizontally as per the site conditions complete with flanges, bends and top cover dully backfilled with ISOGEL earth enhancing compound of 20kgs. along with heavy duty plastic inspection chamber including excavation & refilling etc complete as required.
Supply and laying of 70 sq. mm copper flexible wire for down conductor including all accessories from air terminal to the earth pit complete as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Supply, Installation, Testing and Commissioning of 2 KVA, single phase UPS system with input voltage 150 - 280 volt and out put 230 volt + 1%, 50 Hz + 5 Hz., voltage regulation from no load to full load will be within + 1% in both the case. UPS will withstand 10% oveload for 10 minutes and 50 % over load for 10 seconds. The UPS should have auto and manual baypass arrangments. The UPS should provided to withstand 15 minutes battery backup on full load with suitable rating sealed maintenance free battery i/c interlinks complete etc. as required.
Earthing with G. I. pipe 4.5 m long x 40 mm dia. (Drilling of 300 mm dia, 4.5 Mtr deep by using Borewell machine) including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. including charcoal or coke and salt complete as required.
surbhi association
M/s LEESHA ELECTRICALS
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .