Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹82.2 LAdmitted-Finance 0611 6TH FLOOR RUNWAL R SQUARE L B S MARG OPP VEENA NAGAR MULUND WEST MUMBAI MAHARASHTRA 400080 | MUMBAI SUBURBAN | MAHARASHTRA | 400080 | L1 | Admitted-Finance | |
| 2 | Rejected-Technical 11 BAURIA INDUSTRIAL ESTATE CHENGAIL HOWRAH WEST BENGAL 711307 | HOWRAH | WEST BENGAL | 711307 | - | Rejected-Technical Technically not acceptable |
| Sl No | Description | Qty | Unit | HD FIRE PROTECT PVT.LTD. L1 |
|---|---|---|---|---|
| 1.00A. DELUGE WATER SPRAY SYSTEMS (MVWS SYSTEM + WATER CURTAIN SYSTEM + HVWS SYSTEM) CS Deluge Valve with Dry Pilot Trim & Electric Release Trim, Horizontal Inlet & Horizontal Outlet, without skid, UL/FM Approved, complete with Dry Pilot Trim with Test, Alarm & Drain devices, Local Deluge Valve Control Station (DVLCS) (1 No. per DV), Pressure Transmitters (02 Nos per DV.), 3/3 way SIL2 certified Intrinsically Safe Solenoid Valve-24V DC (1 No. per DV), Pressure Gauges (03 Nos. per DV), Air Filetr Regulator (AFR)(1 No. per DV), Air Vessel of adequate capacity (1 No. per DV), etc. in compliance with the scheme shown in attached "Technical Data Sheets for Fire Fighting & Safety Equipment (TK-1P21A-SA-DAT-0001)". The Deluge Valves shall be supplied with the trim and associated instruments duly assemblied with the deluge valve and with suitable packaging to avoid damage during transportation. The upstream strainer, block valves and by-pass valve including the pipes connecting to these items are NOT in bidder's scope of supply. All items shall be suitable and certified for Zone 1,IIC,T3 area classification. All electrical and instruments shall be certified for intrinsically safe (Ex-ia) and Solenoid valve shall be certified to Explosion Proof (Ex-d). All instruments and enclosures (Junction Boxes/ cabinets/panels/ accessories) in field shall be dust proof and weather proof with IP-67. | ||||
| 1.01 | 200 mm NB | 12 | Set | 33,08,160 ₹33,08,160 Lowest |
| 1.02 | 150 mm NB | 6 | Set | 14,18,880 ₹14,18,880 Lowest |
| 1.03 | 100 mm NB | 4 | Set | 8,87,120 ₹8,87,120 Lowest |
| 1.04 | 80 mm NB | 1 | Set | 2,10,580 ₹2,10,580 Lowest |
| 2.00MVW Spray Nozzle with 1/2" MNPT end connection, MOC - Stainless Steel, UL / FM listed, (with Inbuilt Strainer): SIZE 15 NB | ||||
| 2.01 | MVW Spray Nozzle with 1/2" MNPT end connection, K factor-18, spray angle 120°, MOC - Stainless Steel with corrosion resistant coating, UL Listed. | 200 | Nos | 58,000 ₹58,000 Lowest |
| 2.02 | MVW Spray Nozzle with 1/2" MNPT end connection, K factor-18, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed. | 690 | Nos | 2,00,100 ₹2,00,100 Lowest |
| 2.03 | MVW Spray Nozzle with 1/2" MNPT end connection, K factor-18, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed. | 250 | Nos | 72,500 ₹72,500 Lowest |
| 2.04 | MVW Spray Nozzle with 1/2" MNPT end connection, K factor-22, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed. | 60 | Nos | 17,400 ₹17,400 Lowest |
Tender Value
Refer Docs
Closing Date
12 Aug 2025, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Mr. Amit Borkar
thyssenkrupp Uhde India Private Limited, Vikhroli, Mumbai
SUPPLY OF DELUGE SYSTEM EQUIPMENT FOR MSB UNIT FOR NREP as per Technical Specifications for Numaligarh Refinery Limited, Assam, INDIA.
2025_NRL_867745_1
TK-1P22A-MP-RFQ-0074
Limited
Miscellaneous Goods
Supply
210 days
Numaligarh Refinary Limited Assam
Please refer Tender documents.
6 documents required · 6 mandatory
₹0
Exempted
15 Oct 2025
8 Jul 2025
13 Aug 2025
8 Jul 2025
12 Aug 2025
22 Jul 2025
8 Jul 2025 - 18 Jul 2025
A. DELUGE WATER SPRAY SYSTEMS (MVWS SYSTEM + WATER CURTAIN SYSTEM + HVWS SYSTEM) CS Deluge Valve with Dry Pilot Trim & Electric Release Trim, Horizontal Inlet & Horizontal Outlet, without skid, UL/FM Approved, complete with Dry Pilot Trim with Test, Alarm & Drain devices, Local Deluge Valve Control Station (DVLCS) (1 No. per DV), Pressure Transmitters (02 Nos per DV.), 3/3 way SIL2 certified Intrinsically Safe Solenoid Valve-24V DC (1 No. per DV), Pressure Gauges (03 Nos. per DV), Air Filetr Regulator (AFR)(1 No. per DV), Air Vessel of adequate capacity (1 No. per DV), etc. in compliance with the scheme shown in attached "Technical Data Sheets for Fire Fighting & Safety Equipment (TK-1P21A-SA-DAT-0001)". The Deluge Valves shall be supplied with the trim and associated instruments duly assemblied with the deluge valve and with suitable packaging to avoid damage during transportation. The upstream strainer, block valves and by-pass valve including the pipes connecting to these items are NOT in bidder's scope of supply. All items shall be suitable and certified for Zone 1,IIC,T3 area classification. All electrical and instruments shall be certified for intrinsically safe (Ex-ia) and Solenoid valve shall be certified to Explosion Proof (Ex-d). All instruments and enclosures (Junction Boxes/ cabinets/panels/ accessories) in field shall be dust proof and weather proof with IP-67.
MVW Spray Nozzle with 1/2" MNPT end connection, MOC - Stainless Steel, UL / FM listed, (with Inbuilt Strainer): SIZE 15 NB
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-18, spray angle 120°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-18, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-18, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-22, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-22, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-26, spray angle 120°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-26, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-30, spray angle 120°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-30, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-30, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-35, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-35, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-41, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-51, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-51, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-79, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
Quartzoid Bulb Detector with 1/2" MNPT end connection, MOC - Brass with Nickel chrome plated, K-80, Temp. Rating-93 deg. C, UL Listed. - Size 15 NB
Restriction Orifice Plate, with integrated body and handle, SS 316. RO plate OD shall be suitable to install between flanges as per ANSI B 16.5 #150.
Size 1:- 250 mm Size 2: 127.12 mm Size 3:- 9 mm
Size 1:- 250 mm Size 2: 120 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 137 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 136 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 106 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 105 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 100 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 90 mm Size 3:- 9 mm
Size 1:- 150 mm Size 2: 100 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 93 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 92 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 84 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 82 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 80 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 76 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 74 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 72 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 65 mm Size 3:- 6mm
Size 1:- 100 mm Size 2: 60 mm Size 3:- 6 mm
Size 1:- 100 mm Size 2: 55 mm Size 3:- 6 mm
Size 1:- 100 mm Size 2: 52 mm Size 3:- 6 mm
Size 1:- 100 mm Size 2: 50 mm Size 3:- 6 mm
Size 1:- 100 mm Size 2: 49 mm Size 3:- 6 mm
Size 1:- 100 mm Size 2: 47 mm Size 3:- 6 mm
Size 1:- 80 mm Size 2: 52 mm Size 3:- 3 mm
Size 1:- 80 mm Size 2: 42 mm Size 3:- 3 mm
Size 1:- 80 mm Size 2: 40 mm Size 3:- 3 mm
Size 1:- 80 mm Size 2: 35 mm Size 3:- 3 mm
Size 1:- 80 mm Size 2: 34 mm Size 3:- 3 mm
Size 1:- 80 mm Size 2: 32 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 32 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 30 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 28 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 26 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 25 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 22 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 20 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 18 mm Size 3:- 3 mm
On-site Supervision Service for Installation, Testing & Commissioning of Deluge Valve
SPARES
SPARE PARTS for each size of Deluge Valve with Dry Pilot & Electric Trim, Horizontal Inlet & Horizontal Outlet (as per manufacturer's recommendation) including but not limited to the following items: (a) Diaphragm - 1 set (b) Seat Rubber - 1 No. (c) O Rings - 1 set
Solenoid Valve, 2/2 Way,24V DC, Intrinsically Safe, PESO Certified (same as that to be supplied with deluge valve). -15mm
Pressure Transmitter (same as that to be supplied with deluge valve). - 15mm
Pressure Gauge (same as that to be supplied with deluge valve).- 15mm
Air Filter Regulator (same as that to be supplied with deluge valve). - 15mm
MVW Spray Nozzle with 1/2" MNPT end connection, MOC - Stainless Steel, UL / FM listed, ( with Inbuilt Strainer ): 15 NB
K factor-18, spray angle 120°
K factor-18, spray angle 110°
K factor-18, spray angle 90°
K factor-22, spray angle 110°
K factor-22, spray angle 90°
K factor-26, spray angle 120°
K factor-26, spray angle 90°
K factor-30, spray angle 120°
K factor-30, spray angle 110°
K factor-30, spray angle 90°
K factor-35, spray angle 110°
K factor-35, spray angle 90°
K factor-41, spray angle 90°
K factor-51, spray angle 110°
K factor-51, spray angle 90°
K factor-79, spray angle 90°
Quartzoid Bulb Detector with 1/2" MNPT end connection, MOC - Brass with Nickel chrome plated, K-80, Temp. Rating-93 deg. C, UL Listed. - Size 15 NB
Restriction Orifice Plate, with integrated body and handle, SS 316. RO plate OD shall be suitable to install between flanges as per ANSI B 16.5 #150.
Size 1:- 250mm Size 2:- Blank Size3:- 9 mm
Size 1:- 200mm Size 2:- Blank Size3:- 9 mm
Size 1:- 150mm Size 2:- Blank Size3:- 6 mm
Size 1:- 100mm Size 2:- Blank Size3:- 6 mm
Size 1:- 80mm Size 2:- Blank Size3:- 3 mm
Size 1:- 50mm Size 2:- Blank Size3:- 3 mm
Description of Work / Item(s)
Amount
A. DELUGE WATER SPRAY SYSTEMS (MVWS SYSTEM + WATER CURTAIN SYSTEM + HVWS SYSTEM)
CS Deluge Valve with Dry Pilot Trim & Electric Release Trim, Horizontal Inlet & Horizontal Outlet, without skid, UL/FM Approved, complete with Dry Pilot Trim with Test, Alarm & Drain devices, Local Deluge Valve Control Station (DVLCS) (1 No. per DV), Pressure Transmitters (02 Nos per DV.), 3/3 way SIL2 certified Intrinsically Safe Solenoid Valve-24V DC (1 No. per DV), Pressure Gauges (03 Nos. per DV), Air Filetr Regulator (AFR)(1 No. per DV), Air Vessel of adequate capacity (1 No. per DV), etc. in compliance with the scheme shown in attached "Technical Data Sheets for Fire Fighting & Safety Equipment (TK-1P21A-SA-DAT-0001)". The Deluge Valves shall be supplied with the trim and associated instruments duly assemblied with the deluge valve and with suitable packaging to avoid damage during transportation. The upstream strainer, block valves and by-pass valve including the pipes connecting to these items are NOT in bidder's scope of supply. All items shall be suitable and certified for Zone 1,IIC,T3 area classification. All electrical and instruments shall be certified for intrinsically safe (Ex-ia) and Solenoid valve shall be certified to Explosion Proof (Ex-d). All instruments and enclosures (Junction Boxes/ cabinets/panels/ accessories) in field shall be dust proof and weather proof with IP-67.
MVW Spray Nozzle with 1/2" MNPT end connection, MOC - Stainless Steel, UL / FM listed, (with Inbuilt Strainer): SIZE 15 NB
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-18, spray angle 120°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-18, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-18, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-22, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-22, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-26, spray angle 120°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-26, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-30, spray angle 120°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-30, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-30, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-35, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-35, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-41, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-51, spray angle 110°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-51, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
MVW Spray Nozzle with 1/2" MNPT end connection, K factor-79, spray angle 90°, MOC - Stainless Steel with corrosion resistant coating, UL Listed.
Quartzoid Bulb Detector with 1/2" MNPT end connection, MOC - Brass with Nickel chrome plated, K-80, Temp. Rating-93 deg. C, UL Listed. - Size 15 NB
Restriction Orifice Plate, with integrated body and handle, SS 316. RO plate OD shall be suitable to install between flanges as per ANSI B 16.5 #150.
Size 1:- 250 mm Size 2: 127.12 mm Size 3:- 9 mm
Size 1:- 250 mm Size 2: 120 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 137 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 136 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 106 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 105 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 100 mm Size 3:- 9 mm
Size 1:- 200 mm Size 2: 90 mm Size 3:- 9 mm
Size 1:- 150 mm Size 2: 100 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 93 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 92 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 84 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 82 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 80 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 76 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 74 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 72 mm Size 3:- 6 mm
Size 1:- 150 mm Size 2: 65 mm Size 3:- 6mm
Size 1:- 100 mm Size 2: 60 mm Size 3:- 6 mm
Size 1:- 100 mm Size 2: 55 mm Size 3:- 6 mm
Size 1:- 100 mm Size 2: 52 mm Size 3:- 6 mm
Size 1:- 100 mm Size 2: 50 mm Size 3:- 6 mm
Size 1:- 100 mm Size 2: 49 mm Size 3:- 6 mm
Size 1:- 100 mm Size 2: 47 mm Size 3:- 6 mm
Size 1:- 80 mm Size 2: 52 mm Size 3:- 3 mm
Size 1:- 80 mm Size 2: 42 mm Size 3:- 3 mm
Size 1:- 80 mm Size 2: 40 mm Size 3:- 3 mm
Size 1:- 80 mm Size 2: 35 mm Size 3:- 3 mm
Size 1:- 80 mm Size 2: 34 mm Size 3:- 3 mm
Size 1:- 80 mm Size 2: 32 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 32 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 30 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 28 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 26 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 25 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 22 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 20 mm Size 3:- 3 mm
Size 1:- 50 mm Size 2: 18 mm Size 3:- 3 mm
On-site Supervision Service for Installation, Testing & Commissioning of Deluge Valve
SPARES
SPARE PARTS for each size of Deluge Valve with Dry Pilot & Electric Trim, Horizontal Inlet & Horizontal Outlet (as per manufacturer's recommendation) including but not limited to the following items: (a) Diaphragm - 1 set (b) Seat Rubber - 1 No. (c) O Rings - 1 set
Solenoid Valve, 2/2 Way,24V DC, Intrinsically Safe, PESO Certified (same as that to be supplied with deluge valve). -15mm
Pressure Transmitter (same as that to be supplied with deluge valve). - 15mm
Pressure Gauge (same as that to be supplied with deluge valve).- 15mm
Air Filter Regulator (same as that to be supplied with deluge valve). - 15mm
MVW Spray Nozzle with 1/2" MNPT end connection, MOC - Stainless Steel, UL / FM listed, ( with Inbuilt Strainer ): 15 NB
K factor-18, spray angle 120°
K factor-18, spray angle 110°
K factor-18, spray angle 90°
K factor-22, spray angle 110°
K factor-22, spray angle 90°
K factor-26, spray angle 120°
K factor-26, spray angle 90°
K factor-30, spray angle 120°
K factor-30, spray angle 110°
K factor-30, spray angle 90°
K factor-35, spray angle 110°
K factor-35, spray angle 90°
K factor-41, spray angle 90°
K factor-51, spray angle 110°
K factor-51, spray angle 90°
K factor-79, spray angle 90°
Quartzoid Bulb Detector with 1/2" MNPT end connection, MOC - Brass with Nickel chrome plated, K-80, Temp. Rating-93 deg. C, UL Listed. - Size 15 NB
Restriction Orifice Plate, with integrated body and handle, SS 316. RO plate OD shall be suitable to install between flanges as per ANSI B 16.5 #150.
Size 1:- 250mm Size 2:- Blank Size3:- 9 mm
Size 1:- 200mm Size 2:- Blank Size3:- 9 mm
Size 1:- 150mm Size 2:- Blank Size3:- 6 mm
Size 1:- 100mm Size 2:- Blank Size3:- 6 mm
Size 1:- 80mm Size 2:- Blank Size3:- 3 mm
Size 1:- 50mm Size 2:- Blank Size3:- 3 mm
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .