| 1 | L1₹1.8 CrAccepted-AOC SHIVAJI NAGAR GALI NO 1 DHANGU ROAD MODEL TOWN PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹1.8 Cr | L1 | Accepted-AOC L1 Being Lowest |
| 2 | L2₹2.0 Cr+₹13.9 L (7.64%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹2.0 Cr+₹13.9 L (7.64%) | L2 | Rejected-Finance Other than lowest |
| 3 | L3₹2.0 Cr+₹14.0 L (7.72%)Rejected-Finance 1ST FLOOR RAGHUNATH MARKET NEAR TELEPHONE EXCHANGE PATHANKOT 145001 | PATHANKOT | PUNJAB | 145001 | ₹2.0 Cr+₹14.0 L (7.72%) | L3 | Rejected-Finance Other than lowest |
| 4 | L4₹2.2 Cr+₹36.3 L (20.0%)Rejected-Finance 24 A RAGHBIR MARG NEAR 22 NO PHATAK PATIALA 147001 PB | PATIALA | PATIALA | PUNJAB | 147001 | ₹2.2 Cr+₹36.3 L (20.0%) | L4 | Rejected-Finance Other than lowest |
| 5 | L5₹2.2 Cr+₹38.1 L (20.9%)Rejected-Finance 5037 5038 URBAN ESTATE PH 1 PATIALA 147002 PUNJAB | PATIALA | PATIALA | PUNJAB | 147002 | ₹2.2 Cr+₹38.1 L (20.9%) | L5 | Rejected-Finance Other than lowest |
Tender Value
₹3.0 Cr
EMD Value
₹3.7 L
Closing Date
2 Apr 2024, 6:00 pmClosed
AP Bansal Chief Engineer
HQ CHIEF ENGINEER PATHANKOT ZONE
PROVN OF UNDERGROUND CABLING AND ALLIED WORKS AT DALHOUSIE
2023_MES_634537_2
CA NO. CEPZ-32/2023-24
Open Tender
Civil Works
Item Rate
240 days
AGE (I) DALHOUSIE
as per tender documents
7 documents required · 7 mandatory
₹2,000
Yes
AGE (I) DALHOUSIE
₹3.7 L
Yes
2 May 2024
11 Mar 2024
9 Apr 2024
11 Mar 2024
2 Apr 2024
26 Mar 2024
Amount
Supply, laying and testing HT cable XLPE Insulated (Earthed), screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 11000 Volts grade with aluminium conductor of size 95 Sq mm 3 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 300 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 240 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 150 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 120 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 95 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 70 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 50 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 35 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 25 sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 16 sq mm 4 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 10 sq mm 4 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 16 sq mm 2 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 10 sq mm 2 core complete all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of size 6 sq mm 2 core complete all as specified and directed by Engineer-in-Charge.
Supply and fixing 1.5 sqmm 3 core PVC insulated and PVC round sheathed multistranded copper conductor flexible industrial cable 1100 V grade drawn through PVC conduit (junction box to street light fitting) in existing street light pole complete all as specified and directed. (Note :- PVC Conduit shall be measured and paid for separately)
M&L of FRP junction box of size 250 X 200 X 100 mm having 4 Nos aluminium bus bar of size 25X4 mm fixed on epoxy insulators with MCB SP 6 Amps ,fixed on the pole with 02 Nos clamps of size 25 x 4 mm,nut bolts etc.complete all as specified and directed.
S&F for Rigid non-metallic PVC conduit of 20 mm dia heavy duty along steel tubular swaged poles for wire from junction box to fittings fixed with 04 Nos MS clamps of size 25 x4 mm complete all as specified and directed.
M&L for Cable jointing kit for HT, 11KV (Earthed) grade cable for outdoor type end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core, XLPE, aluminium conductor cable, size 95 Sqmm , complete all as specified and directed by Engineer-in-Charge.
M&L for Cable jointing kit for HT, 11KV (Earthed) grade cable of straight though heat shrink type joint complete with jointing material and accessories suitable for 3 core, XLPE, aluminium conductor cable, size 95 Sqmm , complete all as specified and directed by Engineer-in-Charge.
Supply and erection of steel tubular swaged pole 410 SP 55, 11m long truly vertical position till setting of PCC foundation complete with cast iron base plate, final Taper plug, bolts, nuts and screws as specified type confirming to IS 2713 complete including 2 coats of aluminium paint over one coat of red oxide Zinc chrome primer on external exposed surfaces and 2 coats of black bituminous paint on portion embedded in concrete in internal surface of pole complete all as specified and directed. (Note :- Excavation, PCC required for foundation and coping will be measured and paid for separately).
M&L Cross arm bracing support clamps and back plates fabricated from structural steel sections including nuts, bolts and washers welding bending cold or hot drilling holes for bolts in any shape or sizes as indicated or directed inclusive of one coat of primer and two coats of aluminium paint all as specified & as directed by Engineer-in-Charge.
M&L air break switch gang operated triple pole mechanical operated, vertically or Horizontally mounted on insulator and steel frame with operating mechanism worked from ground level for correct rating 200 amps, 11000 Volts with locking arrangement, connecting and testing, including in Air Break Insulators (Switch) complete all as specide and directed.
Supply and install drop out lift OFF HT 11 KV, 200 Amps fuse link consisting of channel iron base having 11 KV post type insulators in stack & 2 stack per phase complete with fuse carrier of SRBP tube with heavily tinned non ferrous metal parts and spring loaded phosphor bronze contact complete manufactured as per IS 9385 complete all as specified and directed by Engineer-in-Charge.
Supply and fixing of lightning arresters, expulsion type, complete with all fittings, transmission class, discharge capacity 65 kilo amp, suitable for working in 11000 volts complete all as specified and as directed by Engineer-in-Charge.
M&L for stay assembly complete with accessories as shown in electric plate No.1 stay rod 20mm (loop type insulator) stay clamps excavation & concrete measured and paid for separately all as specified & as directed by Engineer-in-Charge.
M&L galvanized stay strand size 7/4mm wire for support of stay on the pole complete all as specified & as directed by Engineer-in-Charge.
M&L for Loop type insulator vitreous porcelain, white or brown or green at large size with over all dimension 90x140mm clearance of hole 25.5 mm complete all as specified and as directed by Engineer-in-Charge.
M&L danger notice plate of 1.6 mm thick MS sheet vitreous enamelled white with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps nuts bolts of approved size complete for HT 11000 volts of size 25x20 cm complete all as specified and as direceted by Engineer-in- Charge.
Excavation in trenches not exc 1.5 mtr wide and n.exc 1.5 mtr deep and getting out in hard/dense soil complete all as specified and as directed by Engineer-in-Charge.
Excavation in trenches for n.exc 1.5 mtr wide and exc 1.5 mtr depth and getting out in hard/dense soil complete all as specified and as directed by Engineer-in-Charge.
Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm complete all as specified & directed.
Removing excavated materials n.exc 50m and depositing where directed at a level n.exc 1.5m above the Starting point.
M & L for good quality dry sand for cushioning to underground cable in layer of 8cm thick before laying the cable and 15cm thick after laying the cable all as specified and directed in clause 19.75 of SSR Part-I (2009). (Note :- Punned thickness shall be measured.)
Supply & laying un-reinforced precast conc cable cover class LV type 1, flat size 250mm x 150mm x 40 mm all as specified & as directed by Engineer-in-Charge.
Supply & laying un-reinforced precast concrete cable cover class HV type 1, flat size 300mm x 180mm x 40 mm all as specified & directed.
M&L for route indicator for 11000 Volts HT line made of angle iron size 40x40x6mm welded in length of 1.2mtr alongwith MS sheet of thickness 3.15mm, size 100x100mm engraved with HT letter, duly embedded in PCC block including nuts and bolts and all other necessary accessories, complete all as specified and directed by Engineer-in-Charge.
Supply and fixing GI pipe light grade 40mm with all fittings laid in trenches complete all as specified and directed.
All as per item no.38 here in before but for size of pipe 50mm.
All as per item no.38 here in before but for size of pipe 80mm.
Dismentling of steel tublar pole/struts, 9mtr/11 mtr complete all as specified and directed .
Dismentling of Stay assembly complete all as specified and directed .
Dismentling of cross-arms of MS channel or angle section, clamp, nut, bolt and washer etc complete on Rail/steel tubuler pole all as specified and directed
Dismentling of insulator any type for overhead line complete on PCC/ steel tublar pole all as specified and directed .
Dismentling of ACSR or AAC conductor any type from overhead line complete on Rail/ steel tubuler pole all as specified and directed
M&L for Disconnecting HT/LT and earth termination connections from transformer, taking down the transformers from plinth/platform and loading into the vehicle and shifting the trasformer at new place in the Dalhousie cantt area permises with using of suitable T&P and reconnecting HT/LT connections at site and charging the transformer on load, commissioning and testing including meggar test at site all as directed by Engineer - in - Charge .
Supply,installation, testing & commisioning LT Panel board, outdoor type, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6 mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge. (Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1(with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: Main LT panel 'A' for Ticca area 200 KVA Transformer Incomer:- (a) MCCB 320 Amps , TPN, 36kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 125 Amps,TPN,25kA,415V,50Hz capacity -03 Nos (01 Stand by) (b) MCCB 25 Amps,TPN,16kA,415V,50Hz capacity -01 Nos (c) multifunction meter to read Amp,Voltage,PF,frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminium Bus bar (3 phase and neutral) of capacity 500 amp and fixed inside the panel on best insulating material-01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers, with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and confirming to IS- 61439/2011, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer sleeve switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 'B" for Ticca area 200 KVA transforer Incomer:- (a) MCCB 125 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -02 Nos (01 Stand by) (b) MCCB 40 Amps ,TPN, 16kA,415V,50Hz capacity -03 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 200 amp and fixed inside the panel on best insulating material -01 Set
Supply,installation, testing & commisioning LT Panel board, outdoor type, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6 mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge. (Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1(with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 2 for Ticca area 200 KVA Transformer Incomer:- (a) MCCB 40 Amps , TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps,TPN,16kA,415V,50Hz capacity -06 Nos (01 Stand by) (b) MCB SPN 16 Amps,DP,16kA,230V,50Hz capacity -02 Nos (c) Multifunction meter to read Amp,Voltage,PF,frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminium Bus bar (3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material-01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 3 for Ticca area 200 KVA transforer Incomer:- (a) MCCB 40 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -03 Nos (01 Stand by) (b) MCB SPN 16 Amps ,DP, 16kA,230V,50Hz capacity -06 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers, with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for going out 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 4 for Ticca area 200 KVA transforer Incomer:- (a) MCCB 40 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,230V,50Hz capacity -05 Nos (01 Stand by) (b) MCB SPN 16 Amps ,DP, 16kA,230V,50Hz capacity -03 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers, with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 5 for Ticca area 200 KVA transforer Incomer:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -06 Nos (01 Stand by) (b) MCB SPN 16 Amps ,DP, 16kA,230V,50Hz capacity -06 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 6 for Ticca area 200 KVA transforer Incomer:- (a) MCCB 125 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 63 Amps ,TPN, 16kA, 415V, 50Hz capacity - 02 Nos (01 Stand by) (b) MCCB 40 Amps TPN, 16kA, 415V, 50Hz capacity -03 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 200 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers, with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 7 for Ticca area 200 KVA transforer Incomer:- (a) MCCB 40 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -09 Nos (01 Stand by) (b) MCB SPN 16 Amps ,DP, 16kA,415V,50Hz capacity -02 Nos (01 Stand by) (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers, with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 8 for Ticca area 200 KVA transforer Incomer:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -04 Nos (01 Stand by) (b) MCB SPN 16 Amps ,DP, 16kA,415V,50Hz capacity -05 (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers, with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 9 for Ticca area 200 KVA transforer Incomer:- (a) MCCB 40 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -07 Nos (01 Stand by) (b) MCB SPN 16 Amps ,DP, 16kA,415V,50Hz capacity -06 (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers, with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item)th PCC platform and suitable cable gland for bottom entry cable comprising of following :- Location: LT panel 10 for Ticca area 200 KVA transforer Incomer:- (a) MCCB 40 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -05 Nos (01 Stand by) (b) MCB SPN 16 Amps ,DP, 16kA,415V,50Hz capacity -04 (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: Main LT panel 'A' for 200 KVA Transforer Mankot area Incomer:- (a) MCCB 320 Amps ,TPN, 36kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -04 Nos (01 Stand by) (b) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos (c) MCCB 25 Amps,TPN, 16kA,415V,50Hz capacity -01 Nos (d) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (e) LED indicating lamp (R,Y,B)- 01 Set of 3 (f) Aluminum Bus bar ( 3 phase and neutral) of capacity 500 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 1 fo Mankot area 200 KVA transforer Incomer:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -06 Nos (01 Stand by) (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 150 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers, with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item)th PCC platform and suitable cable gland for bottom entry cable comprising of following :- Location: LT panel 2 for Mankot 200 KVA transforer Incomer:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -06 Nos (01 Stand by) (b) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (c) LED indicating lamp (R,Y,B)- 01 Set of 3 (d) Aluminum Bus bar ( 3 phase and neutral) of capacity 150 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 3 for Mankot 200 KVA transforer Incomer:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -06 Nos (01 Stand by) (b) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (c) LED indicating lamp (R,Y,B)- 01 Set of 3 (d) Aluminum Bus bar ( 3 phase and neutral) of capacity 150 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 4 for Mankot 200 KVA transforer Incomer:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -04 Nos (01 Stand by) (b) MCB 16 Amps,TPN, 16kA, 415V,50Hz capacity -02 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: Main LT panel 'B' for 100 KVA transformer Mankot area Incomer:- (a) MCCB 200 Amps ,TPN, 36kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -02 Nos (01 Stand by) (b) MCCB 63 Amps, TPN, 16kA,415V, 50Hz capacity -02 Nos (c) MCCB 25 Amps , TPN, 16kA,415V,50Hz capacity -01 Nos (d) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (e) LED indicating lamp (R,Y,B)- 01 Set of 3 (f) Aluminum Bus bar ( 3 phase and neutral) of capacity 300 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 5 for Mankot 100 KVA transforer Incomer:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -04 Nos (01 Stand by) (b) MCB 16 Amps,SPN, 16kA,230V,50Hz capacity -02 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 150 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 6 for Mankot 100 KVA transforer Incomer:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -03 Nos (01 Stand by) (b) MCB 16Amps, SPN,16kA,230V,50Hz capacity -04 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 7 for Mankot 100 KVA transforer Incomer:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -03 Nos (01 Stand by) (b) MCB 16 Amps , SPN, 16kA,215V,50Hz capacity -04 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: Main LT panel 'C' for 250 KVA transformer Mankot area Incomer:- (a) MCCB 400 Amps ,TPN, 36kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -02 Nos (01 Stand by) (b) MCCB 63 Amps , TPN, 16kA,415V,50Hz capacity -05 Nos (c) MCCB 25 Amps,TPN, 16kA,415V,50Hz capacity -01 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 600 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 8 for Mankot 250 KVA transforer Incomer:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -04 Nos (01 Stand by) (b) MCB 16 Amps , SPN, 16kA,230V,50Hz capacity -05 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50*50*6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 9 for Mankot 250 KVA transforer Incomer:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -07 Nos (01 Stand by) (b) MCB 16 Amps , SPN, 16kA,230V,50Hz capacity -03 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 150 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50*50*6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 10 for Mankot 250 KVA transforer Incomer:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -05 Nos (01 Stand by) (b) MCB 16Amps, SPN,16kA,230V,50Hz capacity -05 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 11 for Mankot 250 KVA transforer Incomer:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -06 Nos (01 Stand by) (b) MCB 16 Amps , SPN, 16kA, 230V,50Hz capacity -02 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 12 for Mankot 250 KVA transforer Incomer:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA, 415V, 50Hz capacity -04 Nos (01 Stand by) (b) MCB 16 Amps , SPN, 16kA, 215V,50Hz capacity -05 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel 13 for Mankot 250 KVA transforer Incomer:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -04 Nos (01 Stand by) (b) MCB 16 Amps , SPN, 16kA,215V,50Hz capacity -02 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: Main LT panel 'C' for 100 KVA transformer MH Dalhousie Incomer:- (a) MCCB 200 Amps ,TPN, 36kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -03 Nos (01 Stand by) (b) MCCB 25 Amps , SPN, 16kA,415V,50Hz capacity -01 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 300 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: Main LT panel 'A' for 400 KVA Transformer MH Dalhousie Map area Incomer:- (a) MCCB 630 Amps ,TPN, 50kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 320 Amps ,TPN, 36kA,415V,50Hz capacity -01 Nos (b) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -04 Nos (01 Stand by) (c) MCCB 40 Amps , SPN, 16kA,415V,50Hz capacity -01 Nos (d) MCCB 25 Amps , TPN, 25kA,415V,50Hz capacity -01 Nos (e) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (f) LED indicating lamp (R,Y,B)- 01 Set of 3 (g) Aluminum Bus bar ( 3 phase and neutral) of capacity 1000 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel '1' for 400 KVA Transformer MH Dalhousie Map area Incomer:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -07 Nos (01 Stand by) (d) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 150 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel '2' for 400 KVA Transformer MH Dalhousie Map area Incomer:- (a) MCCB 40 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -03 Nos (01 Stand by) (b) MCB 16Amps, SPN,16kA,230V,50Hz capacity -03 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel '3' for 400 KVA Transformer MH Dalhousie Map area Incomer:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -09 Nos (01 Stand by) (b) MCB 16Amps, SPN,16kA,230V,50Hz capacity -02 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 150 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel '4' for 400 KVA Transformer MH Dalhousie Map area Incomer:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -07 Nos (01 Stand by) (b) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (c) LED indicating lamp (R,Y,B)- 01 Set of 3 (d) Aluminum Bus bar ( 3 phase and neutral) of capacity 150 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: Main LT panel 'B' for 400 KVA Transformer MH Dalhousie Incomer:- (a) MCCB 630 Amps ,TPN, 50kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 125 Amps ,TPN, 25kA,415V,50Hz capacity -04 Nos (01 Stand by) (b) MCCB 160 Amps , TPN , 25kA,415V,50Hz capacity -01 Nos (c) MCCB 63 Amps , TPN, 16kA,415V,50Hz capacity -01 No (d) MCCB 25 Amps, TPN , 16kA,415V,50Hz capacity -01 No (e) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (f) LED indicating lamp (R,Y,B)- 01 Set of 3 (g) Aluminum Bus bar ( 3 phase and neutral) of capacity 1000 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel '5' for 400 KVA Transformer MH Dalhousie Incomer:- (a) MCCB 125 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -07 Nos (01 Stand by) (b) MCB 16 Amp , SPN, 16 kA, 230V, 50 Hz capacity -02 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 200 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel '6' for 400 KVA Transformer MH Dalhousie Incomer:- (a) MCCB 160 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -03 Nos (01 Stand by) (b) MCCB 25 Amps,TPN, 16kA,415V,50Hz capacity -03 Nos (c) MCB 16 Amp, SPN, 16kA,230V,50Hz capacity -01 Nos (d) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (e) LED indicating lamp (R,Y,B)- 01 Set of 3 (f) Aluminum Bus bar ( 3 phase and neutral) of capacity 250 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade crushed stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel '7' for 400 KVA Transformer MH Dalhousie Incomer:- (a) MCCB 63 Amps ,TPN, 16kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -04 Nos (01 Stand by) (b) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (c) LED indicating lamp (R,Y,B)- 01 Set of 3 (d) Aluminum Bus bar ( 3 phase and neutral) of capacity 100 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel '8' for 400 KVA Transformer MH Dalhousie Incomer:- (a) MCCB 125 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -08 Nos (01 Stand by) (b) MCB 16 Amp , SPN, 16 kA, 230 V , 50 Hz capacity -01 Nos (c) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (d) LED indicating lamp (R,Y,B)- 01 Set of 3 (e) Aluminum Bus bar ( 3 phase and neutral) of capacity 200 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel '9' for 400 KVA Transformer MH Dalhousie Incomer:- (a) MCCB 125 Amps ,TPN, 25kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 25 Amps ,TPN, 16kA,415V,50Hz capacity -08 Nos (01 Stand by) (b) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (c) LED indicating lamp (R,Y,B)- 01 Set of 3 (d) Aluminum Bus bar ( 3 phase and neutral) of capacity 200 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: Main LT panel 'A' for 400 KVA Transformer at Bde area Incomer:- (a) MCCB 630 Amps ,TPN, 50kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 250 Amps ,TPN, 36kA,415V,50Hz capacity -02 Nos (01 Stand by) (b) MCCB 200 Amps , TPN,36 kA ,415V,50Hz capacity -01 Nos (c) MCCB 125 Amps , TPN, 25kA,415V,50Hz capacity -01 Nos (d) MCCB 25 Amps , TPN , 16kA,415V,50Hz capacity -01 Nos (e) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (f) LED indicating lamp (R,Y,B)- 01 Set of 3 (g) Aluminum Bus bar ( 3 phase and neutral) of capacity 1000 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel '1' for 400 KVA Transformer at Bde area Incomer:- (a) MCCB 250 Amps ,TPN, 36kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -02 Nos (01 Stand by) (b) MCCB 40 Amps , TPN,16kA,415V,50Hz capacity -01 Nos (c) MCCB 25 Amps, TPN,16kA,415V,50Hz capacity -09 Nos (b) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (c) LED indicating lamp (R,Y,B)- 01 Set of 3 (d) Aluminum Bus bar ( 3 phase and neutral) of capacity 400 amp and fixed inside the panel on best insulating material -01 Set
Supply, installation,testing & commisioning LT Panel board, outdoor type, suitable for operation on 415volts , AC 3 phase,4 wire ,50 Hz electric supply system, outer body made out of 3.15mm thick & inner shell made out 2.00mm thick CRCA sheet, side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated and conforming to IEC-61439 part I & II, The cubical shall have frame work, bottom & 45CM long four legs of size 50 X50 X 6mm Angle iron, aluminium main busbar of 1.5 time to the rating of incomer switch gear & for out going 1.5 times of the individual switch gear duly sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and control wiring with multistranded PVC insulated copper wire size not less then 1.5 Sqmm, complete comprising with following accessories all as specified and directed by the Engr-in-charge.(Note: Feeder piller box shall be mounted on PCC 1:2:4 type B-1 (with 20mm grade stone aggregate) foundation block of suitable size upto 40 cm above ground level as directed. The cost of the PCC foundation shall be deemed to be included in the unit rate quoted for the item) Location: LT panel '2' for 400 KVA Transformer at Bde area Incomer:- (a) MCCB 200 Amps ,TPN, 36kA,415V,50Hz capacity -01 Nos Outgoing:- (a) MCCB 100 Amps ,TPN, 25kA,415V,50Hz capacity -02 Nos (01 Stand by) (b) MCCB 63 Amps,TPN,16kA,415V,50Hz capacity -01 Nos (c) MCCB 25 Amps , TPN,16kA,415V,50Hz capacity -06 Nos (d) Multifunction meter to read Amp, Voltage, PF, frequency meter for 1100 Volts capacity- 1 Set (e) LED indicating lamp (R,Y,B)- 01 Set of 3 (f) Aluminum Bus bar ( 3 phase and neutral) of capacity 300 amp and fixed inside the panel on best insulating material -01 Set
M&L for Transformer plinth suitable for 100 to 400 KVA capacity for above ground level and fancing around the plinth with complete excavation, PCC, brick work, plaster and fencing with angle iron all as specified and directed by Engineer-in-Charge. ( Ref. as per CEPZ Drg No. -CEPZ/C-TD/002/13)
M & L for earthing complete with galvanized steel earth plate electrode 600 X600 X 6mm thickness not less than 6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below the normal ground level) with top edge of plate not less than 1.5 mtr below the normal ground level connected to galvanized iron wire 4mm dia by means of nuts bolts, washers,check nuts of GI steel all as shown in electric plate no 3 of SSR-2009 Part II, all as specified and indicated complete and including charcoal dust,salt etc and GI protection pipe medium grade 40mm and GI watering pipe 20mm light grade with funnel and wire mesh , 40mm thick pre-cast RCC M-15 (nominal mix) cover reinforced with XPM weight not less than 4kg /sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover , PCC M-15 (nominal Mix) pit, excavation and earth work in any type of soil and connected all as specified and as directed . (Note: On testing after completion of the result not found below 5 Ohms earth resistance is not obtained the earthing will be redone at no extra cost).
M & L for earthing complete with galvanized steel earth plate electrode 600 X600 X 6mm thickness not less than 6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below the normal ground level) with top edge of plate not less than 1.5 mtr below the normal ground level connected to galvanized iron strip 32 x 6mm Size by means of nuts bolts, washers,check nuts of GI steel all as shown in electric plate no 3 of SSR-2009 Part II, all as specified and indicated complete and including charcoal dust,salt etc and GI protection pipe medium grade 40mm and GI watering pipe 20mm light grade with funnel and wire mesh , 40mm thick pre-cast RCC M-15 (nominal mix) cover reinforced with XPM weight not less than 4kg /sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover , PCC M-15 (nominal Mix) pit, excavation and earth work in any type of soil and connected all as specified and as directed . (Note: On testing after completion of the result not found below 5 Ohms earth resistance is not obtained the earthing will be redone at no extra cost).
M & L for PCC 1:4:8 type D2, (using 40 mm gradded crushed stone aggregate) in foundations of HT pole complete all as specified and directed.
M & L for PCC 1:3:6 type C2, (using 40 mm gradded crushed stone aggregate) in foundations of stay assembly complete all as specified and directed.
M & L for PCC 1:2:4 type B-1, (using 20 mm gradded stone aggregate) for copying,including form work complete all as specified and directed.
Dismantling and taking down of old unserviceable LT panel complete all as specified and directed by Engineer-in-charge
Dismantling and taking down of old unserviceable bus bar panel complete all as specified and directed by Engineer-in-charge
Dismantling and taking down of old unserviceable cut fuse unit panel complete all as specified and directed by Engineer-in-charge
Dismantling and taking down of unserviceable LT cable 3.5/4 core 25 sqmm to 35 sqmm complete all as specified and directed by Engineer-in-charge
Dismantling and taking down of unserviceable service wire/ cable 3.5/4 core 10 sqmm to 16 sqmm complete all as specified and directed by Engineer-in-charge
Dismantling and taking down of unserviceable LT cable 2 core 10 sqmm to 16 sqmm complete all as specified and directed by Engineer-in-charge
Dismantling and taking down of old unserviceable house service bracket complete all as specified and directed by Engineer-in-charge
NOTE : Total amount of credit i.e, Rs 354879.00 as per Sch of credit shall be deducted from the total amount of BOQ to arrive at contract sum.
R D Bansal
JCC ENGINEERS PRIVATE LIMITED
MAHESH KUMAR SINGLA CONTRACTOR
Sant Construction Co.
SATISH AND CO
M/s GANJOO AND CO
BHARAT MULTITECH INDUSTRIES PVT LTD
NARINDER KUMAR SONS
Vardhman Airport Solutions Private Limited
bamral builder
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .