GE (ARMY) BARMER
MILITARY ENGINEER SERVICES GARRISON ENGINEER (ARMY) POST BOX NO-53, JALIPA MIL STN, BARMER-344 001
REPAIR MAINT OF STREET LIGHTS PERIMETER SECURITY LIGHTS AND REPAIRS TO DG SETS AMF PANELS AND CONNECTED ITEMS AT JALIPA MIL STN UNDER GE ARMY BARMER
2024_MES_658409_1
8762/E8
Open Tender
Civil Works
Item Rate
180 days
GE (ARMY) BARMER
As per tender documents
8 documents required · 8 mandatory
₹500
GE (ARMY) BARMER
₹78,000
30 Aug 2024
7 Jun 2024
10 Jul 2024
7 Jun 2024
5 Jul 2024
21 Jun 2024
Amount
M&L for maintenance and servicing of DG sets (monthly Inspection), of the following capacities including alternator, electric panel board connection to DG set for routine check (A check) of DG set for smooth functioning and carrying out maintanance as directed as specified for the following DG sets :- (a) 250 KVA Capacity-01 Nos (b) 100 KVA Capacity - 04 No (c) 82.5 KVA Capacity - 01 No (d) 62.5 KVA apacity - 04 No (e) 30 KVA Capacity - 01No (f) 20 KVA Capacity - 01 No
Note: (i) Checking engine oil level and topping up as and when required . Oil shall be measures and paid separately (ii) Checking and adjusting the belts for tension and replacement of belts. Note : Belt shall be measured and paid seperately (iii) Checking of air filter element all type. (iv) Checking of exhaust system for any leakage. (v) Draining of sediment/water from fuel filter and fuel tank. (vi) Cleaning of air cleaner element all type. (vii) Checking engine alternator coupling, mounting bolts and alignment. (viii) Tightening of all nuts and bolts in altenator terminal block. (ix) Checking of alternator carbon brush and connections in alternator. (x) Checking and tightening of all connection in DC control wiring. (xi) Checking of all radiator rubber hose, pipe clips and replacement if required. (xii) Checking and recording oil pressure, water and oil temperarute. (xiii) Checking anti vibration mounting and replacement if required. (xiv) Checking throttle linkage. (xv) Checking battery for cell test, electrolyte level, gravity and topping up to required level (xvi) Routine check / repair work of panel, switch, MCCB, main switch, all contactors, engine control unit. Replacement of Door hinges, locks etc also deemed to be inclusive in quoted rates. (xvii) Checking of AMF panel, all electrical connections etc. (xviii) Checking of earthing resistance. (xix) Cleaning of vegitation around the DG set up to 1.5 mtr area. (xx) Contractor shall employ skilled labour (FGM) for the above repairs and one company engineer/ technician for over all repairs once every in month.
M&L required for Inspection, maintenance and servicing of DG Sets of following Capacities including alternator, electric panel board connection to DG set for routine check (B - Check) of DG set for smooth functioning and carrying out maintanance complete all as directed and specified. Note: (i) B-Check once in six month OR 250 Hrs running of DG set whichever is earlier. (ii) B- Check of all DG sets ones shall be paid as one Job (iii) All spare parts required shall be measured and paid separately as supply only (a) 250 KVA Capacity-01 Nos (b) 100 KVA Capacity - 04 No (c) 82.5 KVA Capacity - 01 No (d) 62.5 KVA apacity - 04 No (e) 30 KVA Capacity - 01No (f) 20 KVA Capacity - 01 No
Note: (i) Repeat the activities of A Check including replacement of lubricating oil. (ii) Replacing lubricant oil filter element with 'O' ring (iii) Replacing fuel filter element (primary and secondary) (iv) Replacing coolant (For Radiator) (v) Replacing Governer oil. (vi) Coolent, Lubricant oil shall be measured and paid seperately under relevant items (vii) Contractor shall employ skilled labour (FGM) for the above repairs and one company engineer/technician for over all repairs (viii) Replacing water body assembly. (ix) Replacing water separater. (x) Cleaning of Radiator with chemicals and replacement of radiator filter . (xi) Replacement of by pass filter. (xii) Checking of all radiator rubber hose and replacement if required. (xiii) Checking and recording oil pressure, water and oil temperarute (xiv) Checking anti vibration mounting and replacement if required. (xv) Checking throttle linkage (xvi) Checking battery for cell test, electrolyte level, gravity and topping up to required level (xvii) Routine check / repair work of panel, switch, MCCB, main switch, all contactors, engine control unit. Replacement of Door hinges, locks etc also deemed to be inclusive in quoted rates. (xviii) Checking of AMF panel, all electrical connections etc. (xix) Checking of earthing resistance (xx) Cleaning of vegitation around the DG set up to 1.5 mtr area.
Supply only Radiator Coolent complete all as specified and directed by Engineer in charge.
Supply only Diesel/ Fuel filter (Primery&Secondary) for 25 to 100 KVA DG Set.
Supply only Diesel/ Fuel filter (Primery&Secondary) for 250 KVA DG Set.
Supply only Fan belt suitable for DG sets upto 250KVA capacity.
Supply only defective fuel injectors suitable for DG sets upto 250KVA capacity.
Supply only Engine oil / Lube filter suitable for 20 KVA to 100 KVA DG Set
Supply only Engine oil /Lube filter suitable for 250 KVA DG Set
Supply only Air cleaner elements inner and outer suitable for 20 KVA to 100 KVA DG Sets
Supply only Air cleaner elements inner and outer suitable for 250 KVA DG Set
Material and labour for replacement of lub oil pump suitable upto 250 KVA DG Set complete all as specified and directed by Engr-in-Charge.
Supply & fixing in replacement Diesel pipe set flexible suitable upto 250KVA DG Set incl benjo bolts, copper washers complete all as specified and as directed by Engr-in-Charge.
Supply only cotton waste for daily use at power house for cleaning of the DG sets, pump motors complete all as specified and directed by Engineer in charge.
M&L for engine oil, multi grade 15W40 complete all as specified and directed.
Dismantling the radiator and fan assembly from the engine for cleaning of copper tubes and cooling fins by using descaling solution, soldering, patch work if any leakage including transporting to workshop for repair and bringing back to site upto 250 KVA complete all as specified and directed.
S&F 12V solenoid coil suitable for DG set upto 100KVA capacity of existing make & model complete all as specified and directed.
M&L for dismantling self starter 12 V of DG set for repairing the starter by replacing carbon brushes, brush holder, bearings, solenoid coil, replacement of burnt aremeture, rewinding of Fd coils, replace of pinion gears etc, complete servicing and refixing after repair, testing/commissioning complete for DG Set of any capacity complete all as specified and directed.
Opening of AMF Panel, Cleaning of dust using blower, Checking/Detecting, Removal of Faults, Re-wiring of old u/s wiring & Testing of Control Wiring complete as reqd and closing of AMF Panel after replacement of u/s parts and testing complete all as specified and directed.
Supply & Fixing in repair of Indicating Light, 240V AC, LED Type Red, Yellow, Blue complete all as specified and directed.
Supply & Fixing in repair of Digital DG Set Controller as per existing model complete all as specified and directed.
Supply & Fixing in repair of Ammeter Digital Type of existing model complete all as specified and directed.
Supply & Fixing in repair of Voltmeter Digital Type of existing model complete all as specified and directed.
Supply & Fixing in repair of Self Carbon Bush suitable for DG Set complete all as specified and directed.
Supply & Fixing in repair of Oil Pressure Gauge of existing model complete all as specified and directed.
Supply & Fixing in repair of Push switch STOP EMERGENCY complete all as specified and directed.
Supply & Fixing in repair of Battery lead (using multistranded copper conductor with end terminal lugs) complete all as specified and directed.
Supply & Fixing in repair of Current Transformer (200/5) of existing model complete all as specified and directed.
M & L for sevicing and calibration of governor unit in-si-tu including replacement of worn out parts if any and testing it for a maximum droop of 20% complete all as specified and as directed for 250 KVA DG set complete all as specified and directed.
All as per srl item No 30 above but but 100 KVA.
All as per srl item No 30 above but but 82.5/62.5 KVA .
All as per srl item No 30 above but but 20/30 KVA .
Supply and fixing in replacement Brass, Battery terminals complete all as specified and directed.
M & L for repair and servicing of 100 KVA PT pump assembly and injectors by replacing the unserviceable parts like centre shaft, loading spring, relief valve-2 Nos bearings, governor barrels & plunger-1Set O-ring kits,gasket kit,injector plunger & barrel -6Nos,ball check -6Nos and calibration and phasing of injectors and FIP in test bench and reassembling etc complete all as specified and directed.
All as per srl item No 35 above but 82.5 KVA .
All as per srl item No 35 above but 62.5 KVA .
All as per srl item No 35 above but 30/20 KVA .
M & L in replacement earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to and including galvanized earth wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion and excavation and earth work in any type of soil, PCC 1:3:6 type C1 in chamber, precast RCC cover 50mm thick in cement concrete 1:2:4 type B1, reinforced with welded steel wire fabric or XPM (Weight not less than 4 Kg/Sqm) with cast iron frame, funnel with wire mesh, 20mm bore GI pipe medium grade watering pipe, lugs, 40mm bore GI pipe medium grade protection pipe upto 7.5m. NOTE : Item includes the cost of earth lead and GI protection pipe upto 7.5m. GI wire beyond 7.5m shall be measured and paid for separately.
S & F in repair Changeover switch 200 Amps 415 Volt with sheet metal enclosure, side handle operated complete all as specified and directed.
S & F in repair Changeover switch 100 Amps 415 Volt with sheet metal enclosure side handle operated complete all as specified and directed.
Supply and Fixing in replacement MCCBs 415 V, 50 Hz, Four pole, fixed thermal & fixed magnetic setting, rupturing capacity 25 kA of rating 160 Amps complete all as specified and directed. Make Havells/L&T/ Legrand or eqvt.
Supply and Fixing in replacement MCCBs 415 V, 50 Hz, Four pole, fixed thermal & fixed magnetic setting, rupturing capacity 25 kA of rating 125 Amps complete all as specified and directed. Make Havells/L&T/ Legrand or eqvt.
Supply and Fixing in replacement MCCBs 415 V, 50 Hz, Four pole, fixed thermal & fixed magnetic setting, rupturing capacity 25 kA of rating 100 Amps complete all as specified and directed. Make Havells/L&T/ Legrand or eqvt.
Removing the U/S battery and supply and fix moulded PVC body low maintanence lead acid battery 12 volts 180 AH Make: Exide/Amaron or its eqvt.
Removing the U/S battery and supply and fix moulded PVC body low maintanence lead acid battery 12 volts 150 AH Make: Exide/Amaron or its eqvt.
Repairs to LED street light / of any make / type and capacity by replacing unserviceable parts including replacement of wornout connecting wires as per existing size of conductor and taking down fittings from the pole and refixing in position and testing complete as required and as directed by the Engr-in-Charge. Note :-(i) Unserviceable parts required to be replaced with new one shall be measured and paid separately as "Supply only" against respective items of this Schedule. (ii) Cost of replacement of worn out wire of the fittings and connections as per existing size of conductor of the each fittings is deemed to be included in unit rate quoted.
S&F in replacement 2 core 10 Sqmm weather proof, PVC insulated and PVC sheathed multi stranded aluminium conductor cable, flat type 1100 volts as in service connection etc complete all as specified and directed.
Supply only Driver for LED 25 watt complete. (Make-Bajaj/Havell's/ Crompton )
Supply only Driver for LED 45 watt complete. (Make-Bajaj/Havell's/ Crompton )
Supply only Driver for LED 60 watt complete. (Make-Bajaj/Havell's/ Crompton )
Supply only Surge protector for LED 25 to 90 watt complete. (Make-Bajaj/Havell's/ Crompton )
Repairs to LED Integrated Solar light of make Axxon Tech and capacity12 watt to 24 watt by replacing unserviceable parts including replacement of wornout control wires as per existing size of conductor and taking down fittings from the pole and refixing in position and testing complete as required and as directed by the Engr-in-Charge. Note :-(i) Unserviceable parts required to be replaced with new one shall be measured and paid separately as "Supply only" against respective items of this Schedule. (ii) Cost of replacement of worn out wire of the fittings and connections as per existing size of conductor of the each fittings is deemed to be included in unit rate quoted.
Supply only solar charge controller 5 Amp for 12 watt to 16 watt for integrated solar street light Make: Axxon-12WSCC or techno commercially equivalent in Philips/ C & S
Supply only solar charge controller 10 Amp for 24 watt for integrated solar street light Make: Axxon-24WSCC or techno commercially equivalent in Philips/ C & S
Supply only PIR motion sensor for 170uA for solar street light 12 watt to 24 watt complete
Supply only Lithium Ion Battery 11.1V/15.4 AH of dimension 210 x70 x 40 mm) for 12 watt
Supply only Lithium Ion Battery 11.1V/19.8 AH of dimension 210 x70 x 40 mm) for 16 watt
Supply only Lithium Ion Battery 11.1V/ 28.6 AH of dimension 210 x70 x 40 mm) for 24 watt
Supply and fix in repair energy efficient LED street light fitting of 45 watt made up of pressure die cast aluminium housing with toughened glass and high power LEDS with secondary optics, efficacy 110/120 LPW, IP 66 protection aerodynamically designed for all weather conditions with efficient thermal management including 10 KV SPD complete all as directed by Engineer in Charge. Model: RAPTOR NEO Cat No : TRP-409-45-57-SL-GL-NSG of make CG or techno commercially equivalent model of Havells, Bajaj, Wipro, Halonix
Supply and fix in repair energy efficient LED street light fitting of 60 watt made up of pressure die cast aluminium housing with toughened glass and high power LEDS with secondary optics, efficacy 110/120 LPW, IP 66 protection aerodynamically designed for all weather conditions with efficient thermal management including 10 KV SPD complete all as directed by Engineer in Charge. Model: RAPTOR NEO Cat No : TRP-409-60-57-SL-GL-NSG of make CG or techno commercially equivalent model of Havells, Bajaj, Wipro, Halonix
Supply and fix in repair energy efficient LED street light fitting of 90 watt made up of pressure die cast aluminium housing with toughened glass and high power LEDS with secondary optics, efficacy 110/120 LPW, IP 66 protection aerodynamically designed for all weather conditions with efficient thermal management including 10 KV SPD complete all as directed by Engineer in Charge. Model: RAPTOR NEO Cat No : TRP-409-90-57-SL-GL-NSG of make CG or techno commercially equivalent model of Havells, Bajaj, Wipro, Halonix
Supply and fixing energy efficient Lithium based Energy Efficient Integrated Solar Street Light of 15/16Watt, encases with Monocrystalline Solar PV Panel of 30/35Wp , Lithium Battery 11.1/12.8V, 19.8AH with inbuilt BMS, IP 65, High brightness W-LED(160-180lm/watt) lamp with Aluminum reflector for better light distribution , CRI >70, Color Temperature 5700K - 6500K, Microcontroller based charge controller cum driver, automatic dimming function ( first four hours at full brightness & rest of the time at lower light level with PIR Motion Sensor), Dusk to Dawn Operation, suitable to working temperature: (-) 10C to (+)55C, weight not more than 8-10kg with adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protections: Short Circuit, overload, Reverse polarity and battery protections.Make:- Wipro/Crompton/ Havells.
Supply and fix in repair LED post top lantern (garden light) with B-22 base lamp holder and LED bulb of 9W aesthetically designed landscape and diffused lighting mounted on and including 1.5 mtr length GI pipe of 50 mm dia duly black painted and necessary arrangement for cable connection and foundation complete all as specified and as directed.
Supply and lay in repair LT service cable 6 sqmm 2 core inside PVC conduit 20 mm dia medium grade for landscape lighting/ garden lighting inside trench or on wall/floor complete all as specified and as directed. Note: The rate quoted must be inclusive of laying the cables in trench at max 10 cm depth or mounting on floor/wall
S&F Integral compact wide beam LED flood light luminiaire with die cast aluminium alloy housing with IP 66 protection, tampered protective toughened glass 5mm thick, thermal shock impact resistant cover, epoxy black powder coated finish, high purity pre-anodised specular aluminium sheet reflector, with silver painted contacts suitable for 1x100 Watts LED and connection with two runs of 2.5 Sqmm multi-stranded, copper flexible wire including taking down old unserviceable one and testing complete as specified and as directed by the Engineer-in-Charge. Make : Cat No LHEPCZU7PA6J100 Havells or techno commercially equivalent in Wipro and Crompton
Supply and fix 60 W LED inverter street light luminaire with the following functions (a) Real time clock for automatic ON -OFF and dimming option as 100% at 1800 hrs and then 30% at 2300 hrs, 50% at 0400 hrs and switch off at 0600 hrs (b) In built lithium ion battery 3.7 V for 1.5 to 02 hrs power back up for operation at 15-20% of rated wattage in case of power failure with red indication for 230 V AC available and green blinking for battery charging and green stable for for battery fully charged. (c) Versatile pressure die cast alluminium alloy housing with specially designed integral cooling fins top maintainable , clear toughened glass and high efficient secondary lens with IP 66 protection and isolated compartment for driver and control gear. (d) LM 80 certified LED with 50000 burning hrs and system lumen efficiency 110 lm/W (e) Open and short circuit protection, reverse polarity protection , high voltage cut off at 300 ± 10 V and 5 KV internal surge protection, operating voltage 140 V to 270 V and operating temperature -10 ℃ to 50 ℃ Make Halonix Cat part No HLSLD-06-60-CWL-INV-DIMM-RTC-R or techno commercially equivalent make in Bajaj/Havells, Wipro/Crompton
Supply and fix GI pipe bracket for street light fittings made out of 32 mm dia GI pipe light grade 1.5 mtr long bent to required angle/ shape with and including necessary clamps, nuts, bolts, & washers of suitable size all as directed by Engineer - in - Charge.
S & F PVC weather proof loop-in loop-out box with 4 pole terminal block mounted on porcelain or bakelite and MCB SP 06 Amps for controlling including necessary clamps for mounting on pole etc complete all as specified and directed. Make: Sintex Cat Part No-GSJB 2014 or techno commercially equivalent.
M&L PVC insulated twin core 1100 volts grade 2.5 sqmm copper cable incl connecting up with loop in box to security light fitting complete all as specified and as directed.
S&F Rigid non-metallic PVC conduit 20mm dia fixed to pole inclusive of all fixing accessories such as MS clamp,nuts,bolts etc complete all as specified and as directed
Supply & fix in repair 3-pole contactor suitable for street light controlling with nominal current rating 32 Amp 415 V AC, Make: Indoasian cat part No 850047 or eqv in Legrand/L&T/Havells/Schneider
Supply and fix automatic Street light timer nature switch using Infrared sensor tecnology based, three phase 5-8 KW with 03 Nos 16 Amps Contactor rating and three Nos Outgoing MCB of 20 Amp, enclosed in a pole /wall mounted rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure (with hinged lid) conforming to IP66 protection class 2. The circuit should also have provision for manual operation (i.e. sensor By-pass operation) and nature switch operation shall be based on natural light lux level i.e. automatic switching ON at Dusk (≤60 lux) and switching OFF at Dawn (≥10 lux) including necessary wiring complete all as specified and as directed. Make Healer Enterprises Model Swadeep-66-5KW3P with Hensel enclosure confirming IP 66 or techno commercially equivalent make in Havells/Indoasian
Excavating in trenches, n.exc. 1.5 wide and n.exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sqm on plan and n exc 1.5 m in depth and getting out soft/loose soil all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil all as specified and as directed.
Removing excavated material/surplus soil not exceeding 50 meters and depositing where directed at a level not exceeding 1.5 meter above the starting point.
Material and labour for sand cushioning for under ground cables, spread in trenches, river sand including cleaning, spreading levelling, punning for laying/cushioning of cable all as directed. with layer of 8 cm deep before laying cable and 15 cm depth after laying and stretching the cable complete all as directed. Note: For the Purpose of payment puned thickness shall be measured.
M & L for Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1, flat size 250 mm x 150 mm x 40 mm and abutting each other with gap between adjacent precast concrete cable cover not exceeding 10 mm punned sand over underground cables for protection complete all as specified and directed.
Material and labour for PCC 1:3:6 type C1 using 20 mm graded stone aggegrate in coping/bed places and the like including weathering slightly rounded on chamfered angles and with necessary form work with fair finished surface complete all as specified and directed.
M&L for PCC 1:3:6 type C1 using (20 mm graded stone aggregate) for make good to road surface , hard standing etc complete all as specified and directed.
Supply & Fix GI pipe light grade 50 mm dia for cable protection laid in trenches under road/culvert etc complete all as specified and as directed.
Supply & Fix GI pipe light grade 50 mm for cable protection fixed to poles/bldg incl two Nos MS clamps made to shape out of 25 x 3mm MS flat and painting incl bolt, nut, washer etc complete all as specified and directed.
Supply and lay XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 Volt grade with stranded aluminium conductor of size 10 sq mm 2 core complete all as specified and directed.
All as per srl item No 85 above but 16 Sqmm, 2 core complete all as specified.
All as per srl item No 85 above but 10 Sqmm, 4 core complete all as specified
Repairs to High Mast light fittings (60 to 100 watts, 230/240 volts of any make) at site including taking down existing fittings from pole (up to16 Mtr hight) and refixing the same in position by means of crane/ manually after replacement of unserviceable/defective part(s) of the fittings s as required to make the fittings in smooth serviceable condition and testing complete and as directed by the Engr-in- Charge.
M/s Malinath Electricals
Devi Engineeing
PANKAJ ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .