Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹89.6 LAccepted-AOC RH NO 06 KARMA KSHETRA HOUSING SOCIETY SECTOR 29 PRADHIKARAN RAVET POST DEHU ROAD 412 101 | NA | NA | 412101 | ₹89.6 L Quoted ₹89.8 L | L1 | Accepted-AOC Bidder quoted L1 rates |
| 2 | L2₹92.7 L+₹2.9 L (3.28%)Rejected-Finance 33 CHANDASI HOUSE LANE NO 11 S K PURAM ARYA SAMAJ MANDIR ROAD RPS MORE BAILEY ROAD DANAPUR PATNA BIHAR 801503 | PATNA | PATNA | BIHAR | 801503 | ₹92.7 L+₹2.9 L (3.28%) | L2 | Rejected-Finance Bidder not quoted L1 rates |
| 3 | L3₹95.1 L+₹5.4 L (6.00%)Rejected-Finance 54 10 SHANTI NAGAR NEAR SHINDE CHATRI WANAVADI PUNE 411040 | PUNE | MAHARASHTRA | 411040 | ₹95.1 L+₹5.4 L (6.00%) | L3 | Rejected-Finance Bidder not quoted L1 rates |
| 4 | L4₹97.9 L+₹8.2 L (9.10%)Rejected-Finance HIMACHAL BUILDING SHOP NO 10 CD BARFYWALA ROAD JUHU LANE ANDHERI W MUMBAI 400058 | MUMBAI SUBURBAN | MAHARASHTRA | 400058 | ₹97.9 L+₹8.2 L (9.10%) | L4 | Rejected-Finance Bidder not quoted L1 rates |
| 5 | L5₹98.2 L+₹8.5 L (9.43%)Rejected-Finance 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | ₹98.2 L+₹8.5 L (9.43%) | L5 | Rejected-Finance Bidder not quoted L1 rates |
| Sl No | Description | Qty | Unit | United Sales Corporation L10 | Apurva constructions L6 | UNIQUE ENGINEERS L7 | M/s.BAJRANG CONSTRUCTION L3 | Prasur Electricals & Engineering Co. L9 | Shri Sai Electricals L1 | Vijaypower Generators Limited L5 | SBS Enterprises L8 | M/s PIONEER CONTRACTORS L4 | Roy and Sons Infrastructures L2 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supplying, installing, testing and commissioning, factory assembled silent Diesel Engine driven generator set, fully wired alternator AC, to give an out put of 250 kVA continuously rating at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz ± 1% supply, 1500 RPM, CPCB IV+ regulation, directly coupled with diesel engine liquid cooled turbo charged after cooled mounted on common base frame complete with floor mounting fuel tank (with fuel line & accessories, vibration damper pads, microprocessor based genset monitioring controller Engine Safeties & Protections Battery With Leads , including termination and connection of cable with gland and lugs and comprising of following :-
LOCATION :
(a) NEW CARDIAC CATHERISATION LAB (CCL) AT AICTS PUNE - 01 No.
(b) OT, ALC PUNE - 01 No. | 2 | EACH JOB | 33,00,000 ₹66,00,000 | 28,00,000 ₹56,00,000 | 30,00,000 ₹60,00,000 | 26,75,000 ₹53,50,000 | 28,49,500 ₹56,99,000 | 24,95,000 ₹49,90,000 Lowest | 28,64,001 ₹57,28,002 | 28,77,000 ₹57,54,000 | 27,00,000 ₹54,00,000 | 26,15,000 ₹52,30,000 |
| 1.01(A) Diesel Engine : Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500 RPM 4 stroke, under NTP conditions of BS 5514 and conforming to IS 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories, Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of classG-3, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/ flexible coupling and coupling guard complete. (a) Radiator with blower fan or heat exchanger with guard. (b) Pipe coupling for engine cooling system piping. (c ) Corrosion inhibitor coolant (d) Paper element filters (i) Fuel filter (ii) Lube oil filter (iii) By pass (e) Fly wheel housing and fly wheel to suit alternator. (f) Engine bearing mechanism in fly wheel housing. (g) Shut off coil with safety for LLOP/HWT/over speed. (h) Dry type air cleaners and vacuum indicators. (j) Residential silencers. (k) Stainless steel exhaust flexible bellows. (l) BLANK. (m) Battery charging alternator. | |||||||||||||
| 1.02(B) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:- (i) Battery. -as per manuactrure specified. (ii) Water temperature. (iii) Lubricating oil pressure. (iv) Engine speed -1500 Rpm (v) Engine hours (vi) Frequency. (vii) Voltage. (w) Safety control (Trip and indication). (i) High water temperature (ii) Low lube oil temperature (iii) Overspeed stop (C) Base frame : Sturdy, fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer's design alonwith AVM pads. (D) Battery : as per manufacturer specified with leads & terminals. (E) Alternator : Suitable rated 250 kVA, 0.8 PF, 415 Volts, 3 Phase, 4 Wire, 50 Hz at 1500 RPM, self excited and self regulated with AVR brushles, screen protected, drip proof, insulation class-H, IP -23, voltage regulation grade - VG 3 self ventilated and conforming to BS : 5000 / IS : 4722 suitable for engine as mentioned here-in before, conformig to IS: 13364 (Part-1) (F) Acoustic Enclosure : Specially design for CPCB norms M&L for acoustic enclosure for the above 250 kVA DG set to reduce noise level to 75 dB measured at 1.0 meter distance for audiable frequencies as per guide of Central Pollution Control Board and manufacturer's specification and comprising of following from authorised GOEMs of Gen Set manufacturer's specified . | |||||||||||||
| 2.00 | Supply and installation, testing of AMF panel outdoor type suitable for AMF 250 kva with factory made type panel weather proof, vermin proof, fully ventilated both side opening and fabricated out of 3.00 mm thick crca sheet & mounting channel 75 mm having bus bar of aluminum 600 Amps capacity, three phase and one neutral fixed on insulator and bus bar insulated by colored heat shrinkable sleeve & housed in specified compartment both side open able. Including powder coating internally externally the entire steel surfaces. All the cover shall have with suitable locking arrangements, fully internally wired with suitable size of thimbles. Incoming/outgoing internal connection with pvc insulated pvc sheathed multi stranded copper wire of suitable size all as directed The panel shall be provided with 04 Nos 50mm x 50mm x 6mm thick angle iron suppons of not less than each 0.6 mtr height duly painted with anti cormsive black paint and grouted on floor/well atc and suitable fixing amanament as per she requirement connection to the existing earthing., including PCC 1:3:6 & comprising of following :-
LOCATION :
(a) NEW CARDIAC CATHERISATION LAB (CCL) AT AICTS PUNE - 01 No.
(b) OT, ALC PUNE - 01 No. | 2 | EACH JOB | 3,75,000 ₹7,50,000 | 2,50,000 ₹5,00,000 | 2,74,500 ₹5,49,000 | 1,95,000 ₹3,90,000 | 4,62,500 ₹9,25,000 | 3,55,000 ₹7,10,000 | 2,15,100 ₹4,30,200 | 3,12,000 ₹6,24,000 | 3,03,000 ₹6,06,000 | 1,50,000 ₹3,00,000 Lowest |
| 2.01Under voltage relay 415v AC for main - 1 No Under voltage relay 415 v AC for DG - 1 No AC timer 230 volt, 2 NO. +2 NC - 1 No DC timer 24 Volt - 1 No Control mcb sp 16 A - As required Control mcb sp 6 A - As required Automatic battery charger 24 volts- 1 No Led indicating light for main & DG - 6 Nos. Led indicating light for main & Gen. On - 2 Nos. Led indicating light for battery charger - 1 No. VAF Meter - 2 Nos AMF Controler 3 Phase 4 wire -1 No Volt meter selector switch - 1 No. Amp meter selector switch - 1 No. 500/5 Amp - 3 Nos. DC volt meter 15/30 V - 1 No. DC amp meter 0-15 A - 1 No. Trickle / boost switch - 1 No. Auto / manual switch - 1 No. Push button start & stop with elements - 2 Nos Power contactor 400 Amp 3 pole 415V for DG - 1 No Power contactor 400 Amp 3 pole 415V for main - 1 No MCCB 400 Amp 35 ka 3 pole for main & dg supply - 2 Nos Control relay -1 set Over load relay 2.5-4 A - 1 No. Bus bar 600 A, 3 strips & n/l 300 A . Aluminium - 1 set | |||||||||||||
| 3.00 | Supplying, installing, testing and commissioning, factory assembled silent Diesel Engine driven generator set, fully wired alternator AC, to give an out put of 160 kVA continuously rating at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz ± 1% supply, 1500 RPM,CPCB IV+ regulation, directly coupled with diesel engine liquid cooled mounted on common base frame complete with floor mounting fuel tank (service tank) of minimum capacity 385 ltrs with fuel line & accessories, vibration damper pads, Standard Control Panel With Controller PS0602, Engine Safeties & Protections Battery With Leads With dept tank capacity 60 Ltrs, including termination of cable with gland and lugs and comprising of following :- | 1 | EACH JOB | 23,75,000 ₹23,75,000 | 20,00,000 ₹20,00,000 | 21,42,500 ₹21,42,500 | 21,75,000 ₹21,75,000 | 20,95,000 ₹20,95,000 | 18,25,000 ₹18,25,000 Lowest | 21,28,002 ₹21,28,002 | 25,40,000 ₹25,40,000 | 19,44,000 ₹19,44,000 | 21,70,000 ₹21,70,000 |
| 3.01(A) Diesel Engine : Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500 RPM 4 stroke, 6 cylinderunder NTP conditions of BS 5514 and conforming to IS 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories, Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/ flexible coupling and coupling guard complete. (a) Radiator with blower fan or heat exchanger with guard. (b) Pipe coupling for engine cooling system piping. (c) Corrosion inhibitor coolant (d) Paper element filters (i) Fuel filter (ii) Lube oil filter (iii) By pass (e) Fly wheel housing and fly wheel to suit alternator. (f) Engine bearing mechanism in fly wheel housing. (g) Shut off coil with safety for LLOP/HWT/over speed. (h) Dry type air cleaners and vacuum indicators. (j) Residential silencers. (k) Stainless steel exhaust flexible bellows. (l) BLANK. (m) Battery charging alternator. | |||||||||||||
| 3.02(B) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:- (i) Battery as per manufacturer specified. (ii) Water temperature. (iii) Lubricating oil pressure. (iv) Engine speed -1500 Rpm (v) Engine hours (vi) Frequency. (vii) Voltage. (w) Safety control (Trip and indication). (i) High water temperature (ii) Low lube oil temperature (iii) Overspeed stop (C) Base frame : Sturdy, fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer's design alonwith AVM pads. (D) Battery : as per manufacturer specified with leads & terminals. | |||||||||||||
| 3.03(E) Alternator : Suitable rated 160 kVA, 0.8 PF, 415 Volts, 3 Phase, 4 Wire, 50 Hz at 1500 RPM, self excited and self regulated with AVR brushles, screen protected, drip proof, insulation class-H, IP -23, voltage regulation grade - VG 3 self ventilated and conforming to BS : 5000 / IS : 4722 suitable for engine as mentioned here-in before, conformig to IS: 13364 (Part-1) (F) Acoustic Enclosure : M&L for acoustic enclosure for the above 160 kVA DG set to reduce noise level to 75 dB measured at 1.0 meter distance for audiable frequencies as per guide of Central Pollution Control Board and manufacturer's specification and comprising of following from authorised GOEMs of Gen Set manufacturer's specified. | |||||||||||||
| 4.00 | Supplying, installing, testing and commissioning imdoor CPRI approved AMF Control panel of capcity 160 KVA factory fabricated cubical type, free standing, floor mounted, outdoor type, IP-52, with rotary handle, provided with removable rear panels & hinged front panel for easy accessibility, fabricated out of not less than 2.0 mm thick CRCA sheet with partition and switch enclosure door 1.6 mm including two coats of powder coated paint over a coat of red oxide primer with MS angle stand of size 50x50x6mm and shall be mounted on including necessary grouting in PCC 1:3:6 type C-1 by using 20 mm graded stone aggregate completed with legs 30 cm in ground in PCC and 40 cm above ground and termination of cable with gland and lugs comprising of following :-
LOCATION :
MAINT PUMP HOUSE AT AICTS PUNE - 01 No. | 1 | EACH JOB | 2,75,000 ₹2,75,000 | 2,00,000 ₹2,00,000 | 2,25,000 ₹2,25,000 | 1,75,000 ₹1,75,000 | 3,17,500 ₹3,17,500 | 2,95,000 ₹2,95,000 | 1,68,000 ₹1,68,000 | 2,50,000 ₹2,50,000 | 2,37,500 ₹2,37,500 | 90,000 ₹90,000 Lowest |
Tender Value
₹99.8 L
EMD Value
₹1.8 L
Closing Date
6 Jul 2026, 6:00 pmClosed
COMMANDER WORKS ENGINEER PUNE - 411001
HEADQUARTERS COMMANDER WORKS ENGINEERS GEN CARIAPPA MARG, PUNE-411 001
85968 PROVN OF STANDBY DG SET WITH ALLIED WORK FOR NEW CCL AND MAIN PUMP HOUSE AT AICTS AND SPECIAL REPAIR / RENEWAL OF 250 KVA DG SET IN PLACE OF BER 125 KV DG SET INCLUDING OTHER CONNECTED ACCESSORIES AT ALC OT UNDER AGE E/M-I OF GE (SOUTH) PUNE
2026_MES_773533_1
85968 CWE PUNE
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
GE (SOUTH) PUNE
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹1,000
GE (SOUTH)
₹1.8 L
Yes
29 Aug 2026
19 Jun 2026
11 Jul 2026
19 Jun 2026
6 Jul 2026
29 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, installing, testing and commissioning, factory assembled silent Diesel Engine driven generator set, fully wired alternator AC, to give an out put of 250 kVA continuously rating at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz ± 1% supply, 1500 RPM, CPCB IV+ regulation, directly coupled with diesel engine liquid cooled turbo charged after cooled mounted on common base frame complete with floor mounting fuel tank (with fuel line & accessories, vibration damper pads, microprocessor based genset monitioring controller Engine Safeties & Protections Battery With Leads , including termination and connection of cable with gland and lugs and comprising of following :-
LOCATION :
(a) NEW CARDIAC CATHERISATION LAB (CCL) AT AICTS PUNE - 01 No.
(b) OT, ALC PUNE - 01 No. | 2 | EACH JOB | - | - |
| - | (A) Diesel Engine : Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500 RPM 4 stroke, under NTP conditions of BS 5514 and conforming to IS 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories, Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of classG-3, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/ flexible coupling and coupling guard complete.
(a) Radiator with blower fan or heat exchanger with guard.
(b) Pipe coupling for engine cooling system piping.
(c ) Corrosion inhibitor coolant
(d) Paper element filters
(i) Fuel filter
(ii) Lube oil filter
(iii) By pass
(e) Fly wheel housing and fly wheel to suit alternator.
(f) Engine bearing mechanism in fly wheel housing.
(g) Shut off coil with safety for LLOP/HWT/over speed.
(h) Dry type air cleaners and vacuum indicators.
(j) Residential silencers.
(k) Stainless steel exhaust flexible bellows.
(l) BLANK.
(m) Battery charging alternator. | - | - | - | - |
| - | (B) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:-
(i) Battery. -as per manuactrure specified.
(ii) Water temperature.
(iii) Lubricating oil pressure.
(iv) Engine speed -1500 Rpm
(v) Engine hours
(vi) Frequency.
(vii) Voltage.
(w) Safety control (Trip and indication).
(i) High water temperature
(ii) Low lube oil temperature
(iii) Overspeed stop
(C) Base frame : Sturdy, fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer's design alonwith AVM pads.
(D) Battery : as per manufacturer specified with leads & terminals.
(E) Alternator : Suitable rated 250 kVA, 0.8 PF, 415 Volts, 3 Phase, 4 Wire, 50 Hz at 1500 RPM, self excited and self regulated with AVR brushles, screen protected, drip proof, insulation class-H, IP -23, voltage regulation grade - VG 3 self ventilated and conforming to BS : 5000 / IS : 4722 suitable for engine as mentioned here-in before, conformig to IS: 13364 (Part-1)
(F) Acoustic Enclosure : Specially design for CPCB norms M&L for acoustic enclosure for the above 250 kVA DG set to reduce noise level to 75 dB measured at 1.0 meter distance for audiable frequencies as per guide of Central Pollution Control Board and manufacturer's specification and comprising of following from authorised GOEMs of Gen Set manufacturer's specified . | - | - | - | - |
| - | Supply and installation, testing of AMF panel outdoor type suitable for AMF 250 kva with factory made type panel weather proof, vermin proof, fully ventilated both side opening and fabricated out of 3.00 mm thick crca sheet & mounting channel 75 mm having bus bar of aluminum 600 Amps capacity, three phase and one neutral fixed on insulator and bus bar insulated by colored heat shrinkable sleeve & housed in specified compartment both side open able. Including powder coating internally externally the entire steel surfaces. All the cover shall have with suitable locking arrangements, fully internally wired with suitable size of thimbles. Incoming/outgoing internal connection with pvc insulated pvc sheathed multi stranded copper wire of suitable size all as directed The panel shall be provided with 04 Nos 50mm x 50mm x 6mm thick angle iron suppons of not less than each 0.6 mtr height duly painted with anti cormsive black paint and grouted on floor/well atc and suitable fixing amanament as per she requirement connection to the existing earthing., including PCC 1:3:6 & comprising of following :-
LOCATION :
(a) NEW CARDIAC CATHERISATION LAB (CCL) AT AICTS PUNE - 01 No.
(b) OT, ALC PUNE - 01 No. | 2 | EACH JOB | - | - |
| - | Under voltage relay 415v AC for main - 1 No
Under voltage relay 415 v AC for DG - 1 No
AC timer 230 volt, 2 NO. +2 NC - 1 No
DC timer 24 Volt - 1 No
Control mcb sp 16 A - As required
Control mcb sp 6 A - As required
Automatic battery charger 24 volts- 1 No
Led indicating light for main & DG - 6 Nos.
Led indicating light for main & Gen. On - 2 Nos.
Led indicating light for battery charger - 1 No.
VAF Meter - 2 Nos
AMF Controler 3 Phase 4 wire -1 No
Volt meter selector switch - 1 No.
Amp meter selector switch - 1 No.
500/5 Amp - 3 Nos.
DC volt meter 15/30 V - 1 No.
DC amp meter 0-15 A - 1 No.
Trickle / boost switch - 1 No.
Auto / manual switch - 1 No.
Push button start & stop with elements - 2 Nos
Power contactor 400 Amp 3 pole 415V for DG - 1 No
Power contactor 400 Amp 3 pole 415V for main - 1 No
MCCB 400 Amp 35 ka 3 pole for main & dg supply - 2 Nos
Control relay -1 set
Over load relay 2.5-4 A - 1 No.
Bus bar 600 A, 3 strips & n/l 300 A . Aluminium - 1 set | - | - | - | - |
| - | Supplying, installing, testing and commissioning, factory assembled silent Diesel Engine driven generator set, fully wired alternator AC, to give an out put of 160 kVA continuously rating at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz ± 1% supply, 1500 RPM,CPCB IV+ regulation, directly coupled with diesel engine liquid cooled mounted on common base frame complete with floor mounting fuel tank (service tank) of minimum capacity 385 ltrs with fuel line & accessories, vibration damper pads, Standard Control Panel With Controller PS0602, Engine Safeties & Protections Battery With Leads With dept tank capacity 60 Ltrs, including termination of cable with gland and lugs and comprising of following :- | 1 | EACH JOB | - | - |
| - | (A) Diesel Engine : Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500 RPM 4 stroke, 6 cylinderunder NTP conditions of BS 5514 and conforming to IS 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories, Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/ flexible coupling and coupling guard complete.
(a) Radiator with blower fan or heat exchanger with guard.
(b) Pipe coupling for engine cooling system piping.
(c) Corrosion inhibitor coolant
(d) Paper element filters
(i) Fuel filter
(ii) Lube oil filter
(iii) By pass
(e) Fly wheel housing and fly wheel to suit alternator.
(f) Engine bearing mechanism in fly wheel housing.
(g) Shut off coil with safety for LLOP/HWT/over speed.
(h) Dry type air cleaners and vacuum indicators.
(j) Residential silencers.
(k) Stainless steel exhaust flexible bellows.
(l) BLANK.
(m) Battery charging alternator. | - | - | - | - |
| - | (B) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:-
(i) Battery as per manufacturer specified.
(ii) Water temperature.
(iii) Lubricating oil pressure.
(iv) Engine speed -1500 Rpm
(v) Engine hours
(vi) Frequency.
(vii) Voltage.
(w) Safety control (Trip and indication).
(i) High water temperature
(ii) Low lube oil temperature
(iii) Overspeed stop
(C) Base frame : Sturdy, fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer's design alonwith AVM pads.
(D) Battery : as per manufacturer specified with leads & terminals. | - | - | - | - |
| - | (E) Alternator : Suitable rated 160 kVA, 0.8 PF, 415 Volts, 3 Phase, 4 Wire, 50 Hz at 1500 RPM, self excited and self regulated with AVR brushles, screen protected, drip proof, insulation class-H, IP -23, voltage regulation grade - VG 3 self ventilated and conforming to BS : 5000 / IS : 4722 suitable for engine as mentioned here-in before, conformig to IS: 13364 (Part-1)
(F) Acoustic Enclosure : M&L for acoustic enclosure for the above 160 kVA DG set to reduce noise level to 75 dB measured at 1.0 meter distance for audiable frequencies as per guide of Central Pollution Control Board and manufacturer's specification and comprising of following from authorised GOEMs of Gen Set manufacturer's specified. | - | - | - | - |
| - | Supplying, installing, testing and commissioning imdoor CPRI approved AMF Control panel of capcity 160 KVA factory fabricated cubical type, free standing, floor mounted, outdoor type, IP-52, with rotary handle, provided with removable rear panels & hinged front panel for easy accessibility, fabricated out of not less than 2.0 mm thick CRCA sheet with partition and switch enclosure door 1.6 mm including two coats of powder coated paint over a coat of red oxide primer with MS angle stand of size 50x50x6mm and shall be mounted on including necessary grouting in PCC 1:3:6 type C-1 by using 20 mm graded stone aggregate completed with legs 30 cm in ground in PCC and 40 cm above ground and termination of cable with gland and lugs comprising of following :-
LOCATION :
MAINT PUMP HOUSE AT AICTS PUNE - 01 No. | 1 | EACH JOB | - | - |
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.63 MB
BOQ_866152.xls
BOQ • 0.43 MB
85968TenderDocs.pdf
Tender Documents • 4.63 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .