| Sl No | Description | Qty | Unit | PARDEEP CONSTRUCTION COMPANY L2 | malghotra construction co L1 |
|---|---|---|---|---|---|
| 1.00 | M&L for seven stage cleaning and sterilization of inside the RCC/ PVC water storage tank of capacity not exceeding 500 Litres of any description and in any position comprising following cleaning and sterilization of water tanks through bacteriological treatment by using TERBAC G5/Inchlor-5/NB-10/ TERBAC-G-65/ Inoxi-60/NB-69 AND ULTRA VIOLET RAY. Make: Rays Cleantech/ Inus Watertech/ Satya Enterprise. Location: SAA seven stages are as under plants:- (a). First Stage is to drain out the water by using exit valve or high capacity dewatering system. (b). Second stage is cleaning all the algae formation inside the tank by using TERBAC G10/ Inoxi-60/NB-69 laboratory tested branded chemical of the company ans scrubbing the walls of the tanks. (c). Third strage is fresh water cleaning by high speed jet pump. (d). Fourth stage and first bacteria screening is decertification by using TERBAC-G5/ Inohor-5/NB-10 a Govt Laboratory certified brannded halogen compound or E-in-C approved equivalent product (e). Fifth stage is cleaning the floor of water tank by industrial vaccum cleaner. (f) . Sixth stage is the second bacteria screening and sterilizing method by using ultra violet ray within the tank and killing all suspended bacteria. (g) Seventh stage of cleaning and third bacteria screening is to sterilize the floor of the water tank by using laboratory certified, branded strong oxidizing agent TERBAC-G65/Inoxi-60/NB-69 or E-in-C's approved equivalent product. Note:- i) The work shall be carried out through the specilized agency i.e.Rays Cleantech/ Inus Watertech/ Satya Enterprise.
(ii) The cleaning and sterilization of RCC/ PVC water storage tank or any type of water retaining structure shall be carried out twice times during the contract period. (iii) Company will submit Government Laboratory Test Certificate of Terbac-G5/Inchor-5/Nb-10, Terbac-G65/ Inoxii-60/Nb-69, before cleaning, Fix the sticker mentioning the date of cleaning and name of site and also provide certificate confirming the completion of sterilization of Water Tanks mentioning the Name of Station and date of cleaning. All the cleaning and sterilization staffs should be under Accidental Insurance Coverage.) (iv) Outlet pipe of Overhead Tank should be plugged before cleaning the Overhead Tank to avoid entering scals and the same shall be reconnected after cleaning the OHT (Overhead Tank) and the quoted rates shall be demmed to be inclusive forthis aspect and provision. (v) Sterilization team will be comprised of atleast 30% members who are minimum 03 months certificate holde in water tanks sterilization. (vi) The contractor shall be responsible for rectification of complaints occurred during cleaning the tank i.e. no water In tank/over flow due to broken float valve/ blockage to be Included In quoted rate. | 1,983 | Each Job | 525 ₹10.4 L | 600 ₹11.9 L |
| 2.00 | All as per Serial item No. 1 here-in-before but of inside the RCC/ PVC water storage tank of capacity not exceeding 1000 litres. T | 200 | Each Job | 550 ₹1.1 L | 650 ₹1.3 L |
| 3.00 | All as per Serial item No. 1 here-in-before but of inside the RCC/ Steel Underground/Semi Underground/Over head/Sedmentation/clear water sumps of capacity UG sump reservoir 44000 gallons. Location: Dholewal Military Complex Ludhiana (Punjab). | 7 | Each Job | 25,000 ₹1.8 L | 30,000 ₹2.1 L |
| 4.00 | S&F in repairs 15mm bore Bib Taps, fancy type, chromium plated, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or brass ferrule complete all as specified and directed. | 105 | Each | 500 ₹52,500 | 250 ₹26,250 |
| 5.00 | S&F in repairs 25 mm automatic water level control float valve inside type for water tank with stainless steel exterior finish, BSP thread, nylon material complete all as specified and directed. | 40 | Each | 750 ₹30,000 | 360 ₹14,400 |
| 6.00 | S&F in repair 15mm bore size small GI fittings, such as socket, tee, elbow reducer 20 x 15mm reducer 20 x 15mmm tee of unequal size, GI union 15mm, GI union 20mm etc as required at site complete, all as specified and directed. Unit for this item shall be one No. for each one item) | 410 | Each | 85 ₹34,850 | 50 ₹20,500 |
| 7.00 | Excavating in trenches, in soft/loose soil, not exceeding 1.5m wide and not exceeding 1.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, cables and pipes etc. not exceeding 10Sqm on plan and not exceeding 1.5m in depth and getting out complete all as specified and as direcetd. | 49.2 | Cum | 100 ₹4,920 | 80 ₹3,936 |
| 8.00 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceding 25cm in soft/loose soil complete all as directed. | 36.6 | Cum | 30 ₹1,098 | 20 ₹732 |
| 9.00 | Removing excavated materials to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. | 12.6 | Cum | 40 ₹504 | 20 ₹252 |
| 10.00 | S&F in repairs 20mm bore Galvanised Medium Grade Steel Water Tubing with all fittings and connections fixed complete to walls and celling or laid in trenches and floor, including taking down / dismantling existing pipeline with fittings complete all as specified and directed. | 1,000 | RM | 210 ₹2.1 L | 140 ₹1.4 L |
Updated dates
Tender Value
Refer Docs
EMD Value
₹1.1 L
Closing Date
22 Dec 2025, 6:00 pmClosed
CWE FEROZEPUR CANTT
HQ CWE FEROZEPUR CANTT PIN 152001
REPAIR / MAINT CLEANING AND SANITIZATION OF OVERHEAD TANK AND ALLIED WORKS AT DHOLEWAL MIL COMPLEX CG COMPLEX DORAHA PHILLAUR BADDOWAL AND MOGA UNDER GE LUDHIANA
2025_MES_740365_1
CWE/FZR-52/2025-26
Open Tender
Civil Works
365 days
FEROZEPUR CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE LUDHIANA
₹1.1 L
Yes
17 Jan 2026
18 Nov 2025
29 Dec 2025
18 Nov 2025
22 Dec 2025
9 Dec 2025
Amount
All as per Serial item No. 1 here-in-before but of inside the RCC/ PVC water storage tank of capacity not exceeding 1000 litres. T
All as per Serial item No. 1 here-in-before but of inside the RCC/ Steel Underground/Semi Underground/Over head/Sedmentation/clear water sumps of capacity UG sump reservoir 44000 gallons. Location: Dholewal Military Complex Ludhiana (Punjab).
S&F in repairs 15mm bore Bib Taps, fancy type, chromium plated, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or brass ferrule complete all as specified and directed.
S&F in repairs 25 mm automatic water level control float valve inside type for water tank with stainless steel exterior finish, BSP thread, nylon material complete all as specified and directed.
S&F in repair 15mm bore size small GI fittings, such as socket, tee, elbow reducer 20 x 15mm reducer 20 x 15mmm tee of unequal size, GI union 15mm, GI union 20mm etc as required at site complete, all as specified and directed. Unit for this item shall be one No. for each one item)
Excavating in trenches, in soft/loose soil, not exceeding 1.5m wide and not exceeding 1.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, cables and pipes etc. not exceeding 10Sqm on plan and not exceeding 1.5m in depth and getting out complete all as specified and as direcetd.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceding 25cm in soft/loose soil complete all as directed.
Removing excavated materials to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
S&F in repairs 20mm bore Galvanised Medium Grade Steel Water Tubing with all fittings and connections fixed complete to walls and celling or laid in trenches and floor, including taking down / dismantling existing pipeline with fittings complete all as specified and directed.
S&F in repairs 25mm bore Galvanised Medium Grade Steel Water Tubing with all fittings and connections fixed complete to walls and celling or laid in trenches and floor, including taking down / dismantling existing pipeline with fittingscomplete all as specified and directed.
S&F in repairs framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks, valve pit covers and similar work conforming to Fe.290.Gde-E-165 complete all as specified and directed.
S&F in repairs 20mm bore Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipes including taking down / dismantling existing GM valves complete all as specified and directed.
S&F in repairs 25mm bore Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipes including taking down / dismantling existing GM valves complete all as specified and directed.
S&F in repairs 3-layer PP-R Polypropylene random copolymer concealed pipes size 20mm SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded Polypropylene random fittings fixed complete to walls, ceilings, floors, roads and laid in trenches etc including fittings such as socket, bend, elbow, union,flanges including taking out existing GI tubing with all fittings complete all as specified and directed.
S&F in repairs 3-layer PP-R Polypropylene random copolymer concealed pipes size 25mm SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded Polypropylene random fittings fixed complete to walls, ceilings, floors, roads and laid in trenches etc including fittings such as socket, bend, elbow, union,flanges including taking out existing GI tubing with all fittings including taking out existing GI tubing with all fittings complete all as specified and directed.
S&F in repairs 3-layer PP-R Polypropylene random copolymer concealed pipes size 32mm SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded Polypropylene random fittings fixed complete to walls, ceilings, floors, roads and laid in trenches etc including fittings such as socket, bend, elbow, union,flanges including taking out existing GI tubing with all fittings including taking out existing GI tubing with all fittings complete all as specified and directed.
Making connection of PP-R distribution branch with PP-R main of sizes 16 to 40mm outer dia of pipes by providing and fixing tee including cutting and making fusion joint etc with all fittings complete all as specified and directed.
S&F in replacement 20mm bore PP-R Gate valves (brass insert) with iron wheel head screwed both ends for iron pipes including taking down complete all as specified & directed by Engineer-in-charge.
S&F in replacement 25mm bore PP-R Gate valves (brass insert) with iron wheel head screwed both ends for iron pipes including taking down complete all as specified & directed by Engineer-in-charge.
S&F in replacement 32mm bore PP-R Gate valves (brass insert) with iron wheel head screwed both ends for iron pipes including taking down complete all as specified & directed by Engineer-in-charge.
M&L for brick work built in cement mortar (1:4) with sub class 'B' old size bricks, straight or curved on plan exceeding 6m mean radius complete all as specified and directed.
M&L for 10mm thick rendering cement plaster in cement mortar (1:4) on fair faces of brick walls or concrete surfaces, finished even and smooth without using extra cement complete all as specified and directed.
M&L for 75mm thick Plain Cement Concrete (1:4:8) type D-2 using 40mm graded crushed stone aggregate as in sub base of flooring,surface finished rough to receive floor topping, surface finished even and fair complete all as specified and directed.
M&L for 50mm thick Plain Cement Concrete (1:2:4) type B-2 using 40mm graded crushed stone aggregate as in sub base of flooring,surface finished rough to receive floor topping, surface finished even and fair complete all as specified and directed.
M&L for lime concrete with lime motor 1:3 Mix 75 mm all as specified as directed. Lime concrete with lime mortar 1:3 mix and 40mm graded stone coarse aggregate in sub-floors complete all as specified and directed.
Demolition of un-reinforced cement concrete of any description and in any position not otherwise specially provided for complete all as specified and directed.
S&F in replacement 500 litres capacity rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top), three layered, ISI marked, hoisted & fixed in position & making necessary arrangements for fixing inlet, outlet & over flow pipe & provision of wash out pipe etc. hoisted and fixed including dismentling and taking down old unserviceable water tank capacity 500 litres complete as specified in SSR Part-I. complete all as specified and directed.
S&F in replacement 1000 litres capacity rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top), three layered, ISI marked, hoisted & fixed in position & making necessary arrangements for fixing inlet, outlet & over flow pipe & provision of wash out pipe etc. hoisted and fixed including dismentling and taking down old unserviceable water tank capacity 1000 litres complete as specified in SSR Part-I. complete all as specified and directed.
S&F in replacement 20mm bore ball brass valves,high pressure,with polythene float and flynut complete,screwed for iron pipe or brass ferrule complete, including taking out existing ball valve all as specified and directed.
S&F in replacement 20mm automatic water level control float valve inside type for water tank with stainless steel exterior finish, BSP thread, nylon material complete including taking out existing float valve all as specified and directed.
S&F in repairs 2.00 mm thick mild steel plate /sheet plain or chequered, cut to pieces as required and fixed to MS frame work by means of Electric arc/gas welding including dismantling existiing mild steel sheet/plate complete all as specified and directed.
S&F in repairs 150mm bore Galvanised Medium Grade Steel Water Tubing with all fittings and connections fixed complete to walls and celling or laid in trenches and floor, including taking down / dismantling existing pipeline with fittingscomplete all as specified and directed.
S&F in repairs 100mm bore Galvanised Medium Grade Steel Water Tubing with all fittings and connections fixed complete to walls and celling or laid in trenches and floor, including taking down / dismantling existing pipeline with fittingscomplete all as specified and directed.
S&F in repairs 80mm bore Galvanised Medium Grade Steel Water Tubing with all fittings and connections fixed complete to walls and celling or laid in trenches and floor, including taking down / dismantling existing pipeline with fittingscomplete all as specified and directed.
S&F in repairs 50mm bore Galvanised Medium Grade Steel Water Tubing with all fittings and connections fixed complete to walls and celling or laid in trenches and floor, including taking down / dismantling existing pipeline with fittingscomplete all as specified and directed.
S&F in repairs 40mm bore Galvanised Medium Grade Steel Water Tubing with all fittings and connections fixed complete to walls and celling or laid in trenches and floor, including taking down / dismantling existing pipeline with fittingscomplete all as specified and directed.
Repairs to leakage run lead joint in position of size 150mm bore CI pipes by burning out existing joints,recovering lead, cleaning internal surfaces of socket and providing new joints with using recovered lead and additional new lead, making joint leak proof.
All as per item No 38 above but Size of CI pipe 100mm bore.
All as per item No 38 above but Size of CI pipe 80mm bore. Note for item No. 38 to 39 :- Excavation of Earth work shall be measured and paid seperately)
Repairs to leakage run rubber gasket joint for 150mm bore flanged pipes and fittings including necessary fittings such as bolts, nuts, washers, white lead or mineral oil complete all as specified and directed by Engineer-in-charge.
All as per item No 41 above but Size of GI/CI pipe 100mm bore.
All as per item No 41 above but Size of GI/CI pipe 80mm bore. Note for item No. 41 to 43:- Excavation of Earth work shall be measured and paid seperately)
S&F cast iron fitting upto 150mm bore such as bends (any type, radius and angle), tapers any type (straight, bend, increasing, decreasing or double socket etc), Tee pieces, single branch, 'Y' junction, double branch, cross collar, caps and plugs etc. suitable for spigot and socketed pipes including taking out existing defective fittings from the trenches or ground all as specified and directed.
S&F in replacement cast iron sluice valve suitable for 150mm bore pipe with flanged ends drilled ISI marked class PN-1.6 conforming to IS- 14846 with stainless steel spindle, CI gate with brass nut, bolt, washer and rubber packing for connecting pieces etc including taking down complete all as specified and directed.
S&F in replacement cast iron sluice valve suitable for 100mm bore pipe with flanged ends drilled ISI marked class PN-1.6 conforming to IS- 14846 with stainless steel spindle, CI gate with brass nut, bolt, washer and rubber packing for connecting pieces etc including taking down complete all as specified and directed.
S&F in replacement cast iron sluice valve suitable for 80mm bore pipe with flanged ends drilled ISI marked class PN-1.6 conforming to IS- 14846 with stainless steel spindle spindle, CI gate with brass nut, bolt, washer and rubber packing for connecting pieces etc including taking down complete all as specified and directed.
S&F in replacement gun metal globe or gate valve 40mm bore with iron wheel head screwed both ends for iron pipes including taking down complete all as specified and directed.
S&F in replacement gun metal globe or gate valve 50mm bore with iron wheel head screwed both ends for iron pipes including taking down complete all as specified and directed.
S&F in replacement Over load relay 30 to 50 Amps 415 V including taking down complete all as specified and directed.
S&F in replacement Contractor having AC 1, 85 amp and AC 3, 50 amp.
S&F in replacement Front mounting add on aux contact block MNX A2 including taking down complete all as specified and directed.
S&F in replacement Single phase preventor, 240V AC, relay range 2-5.5A with earth fault protection including taking down complete all as specified and directed.
S&F in replacement Star delta timer ETR. including taking down complete all as specified and directed.
S&F in replacement MPCB 63 Amp 3 Phase including taking down complete all as specified and directed.
S&F in replacement multifunction meter WL 4400 series RS485 including taking down complete all as specified and directed.
S&F in replacement of push button assembly with harness and indicating lamp including taking down complete all as specified and directed.
Rewinding of submersible motor of any make & capacity 25/30 HP by using existing size and gauge of PVC insulated single core copper conductor submersible winding wire including all insulated material complete .Note :- Rates are including lifting of column pipe and submersible motor,transportation all allied accessories required for repair/rewinding and reassembling the submersible motor at existing sites lowering, connecting, testing,commissioning of repaired pump set with existing size column pipes all as specified and directed by Engr- In- Charge
S&F in replacement 1100 Volts grade heavy duty FRLSH PVC insulated flat submersible cable 10 sqmm, 3 core with copper conductor complete including taking down complete all as specified and directed.
S&F in replacement 3 metre long column pipe 100mm dia made out of medium grade GI pipe with two number flanges welded at both ends having drilled hole and cut for submersible cable complete.
S&F in replacement name board with in built LED lights of r/o Pump houses (size 4 feet x 3 feet) with fitted required height of angle iron complete including taking down complete all as specified and directed.
Repairs of valve pit chambers of size 1200mmX900mmX900mm complete including taking down complete all as specified and directed.
Repairs of valve pit chambers of size 900mmX600mmX900mm complete including taking down complete all as specified and directed.. Note for item No. 51 & 52 :- The rate quoted shall be deemed to include the cost of PCC, Bricks works, Plasters, angle iron, hinges, handle, MS plate cover, white wash, painting and nuts and bolts etc.
Supply only chlorination test kit including taking down complete all as specified and directed..
M&L for prepation new painted metal surfaces of any description, over 10cm in width or girth and appling two coat of synthatic enamel paint and priming with red oxide, zinc chrome of approved tint complete all as specified and directed.
M&L for prepation old painted metal surfaces of any description, over 10cm in width or girth and appling one coat of synthatic enamel paint of approved tint complete all as specified and directed.
Testing potability of water by chemical analysis as per IS- 10500 such as PH value, dissolved solids, hardness as CaCO3, calcium, magnesium, chlorides, sulphates, nitrate, alkalinity, iron, turbidity NTU, mineral oil, colour hazen units, taste, odour, residual free chlorine, total coliform per 100ml (microbiological test) & E coli per 100ml (microbiological test) as well as bacteriological portability from any Govt. Laboratory or any NABL accrediated Lab complete all as specified and directed.
S&F in replacement MCCB 63 Amp, 415 V, 25 KA, 4 pole with adjustable thermal magnetic release complete including taking down complete all as specified and directed.
S&F in replacement MCCB 100 Amp, 415 V, 25 KA, 4 pole with adjustable thermal magnetic release complete including taking down complete all as specified and directed.
S&F in replacement MCCB 125 Amp, 415 V, 36 KA, 4 pole with adjustable thermal magnetic release complete including taking down complete all as specified and directed.
S&F in replacement MCCB 250 Amp, 415 V, 36 KA, 4 pole with adjustable thermal magnetic release complete including taking down complete all as specified and directed.
S&F in replacement onload Changeover Switch 63 A, 4P 415 V with enclosure complete including taking down complete all as specified and directed.
S&F in replacement automatic star-delta starter in sheet metal enclosures, 415 volts, 3 phase, 50 Hz type ML-3 with overload relay range 14-23 Amp suitable upto 30 HP electric motor including taking down complete all as specified and directed.
Developement of stabilizing/desiliting of the existing borewell size 300/200 mm dia by using suitable capacity of air compressor/ special tools/ accessories and arrangement required for Job etc.after compressor devolopment of the borewell by using higher size submersible pump minimum 4 to 6 hrs time or upto crystel clear water discharge all as specified and directed by engineer- in- charge.Note:- The rates shall be inclusive of hiring of air compressor/ fuel required, special tools/ accessories, transportation of the same, disposal of discharged water including labour charges for specialy trained man poower for the work of disiliting of borewell.
Cleaning,painting of Overhead tank out and in side,Painting to raising/deleivery/wash out/over flow CI/GI pipe line 150 mm dia Over Head reservoir (RCC) as per existing colour (Apex) code including preparation of old surface of painting with one coat of synthetic enamel paint from ground level to bottom of the dome of the tank complete removing all scale & dirt from bottom & walls and from mouth of circulation pipes of overhead tank of capacity 50,000 gallons at staging height exceeding 15 metre and not exceeding 21.5 metre and disinfecting chemical the same using disinfecting chemical (chlorine) complete all as specified & directed by Engineer-in-charge. Note :- The rate quoted shall be deemed to include the cost of neccessary scaffolding,supports,all type of cleaning material etc.Appx paint for RCC tank & structure and inlet & outlet pipe syenthic enamel paint.
Supply, Installing,Testing and Commissioning of Ultrasonic Level Transmitter at overhead tank for measurement of level with following specification:- Range : 0-8 meters Accuracy : 0.2 % minimum Supply Voltage : 10 - 30V DC Output : 4-20 mA , 0-10V DC Operating Temprature : -20 to 70°C Ultrasonic Frequency : 75 kHz Response Time : Minimum 100 ms Note: -1). The Ultrasonic Sensor need to be covered in a polycarbonate box of size 130X130X75 mm before installation on OHT. 2). The Programming of Ultrasonic Sensor, e.g. Changes in range of sensor, changes in operational features etc. shall be carried out by authorized system integrator of the provided makes. The programmer shall submit a letter from the OEM as proof of his being an authorized system integrator of the OEM. The programmer shall also submit a signed report on original letterhead of the OEM that testing & commissioning has been carried out by him. Make: Nivelco / Siemens / Banner
Supply, Installation, Testing & Commissioning of Outdoor type having Canopy and Double Door for weather protection, PLC ( Programmable Logic Controller) based Automation, Protection Panel suitable for control and monitoring of 01 Nos. Ultrasonic Sensor. The panel should be of minimum size 600(H) X 600(W) X 250(D) mm fabricated from 3.15 mm CRCA Sheet.The Panel should comprise the following functions & items:- (a) Water Level Sensing & Display (ii) 01 No. PLC with follwing specifications:- (MAKE:- SCHNEIDER/ABB/ PHOENIX CONTACT).(a). 1 Nos. Ethernet communication port.(b). Suitable No. of digital / analog input and outputs.(c). Programming Software based on IEC to facilitate building of custom build function blocks.(d). Industrial Grade Processor, Web Server, SMTP E-mail service.(e). Protocol : Master/Slave Modbus, Expandable upto 248 I/O’s and 7 expansion module.(iii) 01 no. HMI - 7" Graphical Touch screen display (Make: SCHNEIDER / SIEMENS/ ABB/ PHOENIX CONTACT/ L&T) (a). Should have 01 No. RS 485 and 01 No. USB programming port.(b). Should have USB downloading port.(c). Support external data storage on a USB memory stick for storing production data and backing up applications.(iv) 01 No. SMPS of 1.5A rating as suitable according to panel design. (Make: SCHNEIDER / OMRON / PHOENIX CONTACT/TTPL).(vii) MCB rating 6-10A. Make:- Legrand/ Schneider/ABB/L&T.(viii) Indicator lamp :- As per requirement (Make:- Schneider/ ESBEE/ABB).CRCA Enclosure:- Make (UNIVERSAL SWITCH GEAR CONTROL / HOFFMAN / ADLEC / TRICOLITE ). Note: - The Programming, Testing, Commissioning & Integration of PLC Panel shall be carried out by authorized system integrator of the provided makes. The programmer shall submit a letter from the OEM as proof of his being an authorized system integrator of the OEM. The programmer shall also submit a signed report on original letterhead of the OEM that Programming, Testing, Commissioning & Integration has been carried out by him.Make of the PLC based panel:- (Universal Switch Gear Control or equivalent in ABB Automation/Tricolite/GE Automation)
Supply, Instal, joint, fix , test and Commission 2 Core 1.5 sqmm PVC FRLSH insulated copper armoured cable including taking out/dismantling complete all as specified and directed.
Supply, Instal, joint, fix , test and Commission 4 Core 1.0 Sqmm copper armoured conductor Shielded cable for Communication including taking out/dismantling complete all as specified and directed.
M&L for retreatement of earthing by removing old earth pit and refilling Charcol & Salt cristals of 50 Kg Each including taking out old expired chemical/Charcol/Salt and refilling of soil, watering & well ramming and constrction of new earth Chamber with fixing of funnel complete with colour code such as green for body earthing/blue etc including taking out/dismantling complete all as specified and directed.
PARDEEP CONSTRUCTION COMPANY (BID ID -3498376)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.45 MB
TENDER52.pdf
Tender Documents • 1.41 MB
BOQ_829013.xls
BOQ • 1.06 MB
Download all tender documents and submit your bid