Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.5 LAccepted-AOC NO 1A 1 SHALOM VALLUVAR STREET SIVANANDHA COLONY COIMBATORE TAMIL NADU 641 012 | COIMBATORE | TAMIL NADU | 641012 | L1 | Accepted-AOC Being Lowest Tenderer | |
| 2 | L2₹14.3 L+₹80,350 (5.97%)Rejected-Finance H NO 111 553 64 CATTLE POUND TOWARDS AVA HILL CAMP ROAD ARUVANKADU NILGIRIS DIST TAMIL NADU 643 202 | THE NILGIRIS | TAMIL NADU | 643202 | L2 | Rejected-Finance Being Not Lowest Tenderer | |
| 3 | L3₹14.8 L+₹1.3 L (9.52%)Rejected-Finance 25 A RR SAMY LANE KATTOOR COIMBATORE 641009 | COIMBATORE | COIMBATORE | TAMIL NADU | 641009 | L3 | Rejected-Finance Being Not Lowest Tenderer | |
| 4 | L4₹16.8 L+₹3.3 L (24.5%)Rejected-Finance | L4 | Rejected-Finance Being Not Lowest Tenderer | |
| 5 | L5₹21.5 L+₹8.1 L (59.8%)Rejected-Finance | L5 | Rejected-Finance Being Not Lowest Tenderer |
Tender Value
₹14.9 L
EMD Value
₹29,800
Closing Date
12 Aug 2022, 6:00 pmClosed
GE Wellington
Garrison Engineer Wellington Barrack Post Nilgiris Pin code-643231
REPAIRS REPLACEMENT AND IMPROVEMENT OF LT OH LINE ACSR CONDUCTOR LT UG CABLE AND LT SWITCH GEARS LT PANEL POLES WITH ACCESSORIES ETC OF WELLINGTON BARRACKS AREA UNDER GE WELLINGTON
2022_MES_538270_1
8723/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Wellington
As per Tender Documents
4 documents required · 4 mandatory
₹500
GE Wellington
₹29,800
Yes
30 Sept 2022
15 Jul 2022
19 Aug 2022
16 Jul 2022
12 Aug 2022
29 Jul 2022
Amount
Supply, testing and replacement of LT UG Cable, 1100 volts grade, XLPE insulated screened PVC bedded, Galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor of size 10 Sqmm x 2 Core laid in trenches / ducts, fixed on wall / inside panel, drawn through pipe including taking out old unserviceable LT cable complete all as specified and directed.
Supply, testing and replacement of LT UG Cable, 1100 volts grade, XLPE insulated screened PVC bedded, Galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor of size 16 Sqmm x 2 Core laid in trenches / ducts, fixed on wall / inside panel, drawn through pipe including taking out old unserviceable LT cable complete all as specified and directed.
Supply, testing and replacement of LT UG Cable, 1100 volts grade, XLPE insulated screened PVC bedded, Galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor of size 16 Sqmm x 4 Core laid in trenches / ducts, fixed on wall / inside panel, drawn through pipe including taking out old unserviceable LT cable complete all as specified and directed.
Supply, testing and replacement of LT UG Cable, 1100 volts grade, XLPE insulated screened PVC bedded, Galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor of size 25 Sqmm x 3½ Core laid in trenches / ducts, fixed on wall / inside panel, drawn through pipe including taking out old unserviceable LT cable complete all as specified and directed.
Supply, testing and replacement of LT UG Cable, 1100 volts grade, XLPE insulated screened PVC bedded, Galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor of size 50 Sqmm x 3½ Core laid in trenches / ducts, fixed on wall / inside panel, drawn through pipe including taking out old unserviceable LT cable complete all as specified and directed.
Supply, testing and replacement of LT UG Cable, 1100 volts grade, XLPE insulated screened PVC bedded, Galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor of size 95 Sqmm x 3½ Core laid in trenches / ducts, fixed on wall / inside panel, drawn through pipe including taking out old unserviceable LT cable complete all as specified and directed.
Supply, testing and replacement of LT UG Cable, 1100 volts grade, XLPE insulated screened PVC bedded, Galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor of size 120 Sqmm x 3½ Core laid in trenches / ducts, fixed on wall / inside panel, drawn through pipe including taking out old unserviceable LT cable complete all as specified and directed. Note for item No 1 to 7: Rate deemed to be inclusive of conecting up with control gear including cable glands and cable lugs complete.
Supply and replace cable route indicator round in shape with cast iron of dia not less than 100 mm duly embossed as LT with 32mm X 6 mm MS Angle welded and foundation with PCC 1:3:6 type C1 using 20 mm graded aggregate complete all as specified and directed
Supply, install, test and commission LT Panel board, TPN 415 Volts, 50 Hz, 400 Amps capacity out door cubical type CPRI approved floor mounted factory made double door dust and vermin proof, IP-54, fabricated out of CRCA sheet not less than 3.15 mm thick with 2mm thick for internal compartment duly powder coated fixed on angle iron pedestal made out of 50X50X6mm with cable chamber for incoming and outgoing connections comprising for the following including necessary PCC foundation of minimum 0.35m height positioned and fixed with suitable nut, bolts, washers etc to the MC pedestal and connecting all incoming and out going cables using necessary cable glands including taking out old panel board of any size all as specified and directed :- (a) INCOMING:- MCCB 4 Pole, 25 KA, 250 Amps 415 Volts - 1 No (b) OUTGOINGS:- (i) MCCB 4 Pole, 25 KA, 100 Amps 415 Volts - 2 Nos (ii) MCCB 4 Pole, 16 KA, 63 Amps 415 Volts - 2 Nos (iii) MCCB 4 Pole, 16 KA, 40 Amps 415 Volts - 2 Nos (iv) MCB SPN 32 Amps - 4 Nos (c) 400 Amps aluminium busbar for phase and 300 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulators in separate compartment - 01 Set (d) Digital multi function panel meter for measuring voltage, Amps and Frequency with suitable CTs and back up protection - 1 No (e) LED type Indication lamp 240 Volts Set of three - 1 Set
Supply, install, test and commission LT Panel board, TPN 415 Volts, 50 Hz, 600 Amps capacity out door cubical type CPRI approved floor mounted factory made double door dust and vermin proof, IP-54, fabricated out of CRCA sheet not less than 3.15 mm thick with 2mm thick for internal compartment duly powder coated fixed on angle iron pedestal made out of 50X50X6mm with cable chamber for incoming and outgoing connections comprising for the following including necessary PCC foundation of minimum 0.35m height positioned and fixed with suitable nut, bolts, washers etc to the MC pedestal and connecting all incoming and out going cables using necessary cable glands including taking out old panel board of any size all as specified and directed :- (a) INCOMING:- MCCB 4 Pole, 35 KA, 400 Amps 415 Volts - 1 No (b) OUTGOINGS:- (i) MCCB 4 Pole, 25 KA, 200 Amps 415 Volts - 2 Nos (ii) MCCB 4 Pole, 25 KA, 100 Amps 415 Volts - 1 No (iii) MCCB 4 Pole, 16 KA, 63 Amps 415 Volts - 1 No (iv) MCB SPN 40 Amps - 4 Nos (c) 600 Amps aluminium busbar for phase and 400 Amps for neutral duly insulated with PVC sleeves RYB, mounted on heavy duty epoxy insulators in separate compartment - 01 Set (d) Digital multi function panel meter for measuring voltage, Amps and Frequency with suitable CTs and back up protection - 1 No (e) LED type Indication lamp 240 Volts Set of three - 1 Set
Excavation in trenches not exceeding 1.5M wide and not exceeding 1.5M in depth and getting out in soft/ loose soil for laying of under ground cable and foundation of poles.etc complete all as specified and directed.
Returning filling in including spreading, leveling watering and well ramming using excavated soil in layers not exceeding 25 Cm thick, complete all as specified and directed.
Removal of excavated surplus soil not exceeding 50 m and depositing where directed at al level not exceeding 1.5 m above the starting point and all as specified and directed.
Supply and spreading clean dry riddled sand in trenches for cushioning all as specified for cable protection in trenches / ducts complete all as specified and directed. Note: The punned down thickness shall only measured for payment.
Bricks sub class 'B' old size bricks to be laid over dry sand cushinoing in trenches as protection to cable all as specified and directed.
Cement concrete (1:4:8) type D2 with 40 mm graded aggegate for foundation of poles including form work and finishing to all exposed surfaces by using extra cement all as specified and as directed.
Cement concrete (1:3:6) type C1 with 20 mm graded aggegate for foundation / road crossing including form work and finishing to all exposed surfaces by using extra cement all as specified and as directed.
Steel tubular swaged poles of complete with cast iron base plate, finial taper, plug, bolts, nuts and screws as specified type 410 SP 31, 9 mtr long pole including taking out old poles complete all as specified and directed.
Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint including dismantling of cross arms of MS channel or angle sections etc complete all as specified and directed.
Supply, install, test and commissioning of feeder pillar box/ Bus bar chamber of size 400x400x230mm made up of 3.15m thick MS sheet, out door type of 200 Amps rated busbar of 3 phase and neutral including supports, cable entry at bottom and stand made of MS angle (2 Nos) of size 50x50x6mm, 1 meter long including foundation in PCC 1:4:8 including taking out old FPB complete all as specified and directed.
Aluminium conductor, steel reinforced including stringing in position complete including dismantling of old ACSR conductor complete all as specified and directed.
Supply and fix in repairs galvanised steel wire 4mm dia / 8mm dia for guard wire, continuous earth wire complete all as specifed and directed.
Stay assembly complete with accessories as shown in electrical plate No 1 with stay rod 16mm dia including dismantling the old unservicable stay complete all as specified and directed. Note: Excavation and concrete shall be measured and paid separetly.
GI Pipe galvanised light grade 80 mm dia for cable protection in trenches/ at PCC pole for loopin/loop out of cable and cable entry at Bldg/block end including taking down old pipe all as specified and directed.
GI Pipe galvanised light grade 40 mm dia for cable protection in trenches/ at PCC pole for loopin/loop out of cable and cable entry at Bldg/block end including taking down old pipe all as specified and directed.
Earthing complete including testing with galvanised steel plate electrode 600x 600x 6mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of plate not less than 1.5 mtrs below normal ground level connected to galvanised iron strip of size 32x6mm from earth plate to body of the equiment by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 connected to earth in test point on completion with and including 15mm bore light grade GI protection pipe ( 7.5 mtr long) for earth including PCC (1:2:4) type B1 chamber pit with pre cast RCC (1:2:4) type B1, 40mm thick reinforced with 6mm dia MS bars @ 100 c/c bothway, lifting hooks made out of 6mm MS bars, watering arrangement with funnel, wire, common salt, charcoal filling, necessary excavation and earth work in any type of soil complete all as specified and as directed.
sree devi construction
rvelectricals
Manoprabha Electricals
Saket Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .