| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹74.3 LAccepted-Finance | 1 | Accepted-Finance Qualified | |
| 2 | 2₹75.4 L+₹1.1 L (1.51%)Accepted-Finance | 2 | Accepted-Finance Qualified | |
| 3 | 3₹85.2 L+₹10.9 L (14.7%)Accepted-Finance | 3 | Accepted-Finance Qualified | |
| 4 | Rejected-Technical | - | Rejected-Technical Non Submission of necessary Documents |
Tender Value
₹78.2 L
EMD Value
₹1.6 L
Closing Date
29 Sept 2020, 2:00 pmClosed
Ex Engg STD Bijbehara
Hamzapora Bijbehara
Construction of 33KV line using 100 Sq mm ACSR Conductor on 11 Mt long S T Poles from R/t Gopalpora to (1x10) MVA proposed receiving station at Kawarigam
2020_PDD_103704_1
STB/17 of 2020-21 Dated 05-09-2020
Open Tender
Electrical Works
Turn-key
80 days
Kawarigam, Achabal Anantnag
Please refer Tender documents.
5 documents required · 5 mandatory
₹2,000
DD in favour of Ex Engg STD Bijbehara
₹1.6 L
Yes
Office of the Ex Engg STD Bijbehara
28 Oct 2020
7 Sept 2020
30 Sept 2020
7 Sept 2020
29 Sept 2020
12 Sept 2020
7 Sept 2020 - 12 Sept 2020
10 Sept 2020
Amount
Providing.errection, testing and commissioning of 11Mtr long S.T Poles (410SP- 56) complete with base and cap as per REC standard and specifications.
Providind,laying , stringing, binding and commissioning of 0.1 ACSR (DOG) Conductor.
Providing, fabrication and fixing of Galvanised V -type Channel Iron X-arm,10' Long Ch Iron,Channel Iron Top and Flat braces as per REC Standard.
Providing , fixing and commissioning of 33KV Polymeric Composite Pin Insulator 36KV,10KN,Lighting Impulse 170KV Positive & 180 KV Negative,Creepage distance 900mm
Providing , fixing and commissioning of 33 KV Polymeric Composite Disc Insulator 36KV,Min failing load 70KN,Lighting Impulse 170KV Positive & 180 KV Negative,Creepage distance 900mm suitable for 0.1 ACSR Conductor
Providing & fixing of P G Clamps for 100mm Sq ACSR
Providing & fixing of 33 KV Danger Plates with clamps
Providing & fixing of Anticlimbing devices with clamps
Providing & fixing of Nuts & bolts with washers
Providing & fixing of Earthing Complete by G I Pipe 40mm or G I Rod 20mm 2.5 Mtr long through G I Strip as per REC Standard
Providing & painting of to 11 Mt Long S.T poles including X Arms with one coat of Red oxide paint & Two Coats of Almunium Paint (ISI mark)
Cement Bottoming of poles of 11 Mtr long upper ground and under ground in 1:2:4 Mix (0.6cum/pole) as per REC
Galvanised Stay set with 50X8mm Stay Clamps,Guy Insulator,Anchor Plat(300X300X8)mm,Nuts/Bolts ,Turn Buckle,1.8 Mt long 20mm Dia Sold GS Stay rod & 7/4.0mm Dia GI Std wire complete
Guard Netting as per REC Standard
Providing,errection, testing and commissioning of 33 KV Isolator set with earthing Blade as per REC standard and specifications.
M/S ASSOCIATE ENGINEERS
N S ENTERPRISES
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .