Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹44.2 CrAccepted-AOC | ₹44.2 Cr | 1 | Accepted-AOC Being lowest and reasonable |
| 2 | 2₹44.4 CrRejected-Finance F 18 ANSAL COMPLEX OPP JWALA HARI MARKET PASCHIM VIHAR NEW DELHI 110063 | NEW DELHI | WEST DELHI | DELHI | 110063 | ₹44.4 Cr | 2 | Rejected-Finance Not being lowest |
| 3 | 3₹44.4 CrRejected-Finance | ₹44.4 Cr | 3 | Rejected-Finance Not being lowest |
| 4 | 4₹44.8 CrRejected-Finance | ₹44.8 Cr | 4 | Rejected-Finance Not being lowest |
| 5 | 5₹45.4 CrRejected-Finance L 87 STREET NO 7C MAHIPALPUR EXTENSION NEW DELHI 110037 | NEW DELHI | NEW DELHI | DELHI | 110037 | ₹45.4 Cr | 5 | Rejected-Finance Not being lowest |
Tender Value
₹48 Cr
EMD Value
₹15 L
Closing Date
12 Sept 2020, 6:00 pmClosed
CE AF SHILLONG ZONE
HQ CHIEF ENGINEER AF SHILLONG ZONE MILITARY ENGINEER SERVICES ELEPHANT FALLS CAMP PO NONGLYER SHILLONG 793009
PROVISION OF DEFICIENT OTM ACCN AND HANGAER COMPLEX UNDER GE AF BORJHAR
2020_MES_354652_1
C/88397/E8
Open Tender
Civil Works - Others
750 days
BORJHAR
AS PER NIT CONDITIONS
8 documents required · 8 mandatory
₹3,000
Yes
GE AF BORJHAR
₹15 L
Yes
HQ CE AF SHILLONG ZONE
8 Oct 2020
22 Jun 2020
17 Sept 2020
22 Jun 2020
12 Sept 2020
7 Sept 2020
6 Jul 2020
Amount
SCHEDULE 'A' PART- I (BUILDINGS/STRUCTURES) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART- II (SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART- III (INTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- IV (INTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART-V (HANGAR FLOOR) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART-VI (DISPERSAL AND PAVEMENT APRON) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- VII (ROAD / PATH / CULVERT) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- VIII (SEWAGE DISPOSAL) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- VIII(A) (AREA DRAINAGE) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- IX (EXTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE 'A' PART- X (EXTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART-XI (PNEUMATIC DISTRIBUTION SYSTEM) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART-XII (LIGHTENING PROTECTION AND CONDUCTING GRID) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART-XIII (WATER COOLER AND AIR CONDITIONING) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART-XIV (DEMOLITION / DISMANTLING) Details of prepriced Schedule is given in tender documents
SCHEDULE 'A' PART -XV (MISCELLANIOUS ITEMS) Note:- This schedule is not pre-priced by MES.
INTERNAL ELECTRIFICATION: S & F of CEILING FAN, 1200mm sweep, AC Single Phase, 240V, 50Hz, BEE 5 star rated, including down rod of suitable size, connected with twin core twisted flixible wire copper conductor cable of suitable size from ceiling rose to ceiling fan, complete, all as specified and directed.
S & F of EXHAUST FAN, 300mm sweep, 1400 RPM, AC Single Phase, 240 V, including connecting with twin core twisted flixible wire copper conductor cable of suitable size from ceiling rose to exhaust fan, complete, all as specified and directed.
S & F of LED batten suitable for T5 18W LED tubes, 240V, including neccesary electric connection with suitable size copper cable from junction box to light fitting, complete, all as specified and directed.
S & F of T5 18W LED tubes, 240V, complete, all as specified and directed.
S & F of LED batten suitable for T8 10W LED tubes, 240V, including neccesary electric connection with suitable size copper cable from junction box to light fitting, complete, all as specified and directed.
S & F of T8 10W LED tubes, 240V, complete, all as specified and directed.
S & F of LED 36W, Polaris III Recessaed/surface 2x2 tile, 240 V, complete, all as specified and directed. MODEL & MAKE: CAT part No.LCTRN-36-CDL of Crompton Greaves or equivalent of listed makes.
S & F of FLAME PROOF and WEATHER PROOF LED tube light fitting suitable for 1x16W/20W, 4 feet, body made out of cast aluminum alloy LM-6, epoxy painted with wire guard, reflector, flame proff clear glass along with complete accessories, prewired, CMRI certified for gas group and hardware, fixed to wall/ceiling with MS flat grouted in wall/ceiling including flameproof flexible conduit with wire from fitting to terminal point, dummy/gland, complete, all as specified and directed. MODEL & MAKE: CAT part No.FIAMMA II EXTN1L8-16/20 of Crompton Greaves or equivalent of listed makes.
S & F of LED Hi-bay light fitting 1 x 150 Watt, Box type, surface mounted, 230V, complete with all accessories, , internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable of suitable size (for Hangar), complete, all as specified and directed.
S & F of LED Area light fitting 1 x 160 Watt, Box type, surface mounted, 230V, complete with all accessories, , internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable of suitable size including MS angle for mounting of dispersal light and necessary PCC work (for Hangar/Dispersal area), complete, all as specified and directed.
S & F of Aviation Obstruction Light 2 x 12 Watt LED with red colour reflection, 240V, complete, all as specified and directed.
S & F of LED builing security light, 25W, IP65, 2409V, complete with all accessories, internally prewired and connecting up with twin core copper conductor of suitable size, complete, all as specified and directed. MODEL & MAKE: CAT part No.LSTS-25 CDL of Crompton Greaves or equivalent of listed makes.
S & F for sub main wiring with 4 runs of single core 10 Sqmm (Nominal area) FR-LSH PVC insulated unsheathed multi-stranded copper conductor cable concealed in wall LT 1100 Volts grade, drawn through in and including PVC conduit pipes of required size including earth continuity conductor using FR-LSH PVC insulated unsheathed copper conductor cable 1 run of size 10 Sqmm (Nominal area) connected to common earth dolly complete all as specified and as directed. NOTES: (1) 5 runs of 10 sqmm cable and one run of PVC conduit pipe shall be measured as one run length. (2) Cutting chases, making good disturbed surface shall be included in quoted lump sum of schedule 'A' Part-I and nothing extra shall be paid on this account.
S & F for sub main wiring with 2 runs of single core 6 Sqmm (Nominal area) FR-LSH PVC insulated unsheathed multi-stranded copper conductor cable LT 1100 Volts grade, drawn through in and including PVC conduit pipes of required size including earth continuity conductor using FR-LSH PVC insulated unsheathed copper conductor cable 1 run of size 6 Sqmm (Nominal area) connected to common earth dolly complete all as specified and as directed. NOTES: (1) Three runs of 6 sqmm cable and one run of PVC conduit pipe shall be measured as one run length. (2) Cutting chases, making good disturbed surface shall be included in quoted lump sum of schedule 'A' Part-I and nothing extra shall be paid on this account.
S & F for sub main wiring with 2 runs of single core 4 Sqmm (Nominal area) FR-LSH PVC insulated unsheathed multi-stranded copper conductor cable LT 1100 Volts grade, drawn through in and including PVC conduit pipes of required size including earth continuity conductor using FR-LSH PVC insulated unsheathed copper conductor cable 1 run of size 4 Sqmm (Nominal area) connected to common earth dolly complete all as specified and as directed. NOTES: (1) Three runs of 4 sqmm cable and one run of PVC conduit pipe shall be measured as one run length. (2) Cutting chases, making good disturbed surface shall be included in quoted lump sum of schedule 'A' Part-I and nothing extra shall be paid on this account.
S & F for MCB SP 6 to 32 Amps (C-Curve), breaking capacity 10 KA, 240 volts with cable connection and copper lugs complete all as specified and directed.
S & F for MCB SP 20 Amps (C-Curve), breaking capacity 10 KA, 240 volts with cable connection and copper lugs complete all as specified and directed.
S & F for MCB SPN 32 Amps (C-Curve), breaking capacity 10 KA, 240 volts with cable connection and copper lugs complete all as specified and directed.
S & F for MCB SPN 40 -63 Amps (C-Curve), breaking capacity 10 KA, 240 volts with cable connection and copper lugs complete all as specified and directed.
Supply, installation, testing and commissioning of advance maintenance free system based earthing comprising of following accessories: (a) Set of 04 Nos 3000mm long, 17.0 mm dia earth electrode made of 99.99% copper circular rod with connect copper strip and electrode with the help copper brazzing of incoming copper strip of size 25 X 3 mm of lenght as per site requirement upto bus bar and distance between each copper earth electrode is minimum 3 m. (b) Copper bus bar of size (300 X 25 X 6) mm act as test point connected with copper nuts and bolts with post insulators. (c) Poly propylene earth pit cover of size 300 X 300 mm (with safe working load 2000 kg) - 04 Nos (d) Copper bus bar of size (250 X 50 X 6) mm exothermically welded with main eath electrode. (e) Earth pit filled with earth enhancement compound / chemical (Magnesium sulphate) only min 75 Kgs /pit all as specified. (f) Required result of earthing less than 01 Ohm. If desired Ohmic value is not achieved than additional set of 01 No of 3000 mm long, 17 mm dia earth electrode made out of 99.9% copper rod with allied items, 01 X pit cover, 01 X bus bar as (d) above 75 kg of chemical shall be provided by contractor withoput extra cost to Govt. No price adjustment shall be made , if additional set is not required complete all as specified by the Engr-in-Charge. Note:- All including like excavtion and removing of 300 mm dia bore hole and trench between electrode and electrode bus bar.
INTERNAL WATER SUPPLY: M & L for 15 mm bore angular stop valve cast copper alloy, chromium plated, screwed down, high pressure with crutch or butterfly handle with long shank and cup, screwed for iron pipe complete all as specified and directed.
M & L for 15 mm dia concealed stop cock, cast copper alloy, chromium plated screwed down, high pressure, fancy type, chromium plated with long shank and cup , screwed both ends for iron pipe or for unions complete all as specified and as directed.
HANGER FLOOR / DISPERSAL AND PAVEMENT APRON / ROAD / PATH / CULVERT: M & L for 150mm (compacted thickness ) wet mix macadam (WMM) (in twi layers of 75mm each compacted separately ) manufactured in WMM plant. Each layer compacted separately (as per Table 400-12 and 400-13 of MORTH specifications) with crushed stone aggregates specified grading, spreading unsing sensor paver and consolidated to required gradient and camber complete all as specified and directed. If the water absorbtion value of coarse aggregate is greater than 2% the soundness test shall be carried out on the material deleivered at site.
M & L for Providing and laying Dry Lean Concrete (DLC) 150 mm thick having compressive strength not less than 7Mpa at 07 days (para 4.1 IRC:SP49-2014) for each consecutive group of 05 cubes. Individual strength of each cube must not be less than 5.5 Mpa at 7 days. DLC laid over prepared and laid WMM with coarse and fine aggregate conforming to IS 383 size of aggregate not exc 26.5mm (grading and other parameter as per table no 600-1 of MORTH specifications/ table IRC : SP-49-2014) mixed in batching planmt , transported to site and laid by sensor paver including spreading and compacting using double drum smooth wheeled roller 80-100 KN of ststic and vibratory capacity including necessary formwork finishing etc complete all as specified and as directed.
M & L for providing and laying 20mm thick pavement quality concrete (PQC) on min field Flexural strength of 45 Kg/SQCM lower control limit at 28 days in pavement slab usnig min 360 Kg of cement per Cum as per IRC 15-2011 (only 43 grade OPC must be used in PQC) mixed with non circular synthetic fiber reinforcement by mechanical means at the rate of 0.25% by weight of cement per cum of PQC. The max size of aggregate in PQC must be 31.5mm and gradtion as per table 600-3 MORTH, IRC SP 49 specifications, design mix mixed in batching plant trasported to site laid with sensor paver including bull nosing rounding off the edges including necessary formwork finishing etc all as specified and directed.
M & L for high density polythene film (transparent colour) in single layer of 400 Micron thickness virgin quality as per ASTMD 2103/IS 2508 laid with side and ovelapping not less than 300mm complete all as specified and directed.
M & L for providing machine pressed cement concrete M-25 with grey cement and no pigment as in kerb stone of size 450 x 300 x 150 mm conforming to IS, complete all as speicified and as directed.
M & L for Forming 25mm wide expansion joint in concrete slab for full depth of PQC. The joint be cleaned and filled with pre- moulded 25 mm thick compressible polyethylene closed cell type filler board as specified and applying closed cell, medium density, cross linked polyethylene foam backup rod of 30 mm dia over filler board and then priming top 15mm with approved primer and filling with polyurethane based sealant complying with BS-5212/ euivalent international code with min MAF +/- 30% having 10 year performance guarantee, applying masking tape on the edges of joints to prevent accidental spillage of sealant and removing the masking tape after filling of sealant as per the method specified by the manufacturer complete all as specified and directed.
M & L for Forming construction joint 28mm deep x 10mm wide using diamond cutter with closed cell, medium density, cross linked polyethene foam back up rod of 12mm dia, applying bond breaker tape on top of back rod for complete width of the joint, priming top 15mm with specified primer and fitting with poyurethane/polysuphide based sealant with min MAF +30% (with 10 years performance guarantee) and removing the masking tape on edge of joint to prevant accidential spillage of sealant and as specified and as per manufacutrer directions, complete all as specified and as directed.
M & L for Forming dummy/contraction joint using diamond cutter with initial saw cut with 3 mm blade soon after concrete set, upto a depth of 1/3rd to 1/4th thickness of slab, widening the first saw cut to 6 mm wide and 24 mm deep from top filling with closed cell, medium density , cross linked polyethylene foam backup rod of 8mm dia for concrete length of joint,priming top 15 mm with approved primer, applying masking tape on edges of joint to prevent accidental spillage of sealant and filling with polyurethane / polysulphide based sealant complying with BS-5212/ euivalent international code with min MAF +/- 30% having 10 year performance guarantee, applying masking tape on the edges of joints to prevent accidental spillage of sealant and removing the masking tape after filling of sealant as per the method specified by the manufacturer complete all as specified and directed.
M & L for providing GSB(Granular sub base) Grade-V of MORTH, IRC specifications, 300 mm thick in two layers n exc 15 cm thick watering, ramming/ rolling by tandem whell roller and finshed to logitudinal gradient (1:150) & traverse gradient (1:100) foe achieving field compaction at least to 98% of MDD (Max Dry density) of soil complete all as specified and as directed.
SEWAGE DISPOSAL: Construction of septic tank for 50 users complete all as specified and as shown on drawings.
Construction of soakage well for 50 users complete all as specified and as shown on drawings.
EXTERNAL WATER SUPPLY: M & L for construction of brick masonary valve pit of size 90 cm x 90 cm x 90 cm (internal dimensions) with one brick thick wall in cement mortar (1 : 4) on 100 mm thick PCC (1:4:8) D2 (using 40 mm graded broken stone aggregate) as in foundation lean concrete, including PCC (1:3:6) type C1 (using 20 mm graded crushed stone aggregate) as in beding and coping and 10 mm thick cement plaster in CM (1:4) internally and externally upto 15 cm below ground level providing valve pit 40 mm X 40 mm X 6 mm angle iron frame all round the fixed point by means of 04 Nos holdfast 150 mm long made out of flat iron 40 mm X 6 mm embedded in PCC block (1:2:4) type B1 (using 20 mm graded crushed stone aggregate) of size 250 mm X 200 mm X 150 mm including provision of hinges welded with Mild Steel cover 3 mm thick, MS handle of suitable and size welded with MS cover and suitable locking arrangement including 65 mm dia Godrej pad lock and 3 Nos. key and applying two coats synthetic enamel paint over a coat of red oxide primer on steel surface including necessary excavation and earth work in soft/loose soil complete all as specified and directed.
M & L for Cutting to existing 100 mm dia CI pipe lines in position for insertion of new Tee of size 100 x 100 x 80 mm dia for branch connection complete all as specified and directed.
EXTERNAL ELECTRIFICATION: M & L for boring of holes carefully under road / pavement / hard standing by trenches using ultra sound technique and necessary machine without dameging the existing road and getting out in any type of soil and disposal of soil to a distance not exceeding 50 m from the site of work with and including 40 mm dia GI pipe of light grade complete all as specified and as directed.
Supply, installation, testing and commissioning of double door, LT Panel Board, indoor type of Suitable size , IP 55 as per IS 13947, weather and vermin proof, canopy on top made out of 2 mm thick CRCA sheet with all necessary frame work with angle iron of required size not less than 50 mm x 50 mm x 5 mm, cubical type duly powder coated paint including 7 tank treatment process over a coat of red oxide zinc chrome primer and 800 Amps 04 Nos aluminium bus bar for three phase and neutral duly PVC laminated including internal wiring by FR-LSH grade multistranded PVC insulated copper conductor of size not less than 1.5 sqmm duly marked, plate for fixing MCCB, MCB etc with the following accessories and provision of PCC (1:3:6) type C1 (using 20mm graded stone aggregate) as foundation of bedding upto a height of 30 cm above gorund level complete all as specified and as directed. INCOMMING (a) LT switch gear 440 volts 3 phase, 4 wire 50 cycles, cubical or truck type complete with air circuit breaker, overload protection, no volt release with necessary CTs meter and cable boxes of rating upto 630 amps. OUTGOING (b) MCCB 4 pole, 415 V, 320 Amps 35 KA - 01 No (c) MCCB 4 pole, 415 V, 400 Amps 35 KA, - 01 No (d) Digital Ammeter with CTs of capacity 0-800 Amps - 01 No (e) Digital Voltmeter with PTs of capacity 0-1100 Volts - 01 No (g) LED indicator lamp RYB - 01 Set
Supply, installation, testing and commissioning of double door, LT feeder pillar box, outdoor type of suitble size , IP 55 as per IS 13947, weather and vermin proof, canopy on top made out of 3.15 mm thick CRCA sheet with all necessary frame work with angle iron of required size not less than 50 mm x 50 mm x 5 mm, cubical type duly powder coated paint including 7 tank treatment process over a coat of red oxide zinc chrome primer and 800 Amps 04 Nos aluminium bus bar for three phase and neutral duly PVC laminated including internal wiring by FR-LSH grade multistranded PVC insulated copper conductor of size not less than 1.5 sqmm duly marked, plate for fixing MCCB, MCB etc with the following accessories and provision of PCC (1:3:6) type C1 (using 20mm graded stone aggregate) as foundation of bedding upto a height of 30 cm above gorund level complete all as specified and as directed. INCOMMING (a) MCCB 4 pole, 415 V,400 Amps 35 KA - 01 No OUTGOING (a) MCCB 4 pole, 415 V, 250 Amps 35 KA - 01 No (b) MCCB 4 pole, 415 V, 160 Amps 35 KA, - 01 No (c) On load Change over switch 415 V in sheet metal enclosure 4 pole of capacity 400 Amps - 01 No (d) Digital Ammeter with CTs of capacity 0-630 Amps - 01 No (e) Digital Voltmeter with PTs of capacity 0-1100 Volts - 01 No (g) LED indicator lamp RYB - 01 Set
Supply, installation, testing and commissioning of double door, LT feeder pillar box, outdoor type of suitable size , IP 55 as per IS 13947, weather and vermin proof, canopy on top made out of 3.15 mm thick CRCA sheet with all necessary frame work with angle iron of required size not less than 50 mm x 50 mm x 5 mm, cubical type duly powder coated paint including 7 tank treatment process over a coat of red oxide zinc chrome primer and 600 Amps 04 Nos aluminium bus bar for three phase and neutral duly PVC laminated including internal wiring by FR-LSH grade multistranded PVC insulated copper conductor of size not less than 1.5 sqmm duly marked, plate for fixing MCCB, MCB etc with the following accessories and provision of PCC (1:3:6) type C1 (using 20mm graded stone aggregate) as foundation of bedding upto a height of 30 cm above gorund level complete all as specified and as directed. INCOMMING (a) MCCB 4 pole, 415 V, 400 Amps 35 KA - 01 No OUTGOING (a) MCCB 4 pole, 415 V, 100 Amps 25 KA - 01 No (b) MCCB 4 pole, 415 V, 100 Amps 25 KA, - 01 No (c) MCCB 4 pole, 415 V, 250 Amps 35 KA, - 01 No (d) Digital Ammeter with CTs of capacity 0-500 Amps - 01 No (e) Digital Voltmeter with PTs of capacity 0-1100 Volts - 01 No (g) LED indicator lamp RYB - 01 Set
Supply, installation, testing and commissioning of double door, LT feeder pillar box, outdoor type of suitable size, IP 55 as per IS 13947, weather and vermin proof, canopy on top made out of 3.15 mm thick CRCA sheet with all necessary frame work with angle iron of required size not less than 50 mm x 50 mm x 5 mm, cubical type duly powder coated paint including 7 tank treatment process over a coat of red oxide zinc chrome primer and 450 Amps 04 Nos aluminium bus bar for three phase and neutral duly PVC laminated including internal wiring by FR-LSH grade multistranded PVC insulated copper conductor of size not less than 1.5 sqmm duly marked, plate for fixing MCCB, MCB etc with the following accessories and provision of PCC (1:3:6) type C1 (using 20mm graded stone aggregate) as foundation of bedding upto a height of 30 cm above gorund level complete all as specified and as directed. INCOMMING (a) MCCB 4 pole, 415 V, 320 Amps 35 KA - 01 No OUTGOING (a) MCCB 4 pole, 415 V, 63 Amps 25 KA - 01 No (b) MCCB 4 pole, 415 V, 63 Amps 25 KA, - 01 No (c) MCCB 4 pole, 415 V, 250 Amps 35 KA, - 01 No (d) Digital Ammeter with CTs of capacity 0-320 Amps - 01 No (e) Digital Voltmeter with PTs of capacity 0-1100 Volts - 01 No (f) Digital Voltmeter with PTs of capacity 0-1100 Volts - 01 No (g) LED indicator lamp RYB - 01 Set
DG SET Supply, installation, commissioning and testing of Silent diesel engine driven generating set 415 volts, 3 phase 4 wire, engine as per IS: 10001/10002, ISO - 3046, BS - 5514, DIN - 6271 of capacity 320 KVA, rated current 450 Amp, 4 Stroke, designed to run continuously at 1500 RPM complete with the following accessories:- (A) Diesel Engine:- (i) Radiator cooling (ii) Radiator fan with guard (iii) Fly wheel with starter ring (iv) Dry type air cleaner (v) Vacuum indicator (vi) Mechenical governor (vii) Exhaust silencer (viii) Fuel filter (ix) Inline fuel pump (x) Water pump (xi) Lub oil filter (xii) 24 V electric start system complete with starter, battery charging alternator (xiii) Engine control panel consisting of starting key switch, lub oil pressure gauge, ammeter safety shut down system for low lube oil pressure and coolant temperature engine maintenance manual with spare parts list. (xiv) Exhaust pipe / stack upto 6m from top of shed with insulation structural steel required for supporting exhaust pipe / stack, fixed supports, sliding supports etc. (xv) First fill of lube oil and coolant. (xvi) Residential silencer eith cladding & supports
Srl Item No 15.46 (Contd.../) (E) Accessories: (i) Base frame of sturdy design - 01 No (ii) Fuel tank rectangle shape capacity suitable for running 12 hrs on full load. (iii) Battery 12 V not less than 100 AH maintenance free with leads & connecting accessoies - 02 Nos (F) Spare parts & tools: (i) Rotary pump diseal with 3 mt hose - 01 set (ii) Box spanner set complete with all sizes (iii) Oil filter set - 02 Nos (iv) Air filter complete with element - 02 Nos (v) Fuel filter set - 02 Nos (vi) AVR - 01 No (vii) Insulated rubber matt of size 900mm x 1500 mm x 3 mm thick - 02 Nos (viii) Jerrican MS sheet of required capacity - 02 Nos Note : (i) PCC foundation of adequate/required size extending 500mm all round more than size of DG set, as per manufacturer design. (ii) DG set shall be tested as type test routine as per IS in presence of GE/his rep. (iii) Contractor shall submit QAP ( quality assurance programme ) after the 15 days from placement of order for DG set testing to factory. DG set shall be dispatch after inspection clearance by inspecting officer. (iv) The contractor shall get approval of GE for the make of DG set they plan to procure. (v) Prior manufacturing the general arrangement drawing design details of the DG set and AMF panel shall be got approved by GE.
Supply, fixing, testing and commissioning of air curtain of 4 feet long complete all as specified and as directed.
LIGHTENING PROTECTION: Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised strip of size 32 mm x 6 mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on complete all as specified and as directed.
S & F for voltage stabilizer automatic operation, single phase, naturally air cooled, indoor type and designed for input variation between 170 Volt to 250 Volt with and output voltage stabilzed at 230V with accuracy + 2.5% and capacity 1 KVA with time delay relay, under /over voltage relay and overload relay complete all as specified and as directed.
S & F for voltage stabilizer automatic operation, single phase, naturally air cooled, indoor type and designed for input variation between 170 Volt to 250 Volt with and output voltage stabilzed at 230V with accuracy + 2.5% and capacity 4 KVA with time delay relay, under /over voltage relay and overload relay complete all as specified and as directed.
S & F for voltage stabilizer automatic operation, single phase, naturally air cooled, indoor type and designed for input variation between 170 Volt to 250 Volt with and output voltage stabilzed at 230V with accuracy + 2.5% and capacity 5 KVA with time delay relay, under /over voltage relay and overload relay complete all as specified and as directed.
EOT CRANE: Design, supply, testing & installation of ordinary EOT crane, double girder having cross span of 26.0m, long travel 70m and weight lifting capacity of 2 Ton considering following conditions:- (i) Hook height of crane from FFL : 7.00m (ii) The operation and micro speed of crane should be as following:- (a) Main Hoist : 3-4m/min. (b) Micro in main hoist : 0.3m/min. (c) Cross travel : 3-5m/min. (d) Micro in cross travel : 0.3m/min. (e) Long travel : 8-10m/min. (f) Micro in long travel: 0.8m/min. (iii) EOT crane shall be ordinary type and shall comply with the safety specifications given in STEC Pamphlet No.7. (iv) Design of crane and proof checking of design from any of Government Chartered Engineers shall be submitted within 02 months from the acceptance of the tender. NOTES: (1) Crane is to be installed in Hangar of size 70m(L) x 86m(W) x 11m (H). (2) One side of the crane has to move on rails fixed over gantry girder over brackets and other side on the rails sunk in the hangar floor.
DEMOLITION / DISMANTLING: Taking down sub main wiring of any description complete all as specified and as directed.
Taking down MCB of any description complete all as specified and as directed.
Taking down earthing of any description complete all as specified and as directed.
Taking down cable of any description complete all as specified and as directed.
Note: Schedule of credit (SCHEDULE 'A' PART- XVI) amount of Rs.95,560.00 shall be deducted from the total quoted amount of BOQ.
City Promoter and Buildwell Pvt. Ltd.
Som Projects Pvt Ltd
Pennar Industries Limited
NSC Projects Pvt. Ltd.
surendra infrastructure pvt ltd
B D Raizada Projects Pvt Ltd
Komal Buildcon Pvt. Ltd.
AKM CONSTRUCTION AND ENGINEERING LLP
PUSHKARRAJ CONSTRUCTION PRIVATE LIMITED
Hariom Projects Pvt Ltd
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.06 MB
Download all tender documents and submit your bid