Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹79.7 LAccepted-AOC 13 29 304 3RD FLOOR EAST PATEL NAGAR OPP SIDDHARTHA HOTEL NEW DELHI 08 | NEW DELHI | NEW DELHI | DELHI | 110008 | 1 | Accepted-AOC Being lowest and reasonable rates | |
| 2 | 2₹89.8 L+₹10.0 L (12.6%)Rejected-Finance 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | DELHI CANTT | NEW DELHI | DELHI | 110010 | 2 | Rejected-Finance Not being lowest | |
| 3 | 3₹90.8 L+₹11.0 L (13.8%)Rejected-Finance SHOP NO 33 GOPI NATH BAZAR DELHI CANTT 10 | DELHI CANTT | NEW DELHI | DELHI | 110010 | 3 | Rejected-Finance Not being lowest | |
| 4 | 4₹94.6 L+₹14.8 L (18.6%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | 4 | Rejected-Finance Not being lowest | |
| 5 | 5₹95.9 L+₹16.2 L (20.3%)Rejected-Finance WZ 1000 B NANGAL RAYA PANKHA ROAD NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | 5 | Rejected-Finance Not being lowest |
Tender Value
Refer Docs
EMD Value
₹1.9 L
Closing Date
31 Oct 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE U
HQ CWE U Delhi Cantt 110010
PROVN OF EXTERNAL ELECT SUPPLY FOR NCN BLDG AT NSB II UNDER GE U ELECT SUPPLY DELHI CANTT 10
2020_MES_377000_1
89035/CWE(U)/D-15/2020-21/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Delhi Cantt
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
Yes
GE U Electric Supply
₹1.9 L
Yes
27 Nov 2020
16 Sept 2020
2 Nov 2020
16 Sept 2020
31 Oct 2020
26 Oct 2020
60 days
Amount
Excavation in trenches in soft and loose soil n.exc 1.5 m wide and n.exc. 1.5 mtr in depth for laying and taking out electric power cable n exc. 10 sqm on plan and n exc 1.5 m in depth and getting out complete all as specified and as directed.
All as per Sl. No. 1 above but in hard rocks.
M&L for returing, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and as directed.
M&L for removing excavated material n exc. 50m and depostiting where directed at a level n exc. 1.5m above the starting point in soils complete all as specified and as directed.
M & L for sand as in sand cushioning to underground PVC cable including punning down of sand layer complete all as specified and as directed. Note : For measurement purpose, only punned sand shall be measured and paid for.
Supply and laying unreinforced precast concrete cable cover, class HVP Type -1 with peak, size 300mm x 180mm x 40 mm. compete all as specified and as directed.
M&L for boring of holes under road/pavement/hard standing by trenchless technology using ultra sound technique and necessary machine including material and labour for HDPE pipe of 160 mm dia suitable for 04 Kg/sqcm working pressure, wall thickness of pipe not less than 6.5 mm complete all as specified and as directed.
Supply and lay cable XLPE insulated screened PVC bedded,galvinised steel strip or wire armoured, electric power cables (heavy duty) 11000 Volt grade with stranded aluminium conductor of size 185 Sqmm 3 core complete all as specified and as directed.
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable for indoor terminal heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 185 sqmm complete all as specified and as directed.
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable for outdoor terminal heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 185 sqmm complete all as specified and as directed.
Supply, jointing and testing, straight through joint, heat shrink type, suitable for HT, 11 KV (E) XLPE cables for aluminium stranded conductors cable of size 185 Sqmm ,3 core complete with jointing material and accessories complete all as specified and as directed.
M& L for earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized iron earth strip 32 x 6 mm as earthing lead by means of bolts and nuts, checknuts and washers of galvanized iron electric arc welding all joints all as specified and shown in electrical plate No. 3 of SSR part - I connected to earthing test point including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia light grade for protection of earth electrode 20 mm dia for watering and tested on completion complete all as specified and as directed.
Supply & install ,testing and commissioning of transformer step down, outdoor type copper wound 11KV/433 Volts (at no load) AC 3 phase 50 Hz 1000 KVA capacity, core type, oil immersed naturally cooled, oil natural air natural (ON/AN) , with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYn-11 with neutral brought out on secondry side (LV) and having taping at +10% in steps of 2.5% on HV side to be changed by means of hand operated off load tap changer gear. The maximum temperature rise shall not exceed 40 degree celsius in oil and 45 degree celsius in HV/LV winding when measured by resistance method after continuous full load run on an ambient temp of 40 degree celsius. Transformer shall be of BOLTLESS core design. Transformer shall be double wound, core type with low loss, non ageing, high permeability prime grade CRGO with M4 grade or better, perfectly insulated and clamped to minimize noise and vibrations complete all as specified and as directed. The transformer shall be IS/IEC 60076 and as per IS-1180 Part - I marked and shall comprise of the following :-
(a) One cable box on HT side (Primary side) consisting of three nos porcelain bushing with copper rods, complete with nuts and washer , with cable glands suitable for reception/taking out 3 core 120 Sqmm, HT 11000 volts grade, XLPE insulated and PVC sheathed, heavy duty , armoured cables including jointing materials complete.
(b) One cable box on LT side(secondary side) consisting of four nos porcelain bushing with copper rods,for connected bus ducts complete with nuts and washers, with cable glands suitable for reception connecting of sandwich type bus truncking system of capacity 2200 Amps including jointing materials complete.
(c ) conservator with filter type drain valve and oil level guage.
(d) De-hydrating breather with first fill of dehydrating agent (Silica Gel).
(e) Explosive vent, Thermometer pocket on tank cover, oil level guage, Oil drain filter valve, Lifting lugs,oil filling hole with cap/plug with connection plate complete, Air release valve plug and four nos plain solid cast steel detachable rollers.
(f) One no 100 mm dia, dial type thermometer, vapour pressure type, having range 0-120 degree celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device.
(g) Two earthing terminals on tank cover to facilitate fixing of 50x6mm galvanised iron earth strip for earthing of body.
(h) Rating plate and terminal marking plate.
(j) Extra bushing for neutral in the LT cable box for providing independent set of earthing for neutral.
(k) First fill of new and unused transformer oil, IS-335 marked, filtered and tested upto 40 KV dielectric strength at 2.5 mm air gap between testing electrodes.
(l) Providing adequate size and nos of channels, embeded in floor, for movement of transformer.
(m) Tranformer losses shall not exceed the loses mentioned in IS: 1180 Part - I with energy Effeciency level - II.
(n) Oil temperator indicator , winding temperature indicator, marshilling box single window, double flit buchhol relay with alarm and trip contact including connection to existing RMU relay with PVC insulated PVC sheathed cable galvanized steel strip or wire armoured electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm 10 core 1100 volts grade.
(o) construction of platform for installation of transformer 1000 KVA as per recommendation of OEM, including excavation and earth work at site complete.
Supply and installation, testing and commissioning of LT panel board powder coated, CPRI approved 440V, AC 3 Phase , 50 Hz factory made outdoor type, floor mounted double front execution, made out of 3.15 mm thick MS sheet with arrangement for bus truncking entry from top of the panel, CRCA with lifting angle 50x50x6mm base of 450mm height. Sandwich type bus trunking of 2000 Amps aluminium entry from top of the panel as incoming and Cable of size upto 1000 sqmm single core seven run out from bottom conforming to degree of protection IP-65 ,gasketing of PU foam gasket ensuring IP protection with temperature with stand by capacity 40 to 80 degree celsius with powder coating and locking arrangements. LT panel mounted on 02 Nos, Brick pillars including excavation and earth work (PCC 1:2:4) type B1, brick work 1:4 and 15mm plaster of cement (1:6). The LT Panel shall be pre-wired proper spacing to accommodate all accessories, cable connection with suitable size of lugs /thimbles and cable glands comprising of the following (a) Aluminium bus bar 3 phase and neutral 2200 Amps equal (4 run) ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set. (b) ACB 440 Volts 3 phase 4 wire 50 Hz complete with adjustable load protection, no-volt release with microprocesser release EDO neccessory CTs, meter and cable boxes of rating 2000 Amps, 65 KA - 01 No.(Incoming).
(c) ACB 440 Volts 3 phase 4 wire 50 Hz complete with adjustable load protection, no-volt release with microprocesser release EDO neccessory CTs, meter and cable boxes of rating 1250 Amps - 02 Nos 65 KA..(O/G). (d ) MCCB 4 pole 100 Amps 50 Hz breaking capacity 25 KA at 415 volt - 01 No. (e) Multifunction meter with communication ports RS 485/232, 5 display, class-1. - 01 set (f) Indication lamps R,Y,B LED type.
Supply, Laying, connecting, testing and commissioning of LT cable of PVC sheathed XLPE armoured heavy duty aluminium conductor 1100 V graded 1000 sqmm single core complete all as specified and directed.
Supply and fix sandwich type bus truncking system with aluminium busbar 2000 Amps, 50 KA breaking capacity, IP 65 protection outdoor type complete all as specified and as directed. Note : Rate quoted are inclusive of the cost of end connection at Transformer/LT panel Horizontal/vertical bends.
Supply and laying burnt bricks Sub Class 'B' bricks locally available laid length of brick parallel to the length of cable in three stage for portection to LT cable complete all as specified and as directed.
M&L for danger notice board of 1.6 mm thick mild steel,vitreous enamelled white with letters,figures and conventional skull and bones in signal red colour and fixed with MS clamps,bolts and nuts of approved size for HT 25 x 20 CM size complete all as specified and as directed.
M&L for PCC in foundation filling and mass concrete type D2 (1:4:8) using 40 mm grded aggregate for foundation complete all as specified and as directed.
M& L for PCC type B1 (1:2:4) using 20 mm graded aggregate including use and waste of formwork complete all as specified and as directed.
M&L for brick work with Sub Class 'B' bricks straight OR curved on plan exc 6 M mean radius built in cement morter 1:6 complete all as specified and as directed.
M &L for plaster, hacking for keys, scrubbing down with water etc and rendering 10 mm thick in cement mortar 1 : 4 on fair faces of brick work or concrete surfaces finished even and smooth (without using extra cement) complete all as specified and as directed.
Supply and fixing framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc. n exc 10 kg each brackets, conforming to Fe.290.Gde-E-165 and grouted in ground with PCC type B1 (1:2:4) using 20 mm graded aggregate for pedestal of angle at site for fencing to sub station/RMU/BUS DUCT and hinged for gate complete all as specified and as directed NOTE :- The cost of Excavation and earth work , Brick work and PCC shall be measured and paid for seperately under respective item of this BOQ.
Supply and fixing 4mm dia galvanised steel wire, 80x40mm mesh, made up into mattresses or cages, lapped, wired and laid in position, including closing after filling complete all as specified and as directed.
Supply and laying under road crosing/hardstanding for protection to cable, HDPE pipe of 160 mm dia suitable for 04 Kg/cm working pressure. Wall thickness of pipe not less than 6.5 mm complete all as specified and as directed.
Supply and installation , testing and commissioning of 11 KV, 630 Amps, 21 KA/3 sec outdoor type Ring main unit IP 54 protection plug in type extensible on one side SF 6 gas insulated two incoming and three outgoing (5 way ) with metering plate form mounted compact switch gear consisting of 02 Nos load break switch as incomer and 03 Nos outgoing VCBs , all live parts, bus bars VCB will be enclosed in robotically/manual welded minimum 2 mm thick stainless steel tank filled with SF 6 gas IP 67 Degree of protection and tested for internal arc 20 KA/1 sec as per latest IEC 62271-200 complete installed on plateform as recommended by OEM, including the cost of PCC foundation for placing of RMU on plinth complete all as specified and as directed. The unit shall include the following with all necessary standard fitting required at site : -
(A) Incoming Load Break Module - 02 Nos each switching unit shall be designed as a three position switch. This three function switch combines the functions of switch disconnector and earthing switch cables switch 12 KV, 630 Amp, 21 KA - 01 Set. Snap action mechanism for motorised and manual(Both) operation with integrated earthing switch - 01 Nos. Cable bushing 630 Amp standard C bushing - 01. Fault passage indicator, On(N-1) load break switch where n= no of load break switch >>s/c & E/F FPI with digital display to be added for detection of cable fault. ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01. Capacitive voltage indication fixed type LED display - 01. ON, OFF, TRIP mechanical indication on the front mimic of the panel - 01. Cable box for termination of cable up to 1 No. x 185 sq.mm - 01. Cable cover standard - 01. Set of 12kV Cable Termination Boots - 01. Cable entry bottom, front - 01
(B) (i) Out going VCBs - 03 No consisting of following - function unit consisting of vaccum circuit breaker in combination with a three position switch. The three position switch fulfills the operation of the disconnector function and earthing function circuits breaker unit is equipped with an over current transformer for the protection of distribution Transformer/circuit vaccum circuit breaker 12 KV, not less than 400 A, 21 KA - 01. Spring assisted closing with stored Energy triping mechanism for motorised operation with integrated earthing switch - 01. live cable LED indicators through capacitor voltage dividers mounted on the bushings push button for breaker trip - 01 sec O/C + E/F self powered numerical protection relay with low and High set for Over current and earth fault Relay should have facility to display the maximum loaded phase current also current also relay shall record minimum 5 fault records with time stamping - 01 Alarm trip indication 6 window anuciator for transformer faults Mechanical ON/OFF/EARTH indication -01. Auxliary contacts on load switch are 1 No+2NC & Auxiliary conract on earth switch is 1 No+ 1NC-01. Self powered electronic numerical protection relay providing 3 over-currents & 1 E/F protection - 01, shunt trip coil 24 V DC-01 capactive voltage indication fixed type LED display -01 ON/OFF/Trip mechanical indication on the front mimic of panel-01 cable box for termination boots-01. Metering Equipment incl. 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), 01 x Tri-VectorMeter (Acc.Cl.0.5) Auxliary relay for transformer protection -06 Nos.
(B) (ii) Out going VCBs - 03 No, One consisting of CT 100/1 -5p10.2.5VA- 03 and other two consisting of CT 150/1 -5p10.2.5VA- 06.
(C ) Additional equipment deliverd separately or mounted seperatly, Bus connected with battery charger and inbuilt battries for motor power supply-01 (i) PT ratio 11KV/3/110/v3, 100 VA, 0.5 class for measurement with volts meter (ii) Auxliary transformer of 11KV/230V, 1 KVA for powering the motors and battery charger (iii ) 24 V DC battery charger and battries for motor power supply. Standard mano meter -01, Operating handle - 02 , cable clamping provision(standard)-01 Operation and maintance manual - o1, installation and commissioning manual - 01
Note :- (a) Cost of PCC works for placing RMU on plinth is deemed to be included in the cost, Height of plinth shall not be less than 0.45 mtrs from ground level. (b)The above module consisting of two Load break Switch and 03 VCBs shall be alligned appropriately and must have electrical and mechanical interlocking as per latest electrical safety norms including installation on plateform as recommended by OEM complete.
Supply and installation , testing and commissioning of 11 KV, 630 Amps, 21 KA/3 sec outdoor type Ring main unit IP 54 protection plug in type extensible on one side SF 6 gas insulated two incoming and one outgoing (3 way ) with metering plate form mounted compact switch gear consisting of 02 Nos load break switch as incommer and 01 Nos outgoing VCBs , all live parts, bus bars VCB will be enclosed in robotically/manual welded minimum 2 mm thick stainless steel tank filled with SF 6 gas IP 67 Degree of protection and tested for internal arc 20 KA/1 sec as per latest IEC 62271-200 complete installed on plateform as recommended by OEM, including the cost of PCC foundation for placing of RMU on plinth complete all as specified and as directed. The unit shall include the following with all necessary standard fitting required at site : -
(A) Incoming Load Break Module - 02 Nos each switching unit shall be designed as a three position switch. This three function switch combines the functions of switch disconnector and earthing switch cables switch 12 KV, 630 Amp, 21 KA - 01 Set. Snap action mechanism for motorised and manual(Both) operation with integrated earthing switch - 01 Nos. Cable bushing 630 Amp standard C bushing - 01. Fault passage indicator, On(N-1) load break switch where n= no of load break switch >>s/c & E/F FPI with digital display to be added for detection of cable fault. ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01. Capacitive voltage indication fixed type LED display - 01. ON, OFF, TRIP mechanical indication on the front mimic of the panel - 01. Cable box for termination of cable up to 1 No. x 185 sq.mm - 01. Cable cover standard - 01. Set of 12kV Cable Termination Boots - 01. Cable entry bottom, front - 01
(B) (i) Out going VCBs - 01 No consisting of following - function unit consist of vaccum circuit breaker in combination with a three position switch. The three position switch fulfills the operation of the disconnector function and earthing function circuits breaker unit is equipped with an over current transformer for the protection of distribution Transformer/circuit vaccum circuit breaker 12 KV, not less than 400 A, 21 KA - 01. Spring assisted closing with stored Energy triping mechanism for motorised operation with integrated earthing switch - 01. Live cable LED indicators through capacitor voltage dividers mounted on the bushings push button for breaker trip - 01 sec O/C + E/F self powered numerical protection relay with low and High set for Over current and earth fault Relay should have facility to display the maximum loaded phase current also relay shall record minimum 5 fault records with time stamping - 01 Alarm trip indication 6 window anuciator for transformer faults Mechanical ON/OFF/EARTH indication -01. Auxliary contacts on load switch are 1 No+2NC & Auxiliary contact on earth switch is 1 No+ 1NC-01. Self powered electronic numerical protection relay providing 3 over-currents & 1 E/F protection - 01, shunt trip coil 24 V DC-01 capactive voltage indication fixed type LED display -01 ON/OFF/Trip mechanical indication on the front mimic of panel-01 cable box for termination boots-01.
Metering Equipment incl. 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), 01 x Tri-VectorMeter (Acc.Cl.0.5) for measuring of PF,KVAR,KVA, KWH ,frequency, voltage with accuracy 1.0 for avtive energy, Auxliary relay for transformer protection -06. The relay having faciliate to Transformer protection and connected with buchhol relay of 1000 KVA Transformer complete all as specified and directed. (B) (ii) Out going VCBs - 01 No, One consisting of CT 100/1 -5p10.2.5VA- 03.
(C) Additional equipment deliverd separately or mounted separately, Bus connected with battery charger and inbuilt batteries for motor power supply-01 (i) PT ratio 11KV/3/110/v3, 100 va, 0.5 class for measurement with volts meter(ii) Auxliary transformer of 11KV/230V, 1 KVA for powering the motors and battery charger (iii ) 24 V DC battery charger and batteries for motor power supply. Standard mano meter -01, Operating handle - 02 , cable clamping provision(standard)-01 Operation and maintenance manual - o1, installation and commissioning manual - 01, cost of PCC works for placing RMU on plinth is deemed to be included in the cost, Height of plinth shall not be less than 0.45 mtrs from ground level.
NOTE :- (a)The above module consisting of two Load break Switch and 01 VCB shall be aligned appropriately and must have electrical and mechanical interlocking as per latest electrical safety norms including installation on plateform as recommended by OEM complete.
Supplying, installing, testing and commissioning of sheet steel clad encloser HT 11 KV Indoor type, dust & vermin proof, motorised, as well as manually charged, fully interlocked, horizontal draw out and isolation type floor mounted, 12 KV grade (Or nearest higher) arc-proof Draw-Out Vacuum Circuit Breaker (VCB) switch gear, rated for 11kV, 630Amp, internal arc not less than 25kA/3-sec, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR not less than – 25 kA for 1sec repturing capacity both side extendable type complete as per IEC 62271-200 and IS- 1311, Accessibility Class LSC2B-PM Class, with all standard accessories and metering equipments complete all as specified and as directed and comprising following : -
(i) 11kV, 630Amp, 25kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 01 Nos. encapsulated vacuum bottles of same make as of circuit breaker, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC)
(ii) Current Transformers 11kV, 100/1-1, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Core3: Class PS-X - Set of 03nos. The 'PS' core will be of suitable knee point voltage and ratio so as to succesfully implement Transformer Differential protection scheme for the upstream power transformer.
(iii) Potential Transformers, rear and bottom Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 25VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - Set of 01nos.
(iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 03CT+01PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (1) directional over-current or earth-fault in any of the three phases, (2) negative sequence currents due to line-to-line or conductor-break faults, (3) residual and three-phase under-voltages/over-voltages (4) circuit-breaker-failure alarm, (5) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage etc. and display the same locally on a built-in back-lit LCD screen as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs. TCP/IP based WebHMI shall be integrated part of relay for remote setting without requiring any special relay software.
(v) Metering Equipment including 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), 01 x Tri-VectorMeter (Acc.Cl.0.5) for measuring of PF,KVAR,KVA, KWH ,frequency, voltage with accuracy 1.0 for active energy.
(vi) Indications - LED for Breaker ON/OFF/TRIP/Spring-Charged/R-Y-B, 08-Window Annunciator with hooter
(vii) Control Equipment incl. 01 x TNC Switch, 01 x Emergency Trip Push Button, MCBs for AC/DC isolation as required
(viii) Other accessories including Space Heater with thermostat for breaker, busbar, LV panel and cable chamber, 3-Pin socket with switch, CFL lamp.
NOTE : - The VCB should connected with existing VCB panel of Make : CG/Andrew Yule. The cost of connecting of VCB with existing bus bar and making good is deemed to included in the cost of VCB.
M P TYAGI ENGINEERS AND CONTRACTORS
M/s JAIMAA ASSOCIATES
Vijay Electricals
mayur enterprises
Chauhan Associates
Buddham Builders
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .