Purchasing, Testing, Designing, Erection and commissioning of Emergency Warning System at Beas Dam Site.
2024_BBMB_181496_1
01/EWS/BBMB/2023-24
Open Tender
Job Works
Tender cum Auction
150 days
Beas Dam Site
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
Yes
Bhakra Beas Management Board
₹4.3 L
Yes
6 Mar 2024
12 Jan 2024
13 Feb 2024
12 Jan 2024
12 Feb 2024
12 Jan 2024
Amount
For Supply ,Testing, Designing, Erection and commissioning of Control Room for Early Warning Software Monitoring Display (43” LED Full HD Display) Should be reputed brand Integration with Control Station B/W Siren Station An Early Warning Mobile app and web based Software controlling system. The software should be suitable for controls upto 100+ sirens, the system can be expand to accommodate changing needs.
For Supply ,Testing, Designing, Erection and commissioning of Autonomy of the System The system should have Solar Panels of Sufficient Rating to be autonomous for minimum three days i.e. the system should have sufficient storage capacity in the shape of batteries charge controller and other accessories required for successful operation of the system in case of non- availability of sunlight and the system operate for minimum five times in a day. Solar panel with 24/12V DC output with required W/VA capacity to be decided by the vendor. The System should be capable of bearing the load of the Local Control System for 3 sunless days in a row. Batteries are to be mounted in the same pole/placed on foundations in a cabinet having IP 65 suitable for open environment. Each Siren should have 24/12V batteries inside controller, to ensure dissemination of warning messages in case of failure of AC mains power. Battery Backup should be sufficient days of idle running + minimum operations (5 messages of 6 duration each). The Solar Panel shall conform to IEC 61215 (Latest edition certificate) and IEC 61730. 2023. Approved Make: Vikram / Waaree / REIL /TATA Solar Reputed Make
For Supply ,Testing, Designing, Erection and commissioning of Electronic Siren up to 2 km The Sirens should be omni directional and the system audio output must be of high quality and distinctly audible upto 2 Km from Siren/Hooter point for Considering ambient noise, system audio output must be at least 3dB above the ambient noise conditions. High Power Electronic Siren System each with a minimum acoustic power of 120 DB (1.4 km meter for Siren & 1.2 km for PA System). The 24/12 V batteries inside the siren controller must be charged by regular 220V AC mains and should have the option for connecting to Solar Panel without the need of an external UPS or inverter. Siren Controller box must be IP65 compliant (or better). • Operating Temperature: -10 to +60deg C The system must have a capability to run continuously for 15minutes without overheating/failure. The system must adhere to EN 60065 certification for compliance to highest European Safety Standards and ISO 9001:2008 certification of product design and manufacturing. Equivalent International i.e., UL, FEMA and Indian Certifications are also acceptable. Standby mode current should not exceed 60mA. Dual feature of Control Remotely from Control Room and Locally at the Siren Controller box for authorized user. Siren Speaker Array must be at ground potential. Lighting arrestors must be provided. There must be provision expanding/increasing the horns in future.
For Supply ,Testing, Designing, Erection and commissioning of Earthing of local station For the safety of all the installed Electrical and Electronic equipment, 02 meter 2 nos. at each location earthing must be done by the agency. Earthing is to be provided as per IS 3043:1996, ISI Standard Specification No: 732-1963 or latest edition.
For Supply ,Testing, Designing, Erection and commissioning of Feedback Unit for status of Local Stations at Control Room All feedbacks (on, off, trip, faults etc) of the equipment installed for Alert, Information and Direct system should communicate to main Control room SCADA.
For Supply ,Testing, Designing, Erection and commissioning of Interface system for Radio and 3G/4G link on wireless communication through dual SIM and associated software at control room A suitable interface/communication system of reputed make should be installed in the Local Station with the capability of operating over 3G/4G Link through Dual SIM and should be accordingly interfaced with main Control Room SCADA.
For Supply ,Testing, Designing, Erection and commissioning of Mounting Poles for Local Stations Pole for Mounting of the system: Minimum height of pole required is 10 meters, Gl pole /S355 grade as per BSEN10025 having maintenance access and suitable platform with a safe and reliable raising and lowering mechanism for accessories mounted on the pole is to be applied along with the system for floor /ground mounting. The clamps, nuts and bolts etc. are also to be provided. Pole Foundation: The foundation /concrete base for mounting of pole will be in vendor's scope and the bidder shall provide foundation /Structural details of the siren mount along with the pole/tower for the siren system to withstand wind speed of 150 Km/hr. Soil testing to be carried out and further foundation to be designed based on the load bearing capacity of soil. MS fencing: The fencing should have a height of 6 feet. Dimension 4ft x 4ft (or higher depending on the pole or tower structure offered) along with the associated equipment and barbed razor wire at the top. Double coat Paint to de done of color specified by the EIC. Lockable gate of dimension 6ft height and 3ft width.
For Supply ,Testing, Designing, Erection and commissioning of Emergency Push Buttons at Local Stations There should be provision of Operating the system from Local via Push buttons in case of Emergency.
For Supply ,Testing, Designing, Erection and commissioning of Cable and required mounting accessories Power Cables and Accessories: All required power cables and accessories to make the system functional will be supplied by the vendor. Cables should comply with IS-694, IS-3961, IS8130 and IS-5831. MAKE: Polycab/ Finolex/ Universal/Havells
For Supply ,Testing, Designing, Erection and commissioning of Mandatory Spares (one set) 1) One No. Siren II) RTU/PLC-1set Ⅲ) Solar Charge Controller IV) Modem V) Strobe Light
For Supply ,Testing, Designing, Erection and commissioning of Dual SIM 3G/4G VPN Router Support TCP server, Design with standard TCP/IP protocol stack Support APN/VPDNO Support Dual SIM/UIM card Support VPN client Cellular Specification GSM/GPRS/EDGE • CDMAD TX Power < 32 dBm RX sensitivity - 93.30 dBm Hardware System CPU Industrial 32bits CPU FLASH 16MB (Extendable to 64MB) DDR2 128MB (Extendable to 256MB) . Interface type, Ethernet-1 No.
Bidder Name
Amount in Words
Telecon Systems
AIMIL LTD
Solas Marine Services Pvt. Ltd.
Telecon Systems
Solas Marine Services Pvt. Ltd.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .