Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹3.0 LAccepted-AOC | ₹3.0 L | 1 | Accepted-AOC ok |
| 2 | 2₹3.5 L+₹51,745 (17.5%)Rejected-Finance 256 MUNDHELA KHURD NEW DELHI 73 | ₹3.5 L+₹51,745 (17.5%) | 2 | Rejected-Finance Higher than the Lowest One |
Tender Value
₹3.5 L
EMD Value
₹7,400
Closing Date
22 Sept 2021, 2:00 pmClosed
Executive Engineer Electrical /NGZ
SOUTH DELHI MUNICIPAL CORPORAION OFFICE OF THE EXECUTIVE ENGINEER ELECT/NGZ ROOM NO -219, II ND FLOOR, ZONAL OFFICE BUILDING, DHANSA STAND , NAJAFGARH, NEW DELHI-110043
Providing Shed for yoga and senior citizen sheds at J Block park west sagarpur in Ward No 31S under NGZ Subhead Provision of EI and Fans
2021_SDMC_88126_2
EE/Elect/Najafgarh Zone /2021-22/ 11
Open Tender
Electrical Works
Item Rate
90 days
NAJAFGARH ZONE SDMC
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
₹7,400
Yes
4 Jan 2023
14 Sept 2021
23 Sept 2021
14 Sept 2021
22 Sept 2021
14 Sept 2021
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for circuit/submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor,single core cable in surface/recessed PVC conduit as required. (a) 2x2.5 sq.mm +1x2.5 sq.mm earth wire
Wiring for circuit/submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor,single core cable in surface/recessed PVC conduit as required. (b) 2x4 sq.mm + 1x4 sq.mm earth wire
Wiring for circuit/submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor,single core cable in surface/recessed PVC conduit as required. (b) 4x4 sq.mm + 2x4 sq.mm earth wire
Supplying and fixing suitable size GI box with modular plate and cover in front on surface / recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connections etc. as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 6 SWG dia GI wire on surface or in recess for loop earthing along with surface/recessed conduit/submain wiring/cable as required.
Installation of exhaust fan in the existing opening ,including making good the damage ,connection,testing,commissioning etc.as required. (a) Up to 450 mm sweep
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way , Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (a) Single pole
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (b) Double Pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonary open duct as required. Up to 35 sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Up to 35 sq.mm ( Clamped with 1 mm thick saddle )
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal)
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
Supply of 4.0 sq. mm ISI marked, FRLS PVC insulated, single core copper conductor cable
Supply of XLPE insulated,PVC sheathed Al.conductor Armoured Cable for working voltage upto 1.1 KV Conforming to IS 7098 of following Sizes.2x 10 Sqmm
Supply of XLPE insulated,PVC sheathed Al.conductor Armoured Cable for working voltage upto 1.1 KV Conforming to IS 7098 of following Sizes. 2x 25 Sqmm
Supply of 15'' ( 380 mm )sweep 1400 rpm exhaust fan heavy duty complete with shutter,blade etc as required
S.I.T.C of LED tube type luminaire 20 watt rating complete with polycarbonate housing batten integrated electronic driver prewired with high efficiency LEDs with the following : (A) Total system wattage 20 watt+/- 5% ,(B) Luminous efficiency Lumens/watt >= 95 , © Power factor >= 0.95
S.I.T.C of 60 watt LED flood luminiare fitted with lens , made of pressure die cast alluminium housing & toughened glass cover complete with the following specification as required .(A) Total system wattage 60 watt+/- 5% ,(B) Luminous efficiency >= 100 Lumens/watt, © Power factor >= 0.95,(d) Protection class -IP-66
P & F of Hot Press Sheet Moulded Compound (SMC),fire retardant (Temp. resistanceup to 200 deg.C),IP-55 weatherproof pole box of inner dimension 200 mmx 160 mmx 98 mm complete with suitable arrangement for fixing of two nos.of 6 to 32 amp single pole MCB and 63 amp double pole isolator (MCB excluded) with neutral link duly shorting on DIN channelwith 2 nos.of MS clamps with SS back plate of suitable size with danger monogram & SDMC property printed on the cover etc. as required
SITC of single / three phase monoblock pump set complete with all accessories workable on 240/415 volts,50 Hz AC supply.(a) 1 HP (0.75 KW) Single phase pump set,head from 12 - 30 meter , suction and delivery 25X25 mm
Supply of 1200 mm Sweep 50 watt, energy saver ISI marked BEE 5 star rating AC ceiling fan suitable for 230 V , 50 Hz ac supply without regulator with blades, downrod etc complete as required.
SITC of pillor box of size 900 mm x 450 mm x 250 mm suitable for mounting incomer of 250 A MCCB/ Main switch 4 pole and energy meter 3 phase complete with electhoypic grade aluminium bus bar of size 25 mm x 10 mm mounted on galvanised M.S. body power quoted pilferage proof SMC door duly welded with SS with rain com size 40 mm x 40 mm x 5 mm x600 mm height in cutting 300 mm height below ground and covered with shade proof SMC sheet of 3 mm as required.
DEV ENGINEERS
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .