Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.4 LAccepted-AOC | L1 | Accepted-AOC Bid found in order | |
| 2 | L2₹17.1 L+₹2.6 L (17.5%)Rejected-AOC NO 68 ANJANEYA TEMPLE CROSS OPP M S RAMAIAH HOSPITAL NEW BEL ROAD BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | L2 | Rejected-AOC Bid found in order | |
| 3 | L3₹19.9 L+₹5.4 L (36.7%)Rejected-AOC | L3 | Rejected-AOC Bid found in order | |
| 4 | L4₹24.0 L+₹9.4 L (64.4%)Rejected-AOC | L4 | Rejected-AOC Bid found in order |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
22 Feb 2022, 6:00 pmClosed
SHRI VINEET MODI
CWE AF North Bangalore Bellary Road JC Nagar Post Bangalore 560006
REPAIR MAINTENANCE OF HT SYSTEM INCLUDING HT SWITCH GEARS OVERHAULING OF TRANSFORMERS CLEANING GRAVELLING AND FACE LIFTING AND CONNECTED WORKS AT CHAFB
2022_MES_502733_1
87445CWEAFNBAN
Open Tender
Civil Works
Item Rate
180 days
GE (AF) BANGALORE
AS PER NIT
6 documents required · 6 mandatory
₹500
GE (AF) BANGALORE
₹40,000
Yes
15 Mar 2022
20 Jan 2022
24 Feb 2022
20 Jan 2022
22 Feb 2022
10 Feb 2022
21 Jan 2022 - 31 Jan 2022
Amount
M & L for locating UG cable fault using Microprocessor based fault locator suitable for low/medium and high volage up to 11KV , XLPE/PVC/PILC of Al/Cu cables under trenches/RCC surface & on wall for finding OC/SC/Flahing faults with any one of the suitable methods Time domain reflectometer method (TDR)/Secondary impulse Method (SIM) /Impulse Current method (ICM)/decay Method to achieve pin point fault location up to 5 Km distance as all as specified. (Note : quoted cost deemed to be included all accessories , equipments and labour cost)
M & L for filteration and dehydration of transformer oil on line by using streamline filteration plant the die electric strength to be brought to not less than 60 KV ( at 2.0mm gap for 1 minute) and testing the oil sample after dehydration Note: - (i) Test result before and after filteration to be recorded as per the sample provided by Engr-in-charge. (ii) The rate quoted deemed to be included for taking necessary connection and the connection to filteration plant from transformers and switchgear oil duly removing the inlet and outlet connections. (iii) For topping up transformer oil will be measured and paid separately under relevent items. iv) The rate quoted deemed to inclusive of testing charges.
Collecting the oil samples of transformers / voltage stabilizers installed at CHAFB areas after filteration and dehydration and carrying out testing the oil from NABL accredited Laboratory and as per IS 335:1993 detail analysis of physical,chemical & electrical parameters including dissolved gas analysis, Furan Analysis , etc and full report is submitted on printed form for each transformer oil samples tested all as specified and direced
M & L for filling insulating oil (transformer oil) confirming to IS-1866:2000 having dielectric strength not less than 60 KV for topping up in 11/0.433 KV transformer all as directed (Filling shall be done by on line filtration plant only) Make. Sarita/HP
S & Fix in Repair/Replacement of air breather any type upto 630 KVA transformer complete with filled silica gel complete
S & Fix in Replacement silica gel for up to 630 KVA transformer of any make type and capacity complete.
S & Fix in Repair/Replacement of oil temprature gauge upto 630 KVA transformer complete
S & Fix in replacement of set of gasket such as top cover, conservator,bucholz relay, breather etc for transformer capacity upto 630 KVA complete
M & L for painting the transformer indoor/outdoor of capacity ranging from up to 630 KVA after preparation of surface and applying two coats of synthetic enamel (matching existing colour) paint on old steel surafcece and marking serial no,MES No,SM No,Date of installation etc all as specified and as directed.
M & L for painting the compact substation including transformer, SF6 breaker and canopy complete of capacity ranging from up to 630 KVA after preparation of surface and applying two coats of synthetic enamel (matching existing colour) paint on old steel surafce marking serial no, MES No,SM No,Date of installation etc all as specified and as directed.
S & Fix in replacement of HT 11 KV bushing porecelain with copper alloy terminals for transformer of capacity upto 630 KVA including dismantling unserviceable complete all as specified and directed
All as per item 11 here-in-before but LT bushings
S & Fix in replacement of burnt Brass Bush connecting rod for transformer up to 630KVA and refixing new connecting rods with oil seal o-ring , nuts, washers etc all as specified and directed by Engineer-in-Charge
M & L for Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint
M & L for servicing of two/four/six pole structure complete including replacement of unserviceable jumpers with PVC 50 Sqmm aluminium cable single core , vice type connectors, bolts nuts washers connecting lugs/thimbles knife contacts, applying petroleum jelly to the moving as well as fixed contacts tightening all the connections for its smooth functioning and preparing the old painted surfaces of the structure such as poles, cross arms, bracing and supports clamps back plates complete painting of two coats of anticorrosive aluminium paint over a coat of redoxide zinc chrome primer and providing yellow and black paint from the ground level all as directed at site by Engineer-in-charge. Note: - No extra payment will be made for the spares required to keep the installation in satisfactory functioning through out the contract period other than given in the schedule.
M & L for spread stone aggregate of size 40 to 90 mm grade all as specified and directed.
Supply and fix in repair/replacement of switches air break gang operated triple pole mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level for current rating upto 200 Amps 11000 volts complete.
Supply fix in replacement of Male moving contacts blades for Gang opertaed/Air break switch assembly with proper nuts ,bolts and applying non corrosive petrolium jelly all as specified and directed
Supply fix in replacement of Female fixed alloy contacts jaws for Gang opertaed/Air break switch assembly with proper nuts ,bolts and applying non corrosive petrolium jelly all as specified and directed
Supply fix in replacement PVC sheahed strandarded aluminium conductor cable of size 70 sqmm for jumper due fixed on GOD with D clamps all as specified and directed
Supply fix in replacement pin type porcelain vitreous, white, brown or green insulator including one galvanized mild steel spindle two galvanized iron washers and one galvanized iron nut 150mm height 150mm dia 11000 volts grade including taking down old unserviceable insulator all as specified and directed.
Supply and fix lightening arrestor non linear type suitable for HT 11 KV installation out door use complete with all fittings transmission class discharge 65 Kilo Amps including taking down the unserviceable all as directed.
M & L for cleaning, dusting and servicing, for the smooth functioning electronic float cum boost battery charging unit suitable for HT VCB panel 110/220 volt DC with sealed battery bank of 2 volt , 100 AH with connection fixed inside MCB control for input circuit, DC out put circuit, tightening the cable connection incoming and out going etc all as specified and directed.
Supply & Fix in replacement of Drop out fuses capacity 20 Amps to 40 Amps. Make: Jayapuria /Bussmann or Equivalent
S & Fix in replacement of HT Bottle fuse 100 Amps for load breaker switch controled all as specified and directed at site. Make : Cooper Bussmann/SIEMENS
M & L for Repair/Maintenance , cleaning, dusting and servicing Vacuum Circuit Breaker, HT 11 KV,50 Hz , 630 Amp indoor switch gear panel by Grounding of complete panel live parts, thorough cleaning, visual checking, tightness checking, and servicing of breaker panel including breaker carriage along with associated mechanism , metering panel, bushbar/cable chambers, motorised spring charging mechanism , DC shunt trip/close coils, operation counter, manual spring charging mechanism , relays, meters , indicators , heater coil, aux supply SMPS , replacing of worn out parts and fuses , applying petroleum jelly to moving and fixed mechanical parts for its smooth functioning all as specified and directed by the Engineer in charge.
M & L for Repair/Maintenance ,cleaning, dusting and servicing, for the smooth functioning of 3 way compact RMU, HT 11 KV , 630 Amp, 3 phase 50 cycle by Grounding of complete panel live parts, thorough cleaning, visual checking, tightness checking, and servicing of breaker panel including breaker carriage along with associated mechanism , metering panel, bushbar/cable chambers , self powered over current and earth falult relay, T-off SF6 circuit breaker module , mechanical fault/on/off indicator etc including refilling of SF6 gas and replacing worn out parts when required etc and confirming smooth reliable operation of RMU unit all as specified and directed.
M & L for Repair/Maintenance , Cleaning, dusting and servicing Oil circuit Breakers HT 11 KV, 50 Hz, 400 Amps capacity by Grounding of complete panel live parts, thorough cleaning, visual checking, tightness checking, and servicing of breaker panel including breaker carriage along with associated mechanism , metering panel, bushbar/cable chambers, DC shunt trip/close coils, operation counter, manual spring charging mechanism , relays, meters , indicators , aux supply SMPS , replacing of worn out parts and fuses carefully for its smooth functioning complete all as directed by the Engineer in charge.
M & L for Repair/Maintenance ,cleaning, dusting and servicing of standalone/Compact substation SF6 Circuit Breaker, HT 11 KV, up to 630 Amp , 3 phase 50 cycle totally enclosed out door type application switch gear by Grounding of complete panel live parts, thorough cleaning, visual checking, tightness checking, and servicing of breaker panel including breaker carriage along with associated mechanism , metering panel, bushbar/cable chambers, motorised spring charging mechanism , DC shunt trip/close coils, operation counter, manual spring charging mechanism , relays, meters , indicators , heater coil, aux supply SMPS , replacing of worn out parts and fuses , applying petroleum jelly to moving and fixed mechanical parts for its smooth functioning all as specified and directed by the Engineer in charge.
M & L for Repair/Maintenance ,cleaning, dusting and servicing, for the smooth functioning of oil cooled servo voltage stabilizer 75 KVA 3 phase by Grounding of complete panel live parts, thorough cleaning, tightness checking, and servicing of servo moter,Auto transformer ,control circuit ,Aux power transformer,bearing,control relays,contactors including checking of looswiring along with associated mechanism and replacing worn out parts etc and testing,confirming smooth reliable operation of voltage stabilizer unit all as specified and directed.
M & L for Decarburizing/cleaning complete HT 11KV, 3 phase independent bus bar, bus bar chamber of HT panel electrification after removing the complete bus bar spout, circuit spout from the bus bar chamber, cleaning with CTC and ensure proper decarburizing, re-fixing the same after applying backtol (Red) solution to the spout, checking all the connections, tightening the nuts, bolts thimbles for incoming and outgoing system complete all as specified and directed, rate quoted is inclusive of bactol red, CTC & cotton waste provided by contractor.
M & L in replacement of terminal protector boot straight/right angle type having insulating capacity of 11/22KV rating for having Protection from Short Circuit due to Intervention by Reptiles,Birds, Animals in Cable Entry Box for transformer/VCBs/RMU/SF6/OCB breakers all as specified and directed
M & L for refilling/topping SF6 (Sulpher Hexa fuloride) gas charging/topuping in existing RMU/SF6 circuit breaker upto specified operating level (min pressure 2.8 Kg/cm2) and conduct gas leakage test and arrest leakage if any complete all as specified and directed
Supply and replacement of LED light Red, Blue, Yellow & green for 110 Volts for HT 11 KV panel all including taking down the unserviceable as directed
Supply and fix in Replacement of Push Button with 1 NO + 1NC on existing HT VCB Panel all as specified and as directed Make : L &T /Seimens/Schnider
Supply and fix in Replacement of Rotary switch for Local / Remote / Neutral / trip / Close function on existing HT VCB/SF6/OCB Panel all as specified and as directed Make : L &T /Seimens/Schnider
Supply and fix in Replacement of Digital Multifunction meter PT/CT (0-110v)/(0-1/5A) operated for measuring votage / Ampere / Power factor / Frequency etc on existing HT VCB/SF6 Panel all as specified and as directed Make : Schnider/L&T/AE/MECO/SELEC
supply and fix in replacement of resin type PT 11KV/110V for phase with fuse, 11KV/110V, with burdon of 100VA, Accuracy 0.5 as existing type , complete suitable for HT 11KV panel , testing and commissioning after completion of the work. Make : Kappa Electricals/Crompton /L&T
Supply and replacement of HT 11 KV current transformer dual core epoxy insulation type as existing CT ratio including taking down the unserviceable all as directed Make: of Kappa Electricals/Crompton /L&T
S & F in replacement of SMF GEL Tubular VRLA 2 Volts 100 Ah Battery for battery bank system, including connecting copper lead , thimbles, nuts, bolts , washers etc. Make: Amaron
Supply and fix in Replacement of Panel space Heaters 80-120 watts coil element AC 230 Volt Input suitable for HT VCB panel of any make fixed inside with suitable clamps , bolts and nuts complete including necessary wiring cable connection complete all as specified and directed
Supply and fix in Replacement of Thermostate switch for controlling the space Heaters temperature settings AC 230 Volt Input suitable for HT VCB panel of any make fixed inside with suitable clamps , bolts and nuts complete including necessary wiring cable connection with control toggle ON-OFF switch - 01 No complete all as specified and directed
Supply and fix in replacement of damaged HT breaker cluster contacts male / female / Isolating / Moving / Fixed Contacts 630/400 amps for VCB/OCB/RMU/SF6 type breaker all as specified & directed Make Kirloskar /ABB
Supply and Replacement of closing coil complete with all accessories suitable for HT 11 KV VCB 400/630 Amps complete including taking down the unserviceable all as directed. Make: Suitable Make of Kirloskar/ABB
Supply and Replacement of tripping coil complete with all accessories suitable for HT 11 KV VCB 400/630 Amps including taking down the unserviceable complete all as directed. Make: Suitable Make of Kirloskar/ABB
Supply and replacement of HT 11 KV VCB 400/630 Amps epoxy spout insulator including taking down the unserviceable. Make: of Kirloskar/ABB
Supply and replacement of CAM wheel assembly suitable for VCB of existing make HT 11 KV,400/630 Amps capacity complete with all accessories as specified and as directed.Make: Suitable Make of Kirloskar/ABB
Supply and replacement of spring charging motor suitable for VCB of make Schnider HT 11 KV, 630 Amps capacity complete with all assembly/accessories as specified and as directed.Make: Suitable Make of Kirloskar/ABB
Supply and Replacement of spring charging gear assembly with all accessories suitable for HT 11 KV VCB 400/630 Amps complete including taking down the unserviceable all as directed. Make: Suitable Make of Kirloskar/ABB
Supply and Replacement of catch/ latchet assembly complete with all accessories suitable for HT 11 KV VCB 400/ 630 Amps complete including taking down the unserviceable all as directed. Make: Suitable Make of Kirloskar/ABB
M & L for calibration and testing of triping system of HT 11 KV OCB/VCB/SF6/compact substation circuit breaker by injecting fault current on primary side of CT/PT , setting the OL/inverse time /Earth fault level and ensure that HT breaker tripping system function properly as per relay setting and submit calibration test certificate duly signed by contractor complete all as specified and directed by Engineer-in-Charge.
M & L for painting the VCB of capacity ranging 630/400 Amps after preparation of surface and applying painting of two coats of anti corrosive smoke grey paint over a coat of redoxide zinc chrome primer out side surface of the metalic enclosure including writing MES No, SM No, Date of installation etc all as specified and directed by the Engineer in charge
M & L for painting the SF 6 /OCB / RMU of any capacity ranging after preparation of surface and applying painting of two coats of anti corrosive smoke grey paint over a coat of redoxide zinc chrome primer out side surface of the metalic enclosure including writing MES No, SM No, Date of installation etc all as specified etc all as directed by the Engineer in charge
M & L for Cable jointing kit for 11 KV (Earthed) grade cable for stright through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 sq mm including taking down the unserviceable.
M & L for replacement of cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing materials and accessories suitable for 3 core XLPE armoured aluiminium conductor cable of size 120 sqmm to 185 Sq mm
M & L for replacement of cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing materials and accessories suitable for 3 core MLPE armoured aluiminium conductor cable of size 120 sqmm to 185 Sq mm
M & L for Repair/Reconditiong of exisitng earth pit by removing damaged Earth PCC chambers and excavate pit soil upto 25% of earth plate/electrode and adding alternate layers of charcoal, mixture of salt and copper sulphate up to 15cm above the earth plate/electrode and moist the mixture using water , cleaning/replacing of funnel with wire mesh where ever necessary , contractor should ensure that the earthing resistance should be below 5 Ohms, making good to distrubed surface and all as specified and directed at site. Note: 1. Deemed including excavation, returning filling and connected items. 2. Salt , charcoal , pit cover will be measured and paid seperatly
Supply only pure charcoal granular/aggregate type having Ash content < 5% , stone free for earthing
Supply only iodine free pure common salt crystal ( NaCl) for earthing
M & L for repair/replacement of eart pit cover with pre moulded cast iron eart pit cover 300mm x300mm x 50mm , provision of funnel, wire mesh necessary excavation and earth work in any type of soil as earth pit complete all as specified and directed
M & L for Test point terminal block made of gun metal or phosphorus bronze size 75 x 75 x 25mm, drilled and screwed including 3 Nos. 8mm dia 25mm long hexagonal head screw complete fixed on wall in and including sheet steel enclosure of thickness 2 mm thickness with locking arrangement complete all as specified and directed.
Taking down old U/S strip of any description and any size
M & L for laying earth continuity conductor GI Strip 25 x 4mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for direct/loop earthing with proper PVC/Porcelain insulator etc all as specified and directed .
M & L for laying earth continuity conductor GI Strip 32 x 6 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for direct/loop earthing with proper PVC/Porcelain insulator etc all as specified and directed .
S & F in replacement of PVC Polymer/Porcelain insulator for existing GI/Aluminium/copper strip support all as specified and directed
M & L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to galvanised iron wire 4 mm dia by means of bolts,nuts and washers of galvanised iron or steel all as shown in elecrtical plate No 3 set of SSR pt I, connected to transformer, DG set, LT panel/DB/earthing test point including PCC chamber , RCC cover 50mm thick with 8 mm dia bars, protection pipe, watering pipe20 mm GI, funnel etc including excavation, earth work, disposal of surplus soil and earth strip protection pipe of GI 15 mm bore light grade upto 7.5 metre including testing on completion all as specified and as directed.
M & L for rubber matting one side chequered and other side plain 19 mm thick insulated for 11000 Volts ISI Marked in standard size 2m x 1m including taking down the unserviceable all as specified and directed.
M&L danger notice board/plate of 1.6mm thick mild steel sheet vitreous enameled white with letter, figures and conventional skull and bones in signal red colour and fixed with MS clamps, nuts and bolts of approved size of HT 25 x 20 cm size.
Supply and replacement of mild steel nuts and bolts and washers of various sizes all as directed.
Repairing/ welding of leaking fins / body of transformer and making the same leak proof all as directed
Supply & fix in replacement of Tinned copper flexible jumper 200/400A rating for Gang operated /Air break switch assembly with proper nuts,bolts and applying non corresive petrolium jelly all as specified and directed
M & L for preventive maintenance/ repairs to transformer step down 11 KV/0.43 KV in door/out door type of any make of 250 KVA - 400 KVA - including cleaning the transformers externally throughly with lint free cloth, tightening the HT/LT terminal nuts, opening the top cover and replacing the worn out copper alloy nuts and tightening the earth terminals and conducting various tests as stipulated in the particular specification
M & L for preventive maintenance/ repairs to transformer step down 11 KV/0.43 KV in door/out door type of any make of 100 KVA - 200 KVA - including cleaning the transformers externally throughly with lint free cloth, tightening the HT/LT terminal nuts, opening the top cover and replacing the worn out copper alloy nuts and tightening the earth terminals and conducting various tests as stipulated in the particular specification
M & L for preventive maintenance/repairs to transformer step down 11 KV/0.43 KV in door/out door type of any make of 500/630 KVA - including cleaning the transformers externally throughly with lint free cloth, tightening the HT/LT terminal nuts, opening the top cover and replacing the worn out copper alloy nuts and tightening the earth terminals and conducting various tests as stipulated in the particular specification
M & L for maintenance/repairs to tap changer of transformer upto 630KVA capacity , tightening of nuts,bolts and all check the functioning of all moving parts , including changing all worn out parts such as moving contacts ,L-connectors,fixed contacts ,mounting blocks etc including testing of tap changer in all positions complete all as specified and directed
S & Fix in replacement of vaccum bottle interrupter rated 11KV , and breaking capacity 31.5 KA , rated current 630A min ,including testing all as specified and directed(Note: Item no 1 to 80 If any HT installations and connected itms become breakdown, the contractor shall loacate the problem/fault at site within 24 hours on intimation by JE/Engineer-In-Charge and ensure that the fault rectified within 48 Hours on locating the fault, failing which an amount of Rs 500 /- per hour will be recovered as penal recovery payment due to the contractor failing to rectify the complaint or fault in right time i.e. after expiry of 48 hours.)
devan enterprises
B5BUILDING SOLUTIONS
M/S Bhagyawanticonstruction
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .