| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.2 LAccepted-AOC | L1 | Accepted-AOC lowest rate quoted | |
| 2 | L2₹4.6 L+₹34,992 (8.28%)Rejected-Finance 11 CROOKED LANE KOLKATA 700069 | KOLKATA | KOLKATA | WEST BENGAL | 700069 | L2 | Rejected-Finance Higher rate quoted | |
| 3 | L3₹4.9 L+₹68,948 (16.3%)Rejected-Finance 33 PEMANTLE STREET KOLKATA 700016 | KOLKATA | KOLKATA | WEST BENGAL | 700016 | L3 | Rejected-Finance Higher rate quoted | |
| 4 | L4₹5.4 L+₹1.1 L (27.0%)Rejected-Finance 10B DR LAHIT BANERJEE SARANI GROUND FLOOR KOLKATA 700 073 | KOLKATA | KOLKATA | WEST BENGAL | 700073 | L4 | Rejected-Finance Highest rate quoted |
Tender Value
Refer Docs
EMD Value
₹11,000
Closing Date
14 Nov 2019, 3:00 pmClosed
EE CKHED
P12 CIT Road 1st floor Kolkata 700014
Repair n renovation of Air Conditioning arrangement at proposed Server Room at top floor of the adjacent building of Administrative Block CNMCH Kolkata
2019_WBPWD_250745_1
WBPWD/EE-I/CKHED/NIT-33/ 2019-20
Open Tender
A/C ORG
Item Rate
45 days
CNMCH
as per NIT
4 documents required · 4 mandatory
₹11,000
EE CKHED P12 CIT Road 1st floor Kolkata 700014
9 Sept 2020
31 Oct 2019
16 Nov 2019
31 Oct 2019
14 Nov 2019
7 Nov 2019
5 Nov 2019
Amount
Supply 7.5TR capacity concealed type Split Air Conditioner of rated cooling capacity of 90000 BTU/hr. with 3Nos. twin rotary compressor, 3nos. IDU of rated power supply-230V-1ph-50Hz. , 1no. ODU of rated power supply-400V-3ph-50Hz. Air-flow/per IDU:- 1000CFM. ( Make: Hitachi/Mitsubishi-Electric)
Lifting, shifting, Erection & Commissioning Charges incl. refrigerant R-22 for 7.5 TR concealed type Split Air Conditioner
Copper Refrigeration pipe line for liquid and suction line with fittings, elbows, bends, supports & brackets (Make-Ryoku)
b) Liquid Line (3/8" OD with 0.6 mm thick)
c) Suction Line (5/8" OD with 0.7mm thick)
Supply & Fixing Pipe Insulation in liquid & suction line with 9mm nitrile rubber tube (Accoflex)
b) Liquid Line (3/8" OD with 0.6 mm thick)
c) Suction Line (5/8" OD with 0.7mm thick)
Control copper Cabling from Condensing Unit to control panel (Make: polycab/finolex)
a) 3 core 2.5 sq.mm communication cable
b) 3 core 4 sq.mm unarmoured cable
Supply and fixing flexible canvass connection for concealed split air-conditioners.
Supplying, fabrication & fixing M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) for making platform for installation of outdoor unit of 7.5 TR Concealed split AC incl. drilling 2 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. fabricated with horizontal angle of 25 mm x 25 mm x 6 mm including supporting angle 50 mm x50mm x 6 mm in each platform in outer edge for transmitting the load centrally through 2Nos. (50 mm x 50 mm x 6 mm) Angle inserted into the exiting wall. The entire structure should be baricated & safe for ODU maintenance. Area of the platform is 3Mtr. x 1.2Mtr.
Supply and fixing of Al powder coated continuous Grill (Make- Premier)
S & L of Drain Water piping work out of PVC / HDPE hard pipes of following sizes incl. fitting, accessories, bends, elbows, tees, flanges, tapings, wall sleeves, hangers, supports, anchors.
a) 25 mm dia
Charges for scaffolding arrangement incl. lifting for outdoor & indoor units
Supplying, fitting & fixing in position suspended boxing for return air arrangement & indoor units of concealed split airconditioner with frame work of aluminium hollow section of size 50mm x25mm (2.0mm thickness) combined with aluminium corners of size 38mm x 25mm, suspended by aluminium hollow tube section of size 38mm x 25mm ,25mm x 25mm powder coated wall angle with aluminium composit panel of thickness 3.0mm comprising of protective film, polyester coating, primer, aluminium coil, adhesive film, polyethylene core again with one layer adhesive film, aluminium bottom coating and finally service coating as per manufacturer's specification finished with aluminium screw and silicon sealent including suitable arrangement for grill fixing complete in all respect as per direction of EIC.
charges for trap door of 1600 mm x 600 mm and 9 mm thickness made of aluminium channel & ply wood for IDU maintenance.
Rate should be quoted incl. of all taxes and cess.
Defect Liability period : 1 year
YOUNG ENGINEERING ENTERPRISE
MILLENNIUM AIRCON
CARRION AIR COOLING
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .