Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.9 LAccepted-AOC 1 C NEPAL BHATTACHARJEE STREET KALIGHAT KOLKATA 700026 | KOLKATA | WEST BENGAL | 700026 | ₹34.9 L | L1 | Accepted-AOC L1 |
| 2 | L2₹36.9 LRejected-Finance 17 23 K P ROY LANE KOLKATA 700 031 | KOLKATA | KOLKATA | WEST BENGAL | 700031 | ₹36.9 L | L2 | Rejected-Finance L2 |
| 3 | L3₹38.8 LRejected-Finance 13 11 MOTILAL GUPTA ROAD KOLKATA 700 008 | KOLKATA | WEST BENGAL | 700008 | ₹38.8 L | L3 | Rejected-Finance L3 |
| 4 | Rejected-Technical | - | - | Rejected-Technical Rejected for the reason- penalty was imposed against acceptance no 31- Q- MESD of 2024 25 of AE MESD for inferior quality of materials and failure to rectify the defect thereafter. The compensation amount has not been submitted till date |
Tender Value
₹35.0 L
EMD Value
₹70,068
Closing Date
13 Dec 2025, 12:00 pmClosed
The Executive Engineer, Kolkata Electrical Div
The Executive Engineer Kolkata Electrical Division P.W.Dte. BlockI (1st Floor) Writers Buildings, Kolkata 700 001
Temporary electrification and illumination work in connection with different VVIP programmes at RCTC Hellipad under Maidan Electrical Section-IV, PWD.
2025_WBPWD_952274_1
WBPWD/EE-KED/eNIQ-36Q/25-26
Open Tender
ELECTRICAL WORKS ORG
180 days
Maidan
Please refer Tender documents.
5 documents required · 5 mandatory
₹70,068
O/O The Executive Engineer Kolkata Electrical Divi
4 Feb 2026
18 Nov 2025
15 Dec 2025
18 Nov 2025
13 Dec 2025
28 Nov 2025
27 Nov 2025
Amount
Distribution wiring in 3 x 1.5 Sqmm single core PVC copper wire to light/fan points incl. fixing holder, switch and double board etc. complete on hire basis and dismantling the same(Hiring Period upto 3 days)
Supplying & Drawing on Hire Basis Three Phase Dist Wiring With 4 x 10 Sqmm with Earth Wire (2x 6 ) Sqmm Or its equivalent PVC copper wiring or its amp equivalent on the hire basis incl. dismantling the same per meter.(Hiring Period upto 3 days)
Providing on hire main wiring with 1.1 KV grade Aluminium Conductor PVC / XLPE armoured cable of following sizes including laying in trench (at least 230 mm below ground) including dismantling the same and mending good the damages.(Hiring Period upto 3 days)
4 Core 25 Sq. mm PVC / XLPE armorured cable
Providing on hire basis following switches etc. on wooden plank board or suitable angle iron frame incl. Providing interconnection wiring with socketing, earthing attachment etc. and dismentaling at the of end function (with PWD / E.I.C. approved materials).(Hiring Period upto 3 days)
415V, 63 amp TPN switch with rewirable fuse
Providing on hire basis following switches etc. on wooden plank board or suitable angle iron frame incl. Providing interconnection wiring with socketing, earthing attachment etc. and dismentaling at the of end function (with PWD / E.I.C. approved materials)(Hiring Period upto 3 days)
415V, Upto 6 Way TPNBDB With 1 No. - 63 amp FPMCB as Incoming & 15No. 6-32 amp SPMCB as Outgoing(Hiring Period upto 3 days)
Providing on hire basis following switches etc. on wooden plank board or suitable angle iron frame incl. Providing interconnection wiring with socketing, earthing attachment etc. and dismentaling at the of end function (with PWD / E.I.C. approved materials)(Hiring Period upto 3 days)
415V, 100 amp, Offload Change Over Switch
Supplying & providing on hire basis 150 watt LED Flood light complete with bracket and clamps on the pole including dismantling incl. replacement of fused lamp (As per approved by E.I.C.)(Hiring Period upto 3 days)
Supplying & providing on Hire Basis 2nos. 6A Switch and 2nos. 6A 3pin socket and 2 nos. 20A Switch and 2 nos. 20A 3pin socket on suitable size MS/TW Board and dismantling the same (Hiring Period upto 3 days)
Supplying & providing 1 no Seperate 6 amp plug and Switch with 150X100X65mm MS/TW switch Board on Hire basis and dismantaling the same(Hiring Period upto 3 days)
Temporary hiring basis 4 TR Tower AC system incl. allied EI work as per direction of EIC. (For hiring period upto 3days)
Providing on hire basis 8 feet height bamboo & install at 2 feet depth below the ground for fixing LED flood light & dismantling after the programme as per direction of EIC.
Supplying & providing single LED fitting complete with tube, commercial type (4 ft) fitting on hire basis and dismantling the same (As per approved by E.I.C.)(Hiring Period upto 3 days)
Supplying & providing on hire basis 240V A. C. 450 mm / 18" sweep Pedestal fan and dismantling the same(Hiring Period upto 3 days)
Providing & Earthing on hire basis with 50 mm dia GI Pipe 2.5 to 3 mtrs. Long and 6/8 SWG GI wire with galvanized nuts and bolts washer etc. below ground level on hire basis and dismantling the same.(Hiring Period upto 3 days)
Supplying & providing & connecting with Existing electrical panel ( With appropriate cable supplied by Contractor )on hire basis different KVA Three phase DG set of Follwing Ratings and dismantling the same, excluding fuel charges..If the DGs are not placed at site on time, pro rata rate will be reduced from bill.
62.5 KVA Three phase 2 nos for Each day
40 KVA Three phase 2 nos for Each day
Deployment of One no. Electrician & One no. Helper per shift per day (i.e. Total 3 nos Electrician & 3 nos Helper per day for 24 Hrs) for carring out all kind of EI maintenance & DG operations etc.
18 % GST on the total amount from item no 1 to 16.
Supply & Pouring of HSD for the hired DG set incl handling cost.
Special Terms and conditions for Temporary E.I. Work - 1) Earthing should conform to IS specification. Earth Continuity wire should not be broken / Jointed. Single Earth continuity wire should be used from Earth Bus-Bar to the installation. 2) All 3ɸ Electrical Panel Should be earthed by two nos. of separate earthing and 1ɸ panel should be earthed by one no earthing. 3) MCB / Rewirable Fuse type Distrubution Board should be installed with proper Trip Current setting / fuse wires. However, MCB type DBs are preferable. 4) No Part of the Electrical Circuit in the pandal / Structure shall be within 12 inches of any decorative cloth / paper. 5) Ordinary Flexible wires should not be used. Only new PVC insulated & sheathed wires (Bearing ISI mark) or PVC insulated wires of FRLS (Fire Resistant Low Smoke) type (ISI Marked) are allowed. 6) All cable ends should be properly sockedted. 7) All joints shall be made with porceline insulated connectors. Twisted & lapped joints shall be avoided. But Joints are strictly not allowed in the dias. 8) Cables / Wires should run along outside the Dias. 9) Ceiling fan (s) / Electrical fittings must not be suspended from the ceiling of Dias. Pedestal fans are not allowed on the Dias. However, Pedestal fans may be installed outside dias, but the body of the fan must be properly earthed.
10) T/L fittings shall be of box type (Indoor commercial type). Any kind of open type fittings must be avoided. 11) Each A.C. Machine should be connected with a separate circuit and earthing should be provided by separate single earth contunuity wire from Earth Bus-bar. 12) P.A. System and Microphone shoud be earthed. 13) Sufficient quantity of Fire Extinguishers and First Aid Box should be provided. 14) If the DGs are not placed at site on time pro rata rate will be reduced from bill. 15) The guarding /security arrangement of all the hired products /installation has to be made by the successful bidder at his/their own cost and responsibility. No additional charge will be paid for any unwanted incidents like theft, damage due to natural calamities or any other reasons whatsoever. 16) During entire hiring period any fault to the hired installation shall be rectified/faulty items replaced, at the cost of agency. Suitable man power for attending and rectification/replacement of damaged items has to be provided by the agency at their own cost. Rectification time is 1 hour for the event day and upto 2hrs for other days. 17) A test certificate cum safety certificate is to be provided by the agency, duly signed by the Supervisor of the agency after completion of installation. 18) A performance guarantee of hired DG sets and AC machines has to be provided by the agency after completion.
ANAMICA ENTERPRISE (BID ID -7540292)
S. K. CHATTERJEE ELECTRICALS PVT LTD (BID ID -7618785)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.47 MB
BOQ_2277998.xls
BOQ • 0.33 MB
2911.pdf
Tender Documents • 0.54 MB
Download all tender documents and submit your bid