SE,EUDC-VII,Ciss-Gomti,LESA,
33/11 K.V. Substation,sct-5D,Vrandavan Yojna,LESA, Lucknow.
Testing of 33 KV Power T/F, 33 KV Transformer breaker, pannel at 33/11 KV S/S s in the area of Alambagh and Kanpur Road against O and M scheme 2023-24 under jurisdiction of E.E., EUTD-III, LESA, Lucknow
2024_MVVNL_918540_1
121/EUDC-VII/LESA/2023-24
Open Tender
Electrical Works
365 days
LUCKNOW
AS PER TENDER DOCUMENTS
2 documents required · 2 mandatory
₹1,180
A/CNo 1277784945,IFSC Code CBIN0280140
₹9,000
27 Mar 2024
16 Mar 2024
23 Mar 2024
16 Mar 2024
23 Mar 2024
16 Mar 2024
Amount
Testing of 33 KV Power T/F & 33 KV Transformer breaker & pannel at 33/11 KV S/S's under jurisdiction of EUTD-3 including following tests:-
(a) Insulation test.
(b) Open circuit/Ratio & short circuit test.
(c) Magnetization current Test
(d) Magnetic balance Test
(e) Other test Including BDV, neutral and body resistance of T/F and earth resistance and vector group test. The test should be carried out by bringing testing kit and all required instruments on site by the contractor, making all necessary connection for above tests and insuring healthiness of transformers. Complete testing shall be done once half yearly or as and when required in emergency. Testing of 33 KV VCB & pannel by primary injection set. Testing of annunciation/indication circuits displaying on pannel. The work includes cleaning, adjustment of relay setting, contacts & springs by manual and protection trip command generated be relays through primary injection set. Remote/local operation also to be checked All T&P's as required for above work should be provided by the contractor.
Testing of 33 KV Power Tranformers Marshalling Box Pannel, oil temperature indicator, oil level indicator & buchholz relay, by operation of individual alarm/trip circuits of above. Testing of annunciation/indication circuits displaying on panel. The work includescleaning adjustment of relay contacts & spring by manual and protection trip commands generated by relays through primary injection set. Remote/local operation also to be checked All T&P's as required for above work should be provided by the contractor.
Testing of 11 KV incoming/outgoing breaker/pannels including testing of CT ratio by primary injection set. Testing of relays and its setting as per requirement. The work includes cleaning of relay. Checking and operation of VCB/OCB by remote/local and manual/protection command generated through primary injection set with operation of relays.For tightening of all contacts testing of relay & control wiring, equipment (About training of employee officers etc.) All T&P's as required for above work should be provided by the contractor.
G.S.T. Extra as per rules.