DIRECTOR NISER
DIRECTORATE NISER
Supply, Installation, Testing and Commissioning of VRF Air Conditioning System in First Floor, Second Floor and Reception Area of Library Building, NISER Campus, Jatni
2020_NISER_537974_2
NISER/MECH/LVRF/2019-20/21
Open Tender
Machineries/ Mechanical Engg Items
Works
90 days
NISER JATNI
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹5.0 L
2 Jun 2020
11 Feb 2020
21 Feb 2020
11 Feb 2020
20 Feb 2020
11 Feb 2020
Outdoor Units :Supply, Installation, Testing and Commissioning of VRF system following and complete as per specification with Refrigerant R410A. Supplying, Installation, Testing and Commissioning of Variable Refrigerant Flow (VRF) System, equipped with Variable Evaporating Temperature or equivalent suitable to maintain indoor design condition at minimum 48°C ambient temperature comprising of the following and complete as per specifications: a) All inverter hermetic scroll compressors / Twin Rotary Compressor, equipped, minimum two compressors for above 14HP modules, complete with high/low pressure cut-outs, oil pressure failure switch, microprocessor based Controller, top discharge type condensing unit(s), with R410A Refrigerant, vibration isolators, with suitable foundation etc. complete as required, fan motor, safety thermostat, over current relay, fusible plugs, fuses, referigerent cooled PCB's and suitable for operation on 380-440V, 3 phase/ Single Phase, 50 Hz A.C. supply.The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. The unit shall be filled with first charge of the refrigerant and ready for use as required. b) Matching air cooled condenser with copper tubes and aluminium fins duly covered by anti- corrosion and hydrophillic resin film. c) Oil separator suitable for the refrigerant piping. d) Accumulator, liquid and gas shut-off valves and solenoid valves/modulation valve with fittings to interconnect compressor, condenser and evaporator coils. Make: O-General/Toshiba/Daikin/Mitsubishi Electric
Outdoor Units- Cooling (R410A) Capacity 30HP - (16HP +14HP), 30 HP unit shall employ 14hp + 16hp units (or above). Subject to minimum two compressors for above 14 hp modules.
Supply, installation, testing and commissioning of following minimum capacity and external static pressure VRF / VRV ceiling mounted ductable type Indoor unit equipped with washable synthetic mediapre - filter, fan section with low noise fan / dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, other necessary supports etc., suitable for operation on single phase AC supply 230V±10%, 50Hz complete as required. The unit shall have automatic force shutdown provision in case of fire on receiveing signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. Make: O-General/Toshiba/Daikin/Mitsubishi Electric
8.0 TR Ductable unit.
5.5 TR Ductable unit.
Y-Joints Copper Ref. Nut
Supply & Installation as required as per specification
Outdoor unit connecting Y joints
BHF Kit
Remote Controllers
Corded Remote Controllers
All indoor and outdoor units is to be interconnected with Wi Fi enabled centralised controller for single point control and monitoring. The control is to be done through application and should be downloaded in mobile / laptop / deskt
Refrigerant Copper Piping Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft / hard drawn copper refrigerant piping for VRV/ VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing / brazing including accessories, insulated with XPLE Class-O tubular insulation / with Class - O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required. Make: Mandev/Rajco/Mexflow/Shrishyam
41.3 mm O.D (With 19 mm insulation)
38.1 mm O.D (With 19 mm insulation)
34.9 mm O.D (With 19 mm insulation)
28.6 mm O.D (With 19 mm insulation)
22.2 mm O.D (With 19 mm insulation)
19.1 mm O.D (With 13 mm insulation)
15.9 mm O.D (With 13 mm insulation)
12.7 mm O.D (With 13 mm insulation)
9.5 mm O.D (With 13 mm insulation)
Covered cable tray with GI Sheet cover for exposed piping
Drain Piping UPVC piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber insulation. Make: Supreme/Prince/Finolex/Astral
50 mm Dia
40mm Dia
32mm Dia
Control & Transmission Wiring Providing & fixing control cum transmission wiring of 2 core x 1.5 sqmm copper in suitable conduits between indoor and out door unit. And remote control as per specifications. Make:Polycab/KEI/Finolex/RRCable
Allied Work Lifting , Shifting, positioning , Refrigerant Gas charging of ODUs & IDUs as per approved drawings
Duct work site Fabricated Duct Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required and as per the instructions of Engineer In Charge. Make: TATA/SAIL/Jindal/Fiberfill
24 gauge (.63mm) galvanized sheet steel
22 gauge (.8mm) galvanized sheet steel
20 gauge (1mm) galvanized sheet steel
18 gauge (1.25mm) galvanized sheet steel
Duct Acoustic Lining Supply, installation, testing and commissioning of acoustic lining of Open cell nitrile rubber in supply air ducting complete with adeshive 15 mm thick 32kg/cu.m. Make Armasound/Thermobreak/Armaflex/Upwiga
Duct Insulation Work: Supplying and fixing of 19 mm thickness duly laminated aluminum foil of matt finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required and as per the instructions by Engineer In Charge. Make:Kflex/Armacell/Armasound/Aflex
Air Distribution - Grills, Diffuser, etc.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core
Jet Nozzle 200mm Dia
ABC CONSTRUCTIONS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .