Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.9 LAccepted-AOC | L1 | Accepted-AOC lowest bidder for the work. | |
| 2 | L2₹48.0 L+₹5.1 L (11.8%)Rejected-Finance | L2 | Rejected-Finance other than the lowest bidder | |
| 3 | L3₹58.8 L+₹15.9 L (37.1%)Rejected-Finance 84 A VIJAY NAGAR COLONY LALGHATI PO NAYAPURA BHOPAL 462032 | 462032 | L3 | Rejected-Finance other than the lowest bidder |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
15 Jun 2022, 6:00 pmClosed
Commander Works Engineer Bhopal
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
PROVN OF DEDICATED DISTRIBUTION TRANSFORMER 400 KVA (11 KV TO 433 V) AND ALLIED WORKS FOR CORPS HQ, CENTRAL AMENITIES AND OFFICERS MARRIED ACCN AT DRONACHAL TOP AT BHOPAL MIL STN UNDER GE DRONACHAL
2022_MES_525083_1
83716/E8
Open Tender
Civil Works
Item Rate
180 days
Bhopal
AS PER NIT CONDITION
8 documents required · 8 mandatory
₹500
Yes
GE Dronachal
₹96,000
Yes
8 Jul 2022
19 May 2022
17 Jun 2022
19 May 2022
15 Jun 2022
2 Jun 2022
19 May 2022 - 2 Jun 2022
Amount
Supplying, installing, connecting, testing & commissioning mineral oil immersed, natural air-cooled, outdoor type, double wound (copper) distribution transformer, three phase, 400 kVA rating, non-sealed type, 50 Hz rated frequency, 11 kV high voltage and 415 V low voltage nominal system voltage, minimum 75 kVp basic insulation level, 11000 V/ 433-250 V no-load voltage ratio, connection (vector) symbol Dyn11, 30⁰ positive phase displacement, off circuit tap changing arrangement for voltage variations of +5% to -10% in steps of 2.5% for variation of HV, minimum energy efficiency level 2 (Star 2 as per the notification issued by the Central Government, in consultation with the Bureau of Energy Efficiency and including all the amendments issued up-to-date), 4.5% impedance, ONAN type cooling all as per IS-1180 (Part 1): 2014 including amendment upto and including amendment No. 4 dated 04 Mar 2021 complete with all fittings, accessories and item as specified and as directed. Note: - The energy efficiency level higher than the minimum energy efficiency level as specified here shall be provided without any extra cost in case the transformer of minimum energy efficiency level is not available.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in hard/ dense soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling, hand punning down complete all as specified and as directed. Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
Supplying & laying in trenches, in road cutting and along pole 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
M & L for laying of bricks locally available sub class 'B' bricks, non-modular sizes as per IS 1077: 1992 for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable all as directed.
Supply & laying unreinforced precast concrete cable cover class HV type 1, flat shape, dimension 300 mm X 180 mm X 40 mm as per IS 5820: 1970 complete all as specified and as directed.
Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 6.35 kV/ 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 95 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 300 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 185 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in road cutting complete all as specified and as directed.
M & L for making road cutting surfaces good using 200 mm thick hardcore (broken stone or boulders) of gauge not exceeding 63 mm, deposited, spread and levelled in layers not exceeding 15 cm thick, watered and rammed to a true surface and using cement concrete M15 (Nominal Mix) using 40 mm nominal size graded crushed stone aggregate 150 mm thick finished even and fair and using earth filling for remaining depth complete all as specified and as directed.
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
S & F XLPE cable end termination, heat shrinkable, outdoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 50 sqmm to 95 sqmm complete all as specified and as directed.
Supply, installation, commissioning and testing factory made, CPRI approved, outdoor type LT panel board of adequate size, made of mild steel sheet of 3.15 mm thick, powder coated, dust & vermin proof, front and rear openable, double doors, compartmentalized, general construction confirming to IS: 8623 (Part 1): 1993, locking arrangements, suitable for 3 phase 4 wire 415 V, 50 Hz with 800 Amps rated aluminium bus bar, including mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm including wiring with PVC copper wire of suitable capacity complete all as specified and as directed and shall be comprising the followings: - Incoming: (a) Air Circuit Breaker (ACB) of rated current 800 A, Rated operational voltage 415 V, Rated insulation voltage 1000 V, 4 Pole, 50 Hz AC supply, Rated ultimate short circuit breaking capacity 50 kA, Rated service short circuit breaking capacity 50 kA, Rated short time withstand capacity 50 kA for 1 second, Rated making capacity 105 kA, Rated impulse withstand voltage of main circuit 8 kV, typical opening time 40 ms, typical closing time 60 ms, thermal magnetic release, manual draw out, overload protection, short circuit protection, earth fault protection – 1 No Outgoing: (a) MCCB rated current (In): 400 A, Icu: 36 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic setting, four pole: -2 Nos (b) MCCB rated current (In): 250 A, Icu: 36 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic setting, four pole: -3 Nos (c) MCCB rated current (In): 160 A, Icu: 36 kA, Ics: 100% of Icu, Uimp: 8 kV, Ui: 690 V, IP40, adjustable thermal (80% to 100%) and adjustable magnetic setting, four pole: -4 Nos (d) Digital voltmeter, rating 0 to 500 V: 1 No. (e) Digital ammeter with suitable size CTs (3 Nos), rating 0 -400 Amp: 1 No. (f) LED Indication lamp (RYB): 3 Nos (g) Cable glands of brass of suitable size for cable (h) Wiring with PVC copper wire of suitable size (Note: (a) The approval of GE for panel design and drawing shall be obtained prior to placing order of panel board (b) The rate quoted by tenderer also includes to fix the legs of the panel box in cement concrete M15(Nominal mix) using 20 mm nominal size graded crushed stone aggregate 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm.)
Excavating in trenches not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3.0 in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and exceeding 1.5 m but not exceeding 3 m in depth and getting out in hard/ dense soil complete all as specified and as directed.
Supplying & laying in trenches, in road cutting and along pole 50 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 6.35 kV/ 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 120 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 400 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 120 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 95 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 70 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 25 mm X 4 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 4.0 mm dia galvanised mild steel wire by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 20 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
S & F XLPE cable end termination, heat shrinkable, outdoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 120 sqmm to 185 sqmm complete all as specified and as directed.
M & L for prestressed concrete pole, 11.0 metres long, 152 mm X 152 mm at top and 152 mm X 260 mm at bottom designed for wind load at the site including preparing and painting on prestressed concrete pole with two coats of cement base paint on exposed portion and including making strips of width 30 cm upto 1.5 m from the ground level in black and white shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
S & F gang operated air break switch, three poles, outdoor type, nominal system voltage 11 kV, rated voltage 12 kV, rated normal current 200 Amps, rated frequency 50 Hz, rated one minute power frequency withstand voltage between (i) earth & poles 28 kV (rms) (ii) across the isolating distance 32 kV (rms), rated lightning impulse withstand voltage (i) to earth and between poles 75 kV (Peak) (ii) across the isolating distance 85 kV (Peak), Rated short-time withstand current 25 kA for 3 seconds, rated peak withstand current 63 kA for climatic conditions at the site, mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level for current complete all as specified and as directed.
Supply and fix 11 kV drop out fuse assembly, double stack channel type, triple pole mounted on porcelain HT insulator 6 Nos and mild steel galvanised steel frame rating upto 200 Amp complete with DO fuse and electrical connections, jumpering by ACSR conductor and connectors complete all as specified and as directed.
M & L for cross arms, bracings, supports, clamps, back plates and stay clamp fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
Supply and erection of three piece metal oxide lightning arrestor suitable for 11 kV continuous operating voltage (3 phase) with rated voltage 12 kV (rms) with nominal discharge current rating of 2.5 kA and complete with galvanised clamping arrangements, GI bolts, nuts, washers etc. complete as specified and as directed.
S & F anti-climbing device; spikes type fabricated out of mild steel bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and as directed.
S & F hot rolled low tensile structural steel of grade E165 as per IS 15911: 2010 as in hand rails, half round or other steel section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embedding in concrete and screwing etc. wind ties for roof including securing bolts; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar works complete all as specified and as directed.
M & L for mild steel TMT bars 10 mm dia and over, cut to length, bent to shape required, including hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips and including welding has to be done with minimum 20 cm over lap for new and old of any height. Complete all as specified and as directed.
S & F mild steel screw bolts (machine made), diameter of neck 5 to 10 mm with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, exceeding 5 cm but not exceeding 10 cm long complete all as specified and as directed.
Fixing only galvanized steel chain link fence fencing including line wires any mesh, size and type to any type of standards, rails, straining bolts, etc. including provn of binding wire complete all as specified and as directed.
Supply only galvanized steel chain link fence fabric of mesh size 50 mm X 50 mm, made out of 2.50 mm nominal dia of mesh wire.
S & F hot rolled medium and high tensile structural steel of grade E165 as per IS 15911: 2010 as in framed work such as grills, grating, etc., with ends of bars of shouldered and/or riveted, or forged into spikes, framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework water tanks and similar work complete all as specified and as directed.
Surface excavation not exceeding 30 cm deep and averaging 15 cm deep and getting out in hard/ sense soil complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
M & L for cement concrete in foundation, filling and mass concrete in M7.5(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for hardcore (broken stone or boulders) of gauge not exceeding 63 mm, deposited, spread and levelled in layers not exceeding 15 cm thick, watered and rammed to a true surface complete all as specified and as directed.
M & L for brick work with sub class 'B' bricks, non-modular sizes as per IS 1077: 1992, straight or curved on plan exceeding 6 m mean radius built in cement mortar 1:6 complete all as specified and as directed.
Material and labour for plastering 15 mm thick (in two coats of 10 mm and 5 mm thick) on fair faces of brick work or concrete surfaces (on vertical surfaces) in cement mortar 1:4 with integral water proofing compound finished even and fair complete all as specified and as directed. Note: - Water proofing compound shall be measured and paid for separately.
M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate in roof kerbs or mud stops, rounded or chamfered on edges complete all as specified and as directed.
M/S RAKESH TRADERS
POONAM ELECTRIC INDUSTRY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .