Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical | Accepted-Technical Responsive |
| 2 | Accepted-Technical | Accepted-Technical Responsive |
| 3 | Accepted-Technical | Accepted-Technical Responsive |
Tender Value
₹13 L
EMD Value
₹26,000
Closing Date
21 Feb 2026, 2:00 pmClosed
Executive Engineer ED Sumbal Near I
Office of the Executive Engineer ED Sumbal Near Irrigation Colony Sumbal
Creation of 200KVA Dedicated Sub Station for Electric Vehicle Charging Station for Indian Oil Crop Ltd at Kirmania Filling Station Sumbal Bandipora under deposit Contribution Head
2026_PDD_301578_1
EDSbl 32 of 2025-26
Open Tender
Electrical Works
Turn-key
45 days
Sumbal
as per SBD enclosed
7 documents required · 7 mandatory
₹1,000
Executive Engineer ED Sumbal
₹26,000
28 Feb 2026
28 Jan 2026
23 Feb 2026
28 Jan 2026
21 Feb 2026
29 Jan 2026
28 Jan 2026 - 29 Jan 2026
Creation of sub station 200KVA
Sub Station Part
SITC of 200kVA 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound , and with LV Cable Box having detachable Al. Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable. ( X-mer without OCTC (Off Ckt Tap Changer))
SITC of 11 Mtr. Long Pole,ST-410 SP56) including pit excuavation 1/6th of pole height
SITC of Galvanized Nuts & Bolts.
SITC of GI Channel Cross arms (100X50X6 mm) and (75X40X6 mm) , V Cross arms etc including transformer Belting, Clamps etc. fabricated out of Galvanised steel of different sizes to be fixed with G.I Nuts and bolts and washers.
SITC of Earthing of Sub-Station - Excavation of earth Pit of 650 mm dia. & depth 3000 mm,Installation of earthing Pipe of 40 mm nominal bore and 4 mm wall thickness and length 2.5 m long as per IS-1239.GI strip for neutral earthing of size 25mm x 3mm for connection of X-mer body,G.O set & LA as per IS-2629/85,Gi nuts and bolts refilled with earth enhancement materials & earth Chamber made of Brick masonary with RCC Slab Cover.
SITC of 11kV Gapeless Surge Arrestor ,9 kV,10 kA,LA with polymer housing station type with all accessories.
SITC of 11 kV G.O AB Switch 3-Phase,3-Pole of Capacity 200A Vertical type with arrangements for pad locks and operating rod. The operating rod should be G.I Pipe (B Class) of 25 mm dia of requisite length.
SITC of LT Distribution Box for: 200 kVA DTR with 315 MCCB 3P 25 kA for incomer & 160 Amp MCCB 3P 16 kA 3 No.s for Outgoing Circuits.
SITC of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
SITC of 11 kV Horn Gape 3-phase Fuse set of capacity 200 A with all accessories.
SITC of 11 kV Polymeric composite Disc insulator 12 kV,minimum failing load of 45 kN,lighting impulse of 75 kV positive & 80 kV negative and with creepage distance of 320 mm with fittings
SITC of PVC Cable 240 mmSq. XLPE Including Al thimbles and Bimetalic SL Clamps (as per latest specifications & drawings adopted and approved by the department).
Providing and Laying of Cement Bottoming 1:2:4 mix as per REC standards 0.66cum/pole including muffing 15 cm above ground level plaster and curing of concrete as per standard adopted by KPDCL
SITC of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25X3 mm
SITC of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
SITC of GI Barbed wire for Anti Climbing
SITC of Danger Plates with Clamps
SITC of Red-Oxide and Aluminium paint for painting of Poles
SITC of 11 kV HT METERING CT AND PT OPERATED 11kV Pilfer resistant metering cubicle for 3phase 4 wire metering system made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Panel having two compartments upper Meter compartment and lower CT/PT compartment. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The metering panel shall be provided with two No G.I channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening the LV chamber door. Single Phase, Single core, single ratio, Epoxy resin Cast Current Transformers suitable for 11kV, copper wound primary type with rated burden 5VA and accuracy class 0.5 or better and conforming to IS2705 (part-I & II) amended upto date. ISF shall be upto 5 ( continued in next row )
The CT ratio shall be as under: i. 15/5 for 200kVA DT PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm² (RYB) and for PT wiring minimum wire size shall be 2.5 mm² (RYB). Copper Lugs preferably ring type duly crimped for termination of wires and tapes Grounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber. The CTs, PT meter and 11kV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10mm² 3Ph3 Wire HT CT/PT operated Fully static Smart Tri-Vector Energymeters DLMS Compliant Category 'C' with RS 232 port for modem compatibility. 11kV/110V, Ph-Ph (3P,3W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) etc. Independent flexible PVC pipes for CT wiring and PT wiring of appropriate size from HT compartment to meter compartment Pedestal made out of G.I Channel of size 75 x 40 mm or angle iron of size (65 x 65 x 5) mm, duly painted as per site requirement for mounting of metering panel including concrete foundation wherever required including cost of nuts and bolts 3 Core 11 kV Aluminium cable XLPE armoured 35 mm² including cost of clamp for its fixing where ever required. 20 Mtrs Cable termination kits suitable for 3 x 35 mm² XLPE Cable (Indoor/Outdoor) 2 set each Earthing by way of 40 mm 2.5 mtr long GI Pipe. Job includes , excavation, enhancement material and Main Hole Chamber (500x450x600)mm with frame and cover. 4 No
HT Part ( any left over part in Ht line is reflected in sub station parts to avoid different rates for same material) (GI V cross etc )
SITC of 13 Mtr. Long Pole,ST-410 SP69) including pit excuavation 1/6th of pole height
SITC of 70 mm² AB (HT) Cable (3 x 70 + 1x 70 insulated ) mm² XLPE (11 kV, 3C + Earth)
SITC of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
SITC of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25X3 mm
SITC of Red-Oxide for painting of Poles
SITC of Aluminium paint for painting of Poles
Providing and laying of Cement Bottoming 1:2:4 mix as per REC standards 0 .78 cum/pole including muffing 15 cm above ground level plaster and curing of concrete
SITC of GI Barbed wire for Anti Climbing
SITC of Danger Plates with Clamps
stage.html
html • 0.02 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.57 MB
BOQ_978537.xls
BOQ • 0.32 MB
SBD32.pdf
Tender Documents • 1.46 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .