Replacement of AHUs and TFAs at T1 and T4 Terminal Buildings at CIA Phase-V
2026_AAI_289973_1
AAI/CHN/E-E/HVAC/AHU-PH-V/2026
Open Tender
Electrical Works
Item Rate
Work
Please refer Tender documents.
14 documents required · 14 mandatory
₹1,180
₹4.2 L
10 Sept 2026
10 Sept 2026
5 Oct 2026
10 Sept 2026
3 Oct 2026
10 Sept 2026
10 Sept 2026 - 19 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply of factory built floor mounted chilled water double skin type horizontal/vertical Air Handling Units made of 43mm thick panels consisting of pre plasticized G.I casing of thickness 0.8mm outside layer and 0.8mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, 2mm thick base frame at bottom, complete with blower section with Backward curve blower, blower suitable for static pressure as detailed below, mixing chamber for fresh and return air, minimum 2 bend GSS/PVC drift eliminators, cooling coil section with aluminium finned copper tubes(tube thickness not less than 0.5mm) cooling coil, filter sections with 50mm thick metal viscous /washable synthetic type air pre-filters, belt drive package with TEFC drive motor of efficiency class IE4 suitable for 415 ± 10% volts, 50Hz, 3 phase, AC Supply, suitably designed for variable frequency drive applications, drain connections with outlet pipe dia of min 50mm, stainless steel (18G) drain pan with PUF insulation, 100 mm dia. dial type pressure gauges and industrial type thermometers at the inlet and outlet of coil, 2 nos of access doors on filter and fan section each, with lighting provision in filter and fan sections & limit switches interlocked with doors so that AHU turns off during access door opening, auto purge valve wherever required, necessary vibration isolation arrangement, necessary control cable for all wiring inside the unit etc. and having sufficient space to accomodate UVGI system etc. Complete as per technical specifications and of following capacities & specifications: | |||||
| 1.1 | 60 TR Capacity, 24,000CFM
a) Static pressure -80mm WC
b) Cooling coil 6 Rows deep
c) Filters with Filtration standard-90% efficiency down to 10 Microns
d) Supply blowers with motors - 1 No
e) Two way modulating valve with rotary type actuator-1 No
f) MS Y strainer-100mm dia-1 No
g) 25mm ball valve for inlet and outlet- 2 nos
h) 100 mm dia. dial type pressure gauges- 2 nos.
i) 100 mm dia industrial type thermometers-2 nos. | 1 | Job | - | - |
| 1.2 | 45 TR Capacity, 18,000CFM
a) Static pressure -80mm WC
b) Cooling coil 6 Rows deep
c) Filters with Filtration standard-90% efficiency down to 10 Microns
d) Supply blowers with motors - 1 No
e) Two way modulating valve with rotary type actuator-1 No
f) MS Y strainer-80mm dia-1 No
g) 25mm ball valve for inlet and outlet- 2 nos
h) 100 mm dia. dial type pressure gauges- 2 nos.
i) 100 mm dia industrial type thermometers-2 nos. | 2 | Job | - | - |
| 1.3 | 37.5 TR Capacity, 15,000CFM
a) Static pressure -80mm WC
b) Cooling coil 6 Rows deep
c) Filters with Filtration standard-90% efficiency down to 10 Microns
d) Supply blowers with motors - 1 No
e) Two way modulating valve with rotary type actuator-1 No
f) MS Y strainer-80mm dia-1 No
g) 25mm ball valve for inlet and outlet- 2 nos
h) 100 mm dia. dial type pressure gauges- 2 nos.
i) 100 mm dia industrial type thermometers-2 nos. | 1 | Job | - | - |
| 2Supply of factory built floor mounted chilled water double skin type Treated Fresh Air Units made of 43mm thick panels consisting pre coated G.I casing of thickness 0.8mm outside layer and 0.8mm inside layer with polyurethane foam(PUF) insulation factory injected between them by injection moulding machine, 2mm thick base frame at bottom, complete with blower section with Backward curve blower, blower suitable for static pressure as detailed below, mixing chamber for fresh air, minimum 2 bend GSS/PVC drift eliminators, 2 nos x 4 row deep (8 row) cooling coil section with aluminium finned copper tubes(tube thickness not less than 0.5mm), filter sections with 50mm thick metal viscous /washable synthetic type air pre-filters, belt drive package with TEFC drive motor of efficiency class IE4 suitable for 415 ± 10% volts, 50Hz, 3 phase, AC Supply, suitably designed for variable frequency drive applications, drain connections with outlet pipe dia of min 50mm, stainless steel (18G) drain pan with PUF insulation, 100 mm dia. dial type pressure gauges and industrial type thermometers at the inlet and outlet of coil, 2 nos of access doors on filter and fan section each, with lighting provision in filter and fan sections & limit switches interlocked with doors so that unit turns off during access door opening, auto purge valve wherever required, necessary vibration isolation arrangement, necessary control cable for all wiring inside the unit etc. Complete as per specification and of following capacities & specifications: | |||||
| 2.1 | 60 TR Capacity, 24,000CFM
a) Chilled water Cooling coil 2 nos x 4 row deep (8 row)
b) Static pressure -80mmWC
c) Filtration standard-90% efficiency down to 10 Microns
d) Supply blower - 1 No
e) Two way modulating valve with rotary type actuator-1 No
f) MS Y strainer-100mm dia-1 No
g) 25mm ball valve for inlet and outlet- 2 nos
h) 100 mm dia. dial type pressure gauges- 2 nos.
i) 100 mm dia industrial type thermometers-2 nos. | 5 | Job | - | - |
| 3Installation, Testing & Commissioning of AHU / TFA of following capacity at Basement of T1 and T4 on floor using necessary concrete blocks / cubes for successful operation complete as required. | |||||
| 3.1 | 24000 CFM AHU | 1 | Job | - | - |
| 3.2 | 18000 CFM AHU | 2 | Job | - | - |
| 3.3 | 15000 CFM AHU | 1 | Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.32 MB
TENDERDOCUMENT.pdf
Tender Documents • 3.59 MB
BOQ_338773.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .