Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.1 LAccepted-AOC NO 92 KUVEMPUNAGAR 2ND STAGE JALAHALLI EAST BANGALORE 560 014 | 560014 | L1 | Accepted-AOC Accepted being L1 | |
| 2 | L2₹43.0 L+₹3.2 L (8.15%)Rejected-Finance SHOP NO 48 HOSANNA LAXMI VENKETESWARA LAYOUT 2ND CROSS MARAGONDANAHALLI K R PURAM POST BANGALORE 560036 | BENGALURU URBAN | KARNATAKA | 560036 | L2 | Rejected-Finance Rejected. Quoted rates are higher than L1 |
Tender Value
₹46 L
EMD Value
₹92,000
Closing Date
12 Dec 2023, 6:00 pmClosed
Garrison Engineer M AF Jalahalli
Garrison Engineer M AF Jalahalli Bangalore 560013
COMPREHENSIVE MAINTENANCE OF MISC B R AND E/M WORKS IN OTM AND MD ACCN UNDER RESPECTIVE AGEs OF WEST AREA OF AFS JALAHALLI
2023_MES_626787_1
8846/E8
Open Tender
Civil Works
Item Rate
181 days
Garrison Engineer M AF Jalahalli
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE AF MAINT JALAHALLI PUBLIC FUND ACCOUNT
₹92,000
29 Dec 2023
10 Nov 2023
14 Dec 2023
10 Nov 2023
12 Dec 2023
23 Nov 2023
10 Nov 2023 - 16 Nov 2023
Amount
SCHEDULE A BOQ
Demolition of cement concrete (unreinforced) in ground floors and pavings not exceeding 15 cm thickness (below or above ground level) complete all as specified and directed. Note :- The material obtained from demolition shall be disposal outside MD land and the unit rate is deemed to be included.
M&L Two coats of cement slurry in CM(1:2) proportion on complete horizontal and vertical area of sunken floor over 15mm thick base plaster in CM (1:4) over sunken portion/roof etc mixed with WPC complete all as specified and as directed. Note: WPC will be measured separately as Supply only.
Supply Only integral water proofing compound complete all as specified and as directed. Make:-Dr. Fixit Pidi Proof or equivalent
Applying evenly a tack coat of industrial bitumen 85/25 at the rate of 1.2 kg per sqm including cleaning surface complete all as specified and as directed.
M&L Plain Cement Concrete Type E2 1:5:10 (using 40 mm graded granite stone aggregate) in sunken floors, filling and mass concrete complete all as specified and directed.
M&L Repair of leakage/seepage from the Nahani trap/ floor trap of kitchen/ bathroom/ washbasin of the upper Qtr, in any position at any height, complete including change of floor trap, PVC horinzontal pipe embeded in floor in bathroom or kitchen making good to the damage portion of flooring, laying and matching of tiles in the existing flooring, complete all as specified and directed by Engineer-in-Charge
M&L Repair of leakage/seepage from the wall/ door bend /door tee/ 'Y' junction/ 'T' Junction of soil pipe / waste pipe/ vent pipe of kitchen/ bathroom/WC of the upper Qtr or at the ground floor Qtr including change of any damage soil waste pipes or fittings of any shape, specification and size, making good to the damaged portion of wall with brick work in cement mortar 1:6 or cement concrete 1:2:4 and plastering to wall in CM 1:4 and finished the surfaces matching to existing wall complete to avoid the leakage/ seepage at the site of work as directed and as specified.
Note for item No 08 :- (a) Find out main cause of leakage and take necessary steps to resolve / rectify. (b) Replace existing tiles in case leakage through NT/FT. (c) The rate also include provision of new NT/FT. (d) The unit rate is also deemed to be included for reqd bonding chemicals to arrest the leakage/seepage as directed by the manufacturer's specification. Make : M/s Sika Chemical, M/s Pidilite, M/s Dr Fixit
Taking down chowkhat or frame(wooden/steel) exceeding 1.50 Sqm not exceeding 4.0 Sqm each with shutter (with out taking off shutters from the frame) all as specified and as directed.
Taking down shutters of any description exc 1.0 Sq.m and n.exc 2.0 Sq.m each complete all as specified and directed.
Refixing of shutters of any description n.exc 1.0 sqm each, in same opening including taking down, petty repairs etc complete all as specified and directed.
Refixing of shutters of any description exc 1.0 sqm but not exc 2.0 sqm each, in same opening including taking down, petty repairs etc complete all as specified and directed.
Cutting holes in stone wall exc half brick and n.exc one brick in cement mortar for inserting hold fasts/lugs and making good dismantled portion in cement mortar 1:3 or 1:2:4 type B-1 concrete as required complete all as specified and as directed.
S&F MS work (flat iron) 25mm x 3mm thick) in small articles such as hold fast and similar smaal articles conforming to Fe 290 Gde E-165 including taking down existing one complete all as directed.
M&L Second class hard wood plain, solid, straight Chowkats and frames, wrought, framed, rebated on the solid, rounded or chamfered, put together with glue pinned at joints complete all as specified and directed.
Supply and Fixing 30 mm thick factory made flush shutter solid core construction with block board core and plywood face panels, comercial type on both faces complete all as specified and directed.
S&F Factory made 35mm thick Glazed and skeleton shutters, open rebated and prepared to receive glass, gauze, etc. divided into squares, with plain, chamfered or rounded, mitred and rebated sash bars, any numbers, edges of framing plain, chamfered or rounded. fitted with cut and mitred beads for securing glass, etc.; sizes of me-mbers of shutters as specified in SSR Part I, Section 8, clause 8.24 (a); all as specified and directed.
Preparation of new wood or wooden surface of any description not otherwise described over 10cm width or girth and applying two coats of synthetic enamel paint over a coat of pink primer complete all as specified and directed
Supply and fixing 100mm long Butt hinges medium weight cold rolled stainless steel, and fixed complete all as specified and as directed.
Supply and fixing 200 mm long aluminum anodized barrel tower bolt extruded section complete all as specified and as directed.
S&F Aluminum handles cast type anodised 200 mm long complete all as specified and as directed.
S&F 250mm Aluminium alloy, anodised, sliding door bolts with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extrudud sections or cast- aluminum alloy and fixed complete all as specified and as directed.
S&F Stainless steel wire cloth 0.36mm nominal dia of wire and average width of aperture 1.4mm complete all as specified and directed.
S&F Floor door stopper of aluminium alloy body and tongue anodized with hard drawn steel spring fixed in floor overall 140mm complete including taking down existing one all as specified and as directed.
S&F Plain fillets, square, rectangular or triangular in section, clean sawn, se-cured with nails or brads in section area 6 sq.cm but not exc 13 sq cm including taking down exisiting one complete all as specified and as directed.
Taking down chowkhat or frame(wooden/steel) not exceeding 1.5 Sqm each with shutter (with out taking off shutters from the frame) all as specified and as directed.
S&F in Steel windows with side hung shutters including projecting type hinges, frame with steel handle, and steel peg stay, complete with glazing bars, dovetailed or welded complete all as specified and directed.
S&F 4 mm thick sheet glass ordinary quality and glazing complete in square n exc 0.50sqm each complete all as specified and directed.
S&F Solid PVC Door Frame of size 50mm x 47mm made out of 5mm plain colour PVC sheet reinforced with MS Square tubecomplete all as specified .
S&F Factory made Solid PVC Door Shutter 30mm thick (style) consisting of frame made out of MS tubes for top & bottom rails. MS frame shall be covered with heat moulded plain colour PVC 'C' channel having a PVC sheet strip of 20mm width stuck inside with solvent cement for stiles and plain colour PVC sheets for top rail, lock rail & bottom rail on either side & as gap insert for top rail & bottom rail. Panelling of plain colour PVC sheet to be fitted in the MS frame welded / sealed to the stiles & rails with suitable PVC sheet beading and jointed together with solvent cement complete all as specified.
S&F Butt hinges 75 mm long medium weight cold rolled stainless steel complete all as specified and as directed.
Supply and fixing 150 mm long aluminum anodized barrel tower bolt extruded section complete all as specified and as directed.
Supply and fixing aluminum handles cast type anodized 150 mm long complete all as specified and as directed.
Supply and fixing in repairs 200 mm long aluminum anodized barrel tower bolt extruded section complete all as specified and as directed.
Supply and fixing in repairs 150 mm long aluminum anodized barrel tower bolt extruded section complete all as specified and as directed.
Supply and fixing 100mm long Butt hinges medium weight cold rolled stainless steel, fixed in repair to wooden frame/welded to metal frame complete all as specified and as directed.
Supply and fixing in repairs butt hinges 75 mm long medium weight cold rolled stainless steel complete all as specified and as directed.
S&F Floor in repairs door stopper of aluminium alloy body and tongue anodized with hard drawn steel spring fixed in floor overall 140mm complete including taking down existing one all as specified and as directed.
Supply and fixing in repairs aluminum handles cast type anodised 200 mm long complete all as specified and as directed.
Supply and fixing in repairs aluminum handles cast type anodised 150 mm long complete all as specified and as directed.
Supply and Fixing in repairs 250mm Aluminium alloy, anodised, sliding door bolts with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extrudud sections or cast- aluminum alloy and fixed complete all as specified and as directed.
S&F in repairs 250mm, ordinary Mild steel rat tail rod pattern springs including roller and roller plate complete all as specified and directed.
S&F Stainless steel wire cloth 0.36mm nominal dia of wire and average width of aperture 1.4mm complete including taking down existing one all as specified and directed.
M&L 2nd class hard wood small fittings such as brackets of any type, latch and hinge blocks, shaped door and window stops and the like, including all necessary' labours; articles not exceeding 200 cu. cm each including dismantling existing all as specified & directed.
S&F Double action floor spring hydraulically regulated made up of minimum 1.25 mm thick aluminium alloy sheet foundation box, main body with stainless steel covert governing pivot made of brass, other parts made of mild steel heavy duty including taking down existing wire cloth all as specified and directed.
S&F Aluminium body door closer hydraulically regulated,designation No.3, universal type, suitable for door shutters of 851 to1000 mm in width and of weight between 61 to 80 kg and fixed including taking existing one complete as directed by Engr-in-charge.
Resecuring without taking down chowkhats or frames but with shutters (without taking off shutters from the frames) not exc 1.5 sqm each complete all as specified and as directed.
Resecuring without taking down chowkhats or frames but with shutters (without taking off shutters from the frames) exc 1.5 sqm but n exc 4 sqm each complete all as specified and as directed.
Fixing only in repairs loose wooden pelmet boxes/curtain rods in position by using rawl plugs/wooden gutties fixed with MS holder clips complete incl tightening of screws etc complete in all respect length of each pelmet n exc 2.50 mtr long complete all as specified and as directed.
Supply and fixing in repairs second class hard wood top rail of size 100 mm wide and 35 mm thick including making of grooves and fixing using fevicol and wooden pinning including preparation of new surfaces and applying two coats of synthetic enamel painting to match with existing over over one coat of pink primer complete all as specified and directed by Engr-in-charge.
M&L in repair to middle/lock rail of doors 150 mm wide with second class hard wood 35 mm thick including making of grooves and fixing,using fevicol and wooden pinning and treated with two coats of synthetic enamel painting over one coat of pink primer complete all as specified and directed by Engr-in-charge.
S&F 5mm thick rubber beading strips of entrance doors having width exc 3cm to not exc 5cm to arrest entry insects including taking down existing one complete all as specified and as directed
Applying silicon sealent on joints of wall,cill jambs roof etc complete all as specified as directed
Minor repair to aluminum/glass doors, windows, partitions and making good the same (i.e. Handles, hinges, rubber beadings, clips etc) complete all as specified and directed.
Easing of door shutters for easy closing/opening and tightening of hinges or changing the position of hinges, adjustment of tower bolts, sliding bolts with new screws etc, Size of door upto 2 Sqm complete all as specified and directed by Engineer-in-Charge.
Easing of window shutters, kitchen cupboard shutters, show case shutter drawers including fixing of screws adjusting handles, knobs tightening piano hinges including misc small adjustments , size of window upto 1.5 Sqm. complete all as specified and directed by Engineer-in-Charge
Providing and injecting chemical for post constructional Anti TermiteTreatment at points of contact of wood work by chemical emulsion (in oil or kerosene based solution) @ 0.5 litre/hole by drilling 6mm dia holes at a downward angle of 45 degree at 150mm centre to centre and sealing the same all as specified and directed.
Supply and fixing in repairs bottom rail 200 mm wide of second class hard wood 35 mm thick including making of grooves and fixing new bottom rail using fevicol and wooden pinning and treated with two coats of synthetic enamel painting over one coat of pink primer complete all as specified and directed by Engr-in-charge.
Taking down of aluminum/Glass doors carefully and re-fixing in same opening including necessary repairing/cleaning/greasing etc and make the same fully functional all as specified and directed.
M&L Checking of joinery (wooden/steel) iron/ aluminium mongery, pelmet box, door springs etc requiring carpentry work and carrying out minor repairs such as tightening of screws/ nails, fixing glass panes, minor adjustment of joinery, door etc. including petty repairs material like screws/ nails, plug etc to make it functional complete all as specified and as directed by Engineer-in-Charge. Note :- In case any replacement of new handles, Butt hinges, cupboard knobs, floor door stopper and pelmet box shall be measured and paid as supply only seperately. However, the unit rate is deemed to be included for labour element.
Supply only wooden pelmet boxes/curtain rods in position by using rawl plugs/wooden gutties fixed with MS holder clips complete incl tightening of screws etc complete in all respect length of each pelmet n exc 2.50 mtr long complete all as specified and directed.
Supply only 200mm extruded aluminum alloy handles , fabricated type, anodised complete all as specified and directed.
Supply only aluminum handles cast type anodised 150 mm long complete all as specified and directed.
Supply only Floor door stopper of aluminium alloy body and tongue anodized with hard drawn steel spring fixed in floor overall 140mm complete all as specified and directed.
Supply only 100mm long Butt hinges medium weight cold rolled stainless steel, and fixed complete all as specified and directed.
Supply only 40 mm dia cupboard knobs fixed with nut, screw and washer of brass polished complete all as specified and directed.
S&F in repair Stainless Steel Door Magic Eye with Flap to wooden doors , unique design any type complete all as specified and directed
Supply and fixing 4mm thick figured glass pin head type and glazing with oil putty or wooden beads in squares n. exc. 0.50 Sqmtr each pane including Hacking out old borken glass (any thickness, size, quality or description) from wooden frames/steel frames glazed with putty or fixed with beads complete all as specified and directed.
Taking down the existing locking system, contains any number of levers repalcing the strucked/damaged levers, applying oil to all parts and making functional properly and refixed in position complete all as specifed and as directed
S&F Sinks with drainage board made of stainless steel lmm thick kitchen or laboratory with plugs,washers and wastes; including bedding in cement mortar to dwarf wall or including fixing cantilever brackets and connecting union to pipe overall size 915mm x 460mm bowl size 410mm x 330mm x 160mm fixed in repairs all as specified and directed. Make : M/s Diamond / Nirali / Amco / TATA.
S&F Plate rack of size 65 cm x 96 cm made of stainless steel fixed in repairs complete all as specified.
S&F in repair looking mirror 3 mm of size 600mm x 450mm on commerical ply wood 6mm thick with PVC/ wooden moulding beading fixed to wooden plugs with chromium plated brass, screws and cup, washers, aluminium frame and fixed complete all as specified and directed.
S&F PVC body cabinet box mirror of size 350mm X 450mm X 10mm PTMT alloy of approved pattern and design including taking existing one complete as directed by Engr-in-charge.
M&L 25mm dia mild steel powder coated drapery rod out to length required without joint in between and fixed at openings including taking existing one complete as directed by Engr-in-charge.
Supply and Fixing in repairs Mild steel powder coated fancy type brackets fixed at both the end of drapery rod of same colour and type of drapaery rod as directed.
S&F 6mm thick frame less bevelled edge mirror fixed with steel stud as per direction of Engineeer-in-charge including taking down all as specified and as directed.
S&F 300mm of arc size, 5mm thick corner glass shelf with stainless steel brackets, stainless steel railing in bathroom and fixed to wall with brackets including removing the existing fitting as per manufacturer's instructions and as required at site complete all as specified and as directed
M&L 18/19mm thick Prelaminated particle board, interior Grade, prelaminated one side with decorative choice lamination and other side balancing white lamination, fixed with screws to timber frame work including taking down complete all as specified and as directed.
M&L 6 mm thick teak wood lipping for 18/19 mm thick particle board fixing with nails complete including taking down all as specified and as directed.
S&F 40 mm dia cupboard knobs fixed with nut, screw and washer of brass polished complete including taking down existing one all as specified and as directed.
S&F Continuous (piano) hinges, stainless steel bright finish or electrogalvanised of 40mm width of flaps (when open) complete including taking down all as specified and as directed.
S&F Magnetic catches with 8mm dia steel ball and brass body and striking plate including taking down in complete all as specified and directed.
Supply and fixing in repair aluminium anodized hasp and staples safety type with mild steel hinge pin incl bolt to hinge plate fixed with screws of 100mm length complete all as specified and as directed.
Supply & fixed in repair of 12 mm thick ,7 ply, plywood ,grade BWR ,type BB fixed to wooden frame work in wall with nails including taking down all as specified and as directed.
S&F Decorative laminates of 0.90 mm thick type matt finish, colour and pattern as approved including taking down existing one complete all as specified and as directed.
Taking down MS window shutters n. exe 1.5 sqm through cutting of existing any type of hinges, handle and tower bolt and fixing new box type hinges, MS handle and MS tower bolt the same window by welding. The quoted rates shall be included the following aspect:- (a) Cutting of existing piano hinges, handle and tower bolt from window frame and shutter. (b) Fixing of removed shutter in the same frame on MS box type hinges 100mm, MS handle 100mm and MS tower bolt 100mm by welding. (c) Easing and adjusting the shutter before re-fixing if found required. (d) Finishing the window frame and shutter with two coat of enamel paint. (e) Necessary scaffolding material to be included as the building height is more than 10mtr. Note : Box type hinges, handle and tower bolt will be measured separately as supply only and labour element is deemed to be included in this item.
Supply only MS Box type hinges 50mm.
Supply only MS Handle 100mm.
Supply only MS tower bolt 75mm
S&F in repairs Stainless steel peg set of having 5 pegs powder coated fixed to wall surface with pvc plug and screw complete including taking down all as specified and as directed.
Supply and fixing in repair steel window handles with nuts and bolts or with screws including welding/fixing with nuts complete all as specified and directed by Engr-in-charge.
Supply and fixing in repair steel window peg stay all as specified and directed by Engr-in-charge.
Supply and fixing in repair steel window hinges as per sample by welding all as specified and directed by Engr-in-charge.
M&L Hacking out old broken glass (any thickness, size, quality or description) from wooden frames/steel frames glazed with putty or fixed with beads and material and labour for 4mm thick plain sheet glass ordinary quality and glazed with oil putty or fixed with fillets 2nd class hard wood of sectional area not exc 3 Sqcm and glass not exc 0.5 sqm each pane complete all as specified and directed.
M&L Hacking out old broken glass (any thickness, size, quality or description) from wooden frames/steel frames glazed with putty or fixed with beads and material and labour for 4mm thick plain sheet glass ordinary quality and glazed with oil putty or fixed with fillets 2nd class hard wood of sectional area not exc 3 Sqcm and glass exc 0.5 sqm each pane complete all as specified and directed.
Dismantling floor, floor hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises and Joint free Non - skid Ceramic tiles 7 to 8 mm thick (square/ rectangular) area of each tile of size exc 0.09 Sqm but n exc 0.18 Sqm in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match incuding screed bed or bedding layer of mortar 15mm thick for laying floor finishes in cement mortar (1:4) complete all as directed.
Dismantling floor, floor hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises and Material and labour for Glazed ceramic coloured tiles 450 x 300 mm x 7/8 mm thick set and jointed in neat cement slurry and pointed in white or coloured cement to match with tiles on vertical surface such as skirting/ dado including 10mm thick 1:3 backing coat complete all as specified and directed.
Petty repair to wooden door,PVC door, cupboard door, wardrobe door with shutter (size not more than 2sqm) including roller, windows, etc with minor repair and easying and adjustment/aligment to openable with assessories if requred any ( like roller of cupboard door, butt hinge, handle, tower bolt, beading, bow handle, etc complete) complete all as directed.
S & F in repair rubber beading suitable for fixing 4 mm/5mm thick glass in aluminium window/doors. etc complete all as specified and directed.
S&F in repair star lock for window incl all necessary fittings complete all as specified and as directed.
S&F in repair aluminium windows bearing per windows complete all as specified and as directed.
S&F in repairs 0.56 mm thick Plain, Aluminium sheeting, Alloy 31000 H4 in ridges, hips, valley gutter, drip and straight flashing (length and girth as fixed)
S&F False ceiling using GI snap grid size 60x60cm with main runner 38x24,wall angle & cross tee 29x24mm wall angle 24x24mm suspended with 4mm dia GI Wire fixed with steel dash fasteners carrying max load upto 8.1 Kg/Sqcm with 4mm thick designer ceiling board (Lake & Hill) all as per Everest regular T-2430 or equivalent (Make-Ramco/Charminar/Armstrong) including dismantling all as specified and as directed.
Petty repairs to refixing the existing Wash hand basin and Sinks made of stainless steel 1mm thick kitchen flat back with including fixing cantilever CI/Angle iron brackets embedded in concrete block including connecting waste coupling 32mm bore, including bedding, waste fitting, waste pipe in cement mortar on to dwarf wall and connecting union to pipe, filling gap in white cement and all neccessary fittings to fixed in repair (including taking and refixing the same position) complete all as directed.
S&F PVC (SWR) 'P' trap of 110 mm bore including taking down all as specified and directed.
S&F PVC (SWR) 'S' trap of 110 mm bore including taking down existing all as specified and directed.
S&F Wash basin vitrous china (flat back and angle back Type) size 580x400mm including taps waste chain and plug and porceline stopper but brackets including cutting for and pinning in ends of brackets or erecting stand with waste pipe ,fixed including taking taking down existing one complete as directed by Engr-in-charge.
S&F Rotational moulded polythene water storage tank of 1000 Ltrs capacity (three layer white colour) cylinderical vertical with closed top including 3 Nos GI check nuts and tank nipple of 25mm bore for inlet and outlet, 25mm bore ball valves high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball hoisted and fixed in position all as specified in SSR part -I including taking down of old unserviceable tank complete all as specified and directed.
Supply and fixing in repairs 20mm dia gun metal gate valve with iron wheel screwed both ends for iron pipe and all as specified and directed.
S&F Vitreous china squatting pan 'Orissa' Pattern size 580x440mm white with integral foot rests (excluding flushing cistern and flush pipe ) including provision of lime concrete bedding fixed in repairs all as specified and as directed.
S & F in repairs Bib taps fancy type chromium plated with crutch or butterfly handle screwed down screwed for galvanised iron pipe or for brass ferrule and fixed complete for 15 mm bore all as specified and as directed.
S&F CP Hand shower (Health Faucet) with 1M Flexible tube with 8mm dia wall hook with NRV (Back flow preventor) including taking down existing one complete all as specified and as directed.
S&F Angular stop cock, valves high pressure screwed both ends iron pipe or for unioins 15mm dia, (Make: Parryware /Hindware/Cera) including taking existing one complete as directed by Engr-in-charge.
S&F Glass self assembly including taking existing one complete as directed by Engr-in-charge. (Make : Parryware /Cera/Hindware all as specified and as directed.
Supply and fixing in repairs plastic water closet seat cover white or tinted, closed pattern with flat bottom , and cover and mild steel chromium plated or aluminised hinge device and including taking existing one complete as directed by Engr-in-charge. Make: Parryware/Hindware/Cera
S&F Towel Ring round including taking existing one complete as directed by Engr-in-charge. Make:Hindware / Parryware/Cera all as specified and as directed.
S&F in repairs CP 2 way bib cock with wall flange fancy type screwed down screwed for iron pipe in repairs 15mm bore (Make:Hindware / Parryware/Cera) complete all as specified and as directed by Engineer-in-Charge
S&F in repairs 32mm bore low density polyethylene (LDPE) pipes of pressure rating 6 kgf/sqcm for WHB/Sink including taking down all as specified and as directed.
S&F CP Concealed stop cock, Regular body with adjustable wall flange screwed down screwed for iron pipe 15mm bore (Make:Hindware / Parryware/Cera). including taken down existing one complete all as specified and as directed by Engineer-in-Charge
S&F CP sink cock with swinging casted round shape spout screwed down screwed for iron pipe in repairs 15mm bore including taking down existing one complete all as specified and as directed.
S&F in repair Chromium plated soap dish including fixing arrangement complete all as specified and directed . (Make: Parryware /Hindware/Cera)
S&F in repairs Overhead Shower rose ø125mm (Brass Chrome Plated) complete all as specified and as directed.
S&F in repairs 15 mm bore Pillar taps, cast copper alloy, with capstan heads, chromium plated, screwed down high pressure, screwed for iron pipe. (Make: /Parryware/Hindware/ Cera) including taking existing one complete as directed by Engr-in-charge.
S&F in repair Brass Chromium plated wall mixer for mixing hot & cold water screwed down for 15mm bore iron pipe complete all as specified and directed .
S&F in repair PVC Dual flush ceramic colour cistern , low level, 10 litres capacity, star white with inlet float ball valve, PVC flush pipe and handle, making proper fixing and hanging arrangements (Make: /Parryware/Hindware/ Cera) all as specified and as directed.
S&F in repairs of chromium plated tubular towel rail 20 mm dia brass D type 60 cm long between flanges complete all as specified and as directed.
S & F in repair Toilet paper holder box type of vitreous china fixed to walls with chromium plated (CP) brass screws and complete all as specified.
S&F in repairs of Bib tap standard of PTMT any colour high pressure screwed for iron pipe and fixed.(Minimum weight15mm-90gms) and directed by Engineer in Charge.
S&F 150 mm dia round/square grating of CP with or without hole including Jointed to PVC pipe complete all as specified.
S&F in repairs 40 mm Waste coupling fittings, brass, chromium plated for glazed ware sinks, basins, etc. with long screwed shanks and fly-nuts, flange end bedded in red lead cement and other end fixed one complete all as manufactures and all as specified
S&F 32 mm Waste Coupling fittings, brass, chromium plated for glazed ware sinks, basins, etc. with long screwed shanks and fly-nuts, flange end bedded in red lead cement and other end fixed including taking down existing one complete all as manufactures and all as specified and directed by Engineer- In - charge
S&F PVC connections 15mm size with PTMT nuts of length 600 mm including taking down existing one complete all as manufactures and all as specified and directed by Engineer- In - charge.
S&F Vitreous china wash down water closet pan (pedestal pattern), white (exluding fixing bolts,flushing cistren and flushpipe) and including seat cover for pedestal pattern complete fixed in repair, all as specified and as directed.
S&F Rotational moulded polythene water storage tank of 500 Ltrs capacity (three layer white colour) cylinderical vertical with closed top including 3 Nos GI check nuts and tank nipple of 25mm bore for inlet and outlet, 25mm bore ball valves high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball hoisted and fixed in position all as specified in SSR part -I including taking down of old unserviceable tank complete all as specified and directed.
S&F PVC connections 15mm size with PTMT nuts of length 450 mm including taking down existing one complete all as manufactures and all as specified and directed by Engineer- In - charge
S&F in repairs 40mm bore unplasticised PVC pipe of pressure rating 10 kgf/Sqcm fixed complete to walls, ceiling or laid in floors complete all as specified and directed.
S & F in repair PVC waste pipe 32 to 40 mm dia and length n exc 1m for WHB/Sink/Urinal up to floor trap and fixed complete all as specified
Taking down steel tubing 20mm bore and connections including cleaning and refixing of old GI tubing 20mm bore including connections in new or old position (wall, ceiling & floor)complete all as specified and as directed. Note :- The unit rate quoted is deemed to include for all fittings required for re-connection.
Taking down steel tubing 15mm bore and connections including cleaning and refixing of old GI tubing 15mm bore including connections in new or old position (wall, ceiling & floor). Note :- The unit rate is included for all to be fittings for re-connection.
Cleaning of air/dust blokages in the internal water supply lines concealed or fixed on the wall or floor surfaces by dismantling the fitting such as taps, valves, unions etc to facilitate/stimulate clearance of blockages/airlocks and re fixing the dismantled items after clearance of blockage/airlocks including fiiitngs etc complete all as specified and as directed
S&F PVC (SWR) pipes single socketed in any length with rubber ring joints of 110 mm bore fixed to wall/floor including taking down existing one complete all as specified and as directed by Engineer-in-Charge
S&F PVC bends 110mm bore including taking down existing one complete all as specified and as directed by Engineer-in-Charge
S&F PVC (SWR) 110mm junction (single T) equal or unequal provided with access door including taking down existing one complete all as specified and as directed.
S&F PVC (SWR) 110mm junction vent cowl all as specifed including taking down existing one complete all as specified and as directed by Engineer-in-Charge
S&F PVC (SWR) pipes single socket in any length with rubber ring joints of 75 mm bore fixed to wall including taking down existing one complete all as specified and as directed by Engineer-in-Charge
S&F PVC (SWR) branch piece (single Y) 75mm equal or unequal provided with access door including taking down existing one complete all as specified and as directed by Engineer-in-Charge
S&F PVC bends 75mm bore including taking down existing one complete all as specified and as directed by Engineer-in-Charge
S&F PVC (SWR) 75mm junction (single T) equal or unequal provided with access door including taking down existing one complete all as specified and as directed.
S&F in repairs PVC (SWR) floor trap 75mm dia of outlet pipe, plain with grating including jointing with solvent cement complete all as specified and as directed.
S&F in repairs PVC (SWR) multi floor trap 75mm dia of outlet pipe, plain with grating including jointing with solvent cement complete all as specified and as directed.
S&F PVC (SWR) 75 mm junction vent cowl all as specifed including taking down existing one complete all as specified and as directed by Engineer-in-Charge
S&F in repairs Stack clamps made out of 50 mm x 5 mm flat iron and 110 mm dia round iron stays, including bolts and nuts and securing ends of stays to wall or roof for 110 mm bore complete all as specified and directed.
S&F in repairs Stack clamps made out of 50 mm x 5 mm flat iron and 75 mm dia round iron stays, including bolts and nuts and securing ends of stays to wall or roof for 75 mm bore complete all as specified and directed.
Supplying and laying of 20mm outer dia CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors complete all as specified and taking out steel/plastic/cpvc water tubing and connections including cleaning for refixing 15 mm/20mm dia .
Supplying and fixing in repairs of 20mm outer dia Female Brass Threaded Adaptor (FTA/ FBTA CPVC complete all as specified.
Supplying and fixing in repairs 20mm outer dia CPVC brass elbow and all as specified.
Supply and fixing 15mm bore galvanized steel water tubing, medium grade with all fittings and fixed complete to walls and ceiling or laid in floors including taking down up or down 15mm bore steel tubing galvanized and connection including cleaning for re-fixing or removal from site complete all as specified.
Supply and fixing 20 mm bore galvanized steel water tubing, medium grade with all fittings and fixed complete to walls and ceiling or laid in floors including taking down up or down 20mm bore steel tubing galvanized and connection including cleaning for re-fixing or removal from site complete all as specified.
M&L Petty repairs to leaking water in bib taps, pillar cock, stop cock, angle valve, concealed stop valve, bottle trap of any description by changing the PVC washers/ Sheet washers,spindle brass,jumper brass or any other minor accessories items included etc (incl taking down and refixing) complete all as specified and directed
Petty repair to wall mixer,basin mixer,sink mixer etc including replacement of spindle brass, Jumper brass, rubber washer, head incl taking down and refixing etc all as directed
Taking down & re fixing high or low level flushing cistren 10 ltrs capacity & connections to pipes & fixing of chain & pull or lever after cleaning inside of all dirt, scale formation, replacement of rubber washers, syphon set, float valve,stopping of leakage etc complete all as specified and as directed
Petty repair to internal/external water inlet water pipe line coming from over head tank to the quarter including socket,elbow,nipple ,with repair to water blockage , pipe line leakage, cleaning internally , removing the blockage including concealed water tubing etc of any height using scaffolding and and making the water supply good complete all as specified and directed.
Dismantling wrought iron or mild steel work of any description all as specified and directed.
Supply and fixing MS tubes/Square bars/Angle square bar iron using various sections such as poles, rafters, purlins ladders and cleats as directed by Engineer-in-Charge and all specified and directed.
M&L for Rolled sections as in framing for cladding, glazing and the like fixed with angle cleats and connecting plates, etc confirming to Fe 410 -W (Gde- E-250) quality -A and complete all as specified and as directed.
S&F Pre painted Coloured Galvalume roofing system sheet 0.50 mm thick having Zinc aluminum alloy coating AZ150 shall be as per IS:277/ASTM 1379 150 gsm/ sqm double ribbed trapezoidal profile steel sheet any colour having tensile strength of 550 Mpa as in Roof covering /cladding to wall fixed with self tapping screws and including dismantling of any type of sheets in roof coverings complete all as specified & directed complete all as directed.
S&F Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/ cladding to wall, fixed with self tapping screws dismantling of any type of sheets in roof coverings complete all as specified & directed complete all as directed.
Note for pre-painted coloured Galvalume roofing :-
(i) The manufacturer's test certificate and individual test certificate for the chemical and mechanical properties of sheet must be submitted for approval by the concerned authority prior to installation.
(ii) The contractor shall ensured that no leakages take place from the roof. The roofing shall be Coloured Galvalume roofing system (olive green colour or as approved by GE) with feed material manufactured from 0.50 mm Total coated thickness (TCT), minimum 550 MPa yield strength and shall conform to the physical specifications of IS: 2062 of 2011, coated with hot dip metallic Aluminium / Zinc alloy coating AZ150 as 150 gm/sq.mt total on both sides.
(iii) The painting shall be coloured baked enamel polyester with silicon coating of film thickness 25 microns nominal on the exposed face/exterior side and on the reverse side ( interior face) shall be white with 15 microns film thickness, over a coat of 5 micron nominal thickness Primer.
M&L for second glass hard-wood in scandlings, clean sawn and included taking down existing complete all as specified and as directed
M & L for 100 mm thick PCC 1:2:4 type B-2 (using 20 mm graded crushed stone agg) as in PCC in Hard standing etc. with , spike rolling ,or making impression of expanded metal, while the concrete is green complete all as specified and Demolition of Concrete (un reinforced) of any description and in any position not otherwise specifically provided.
M&L Virified Ceramic tiles 10 mm thick, light shade (square/ rectangular) polished, area of each tiles not exceeding 0.36 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match, laid over and including screed bed or bedding layer, 15 mm thick in Cement Mortar 1:6 complete including dismantling of existing tile and disposal of to outside MD land all as specified and as directed.
M&L Virified Ceramic tiles 10 mm thick, light shade (square/ rectangular) polished, area of each tiles not exceeding 0.36 sqm, in vertcal surfaces such as skirting/ dedo etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match, laid over and including screed bed or bedding layer ,15 mm thick in Cement Mortar 1:6 complete including dismantling of existing tile and disposal of to outside MD land all as specified and as directed.
M&L in repairs pre-cast PCC 1:3:6 type C1 (20 mm graded agg) cement concrete block masonry with solid blocks exc. 10cm in width and set in cement mortar 1:6 including demolition of brick work / stone masonry/PCC block built in cement mortar of any description as specified and directed.
M&L Rendering 15 mm thick in two coats on brick or stone or concrete surfaces,first coat 10mm thick in cement mortar 1:4 and 2nd coat 5mm thick in cement mortar 1:4 mixed with water proofing compound as per manufacturer instructions finished even and smooth without using extra cement complete all as specified and directed. Note: Supply only water proofing compound shall be measured and paid seperately.
M&L Checking of floor, plinth, plaster etc requiring masonry work and carrying out minor repairs such as edges, patches etc, including petty repairs material like sand, cement & aggregate to make it functional complete all as specified and as directed by Engineer-in-Charge. The rates for plastering / plinth include for: (a) Preparing the surfaces. (b) Thickness of plaster/plinth key in joints, etc as per existing. (c) Anises, chamfers of any width, internal rounded angles upto 80mm in width or girth external rounded angles upto 80mm in width or girth. (d) All materials, labour and equipment & supply of integral waterproofing compound, (e) Scoring surface of plastering for key, where the surface is not required to be finished fair. (f) Plastering in patches (in repairs), exc 3 sq.m each patch, for preparing old walls to receive plastering'. Nothing extra shall be admissible for matching with existing work etc. (g) Any individual patch (other than nail hole, plug hole, etc.) are included for provided existing surface finish .
Taking down cement plaster on brick or stone walls, or concrete or ceilings etc., including raking out joints, hacking for key, scrubbing down with water, etc., including removal of rubbish off the premises and leaving the work clear of any plastering and material and labour for Rendering 15 mm thick in two layers on brick or stone or concrete surfaces,first coat 10mm thick in cement mortar 1:4 and 2nd coat 5mm thick in cement mortar 1:4 mixed with water proofing compound as per manufacturer instructions finished even and smooth without using extra cement complete all as specified and directed. Note :- (a) Water proofing compound shall be measured and paid seperately. (b) The unit rate quoted is deemed to include for removal of accumulated earth of any width and depth upto 15 cm cleaning/cutting the grass with hand operated petrol/kerosene driven grass cutting machine and removing the grass waste around 3 m from plinth protection to outside MD land.
Supply only water proofing compound
M&L preparation of newly plastered surfaces wall/ ceiling and applying three coats of white washing on ceiling/ walls surfaces complete all as specified and directed.
M&L applying two coat of cement based paint over a coat of primer, including preparation of newly plastered wall surfaces of any description, complete all as specified and as directed.
M&L for Preparation of old decorated plastered or unplastered surface of wall, brooming down or steel wire brushing down smoke soot, moulds mass, efflorescent , trading, oil, greasy spots and applying one coat oil bound distemper complete all as specified and as directed.
M&L for Preparation of old plastered surfaces of wall by using pressure washer, removal all dirt and dust and applying one coat of exterior emulsion weater proof paint complete all as specified and as directed. Note:-(i) Cost of scaffolding required deemed to be included in the quoted rate of item and nothing extra shall be admissible on this account.
M&L for Preparation of old decorated surfaces of walls by using pressure washer, remove all dirt & dust ,applying one coat of wall care putty and then and applying two coats of premium oil bound distemper over one coat of primer as per manufauture instruction of required shade complete all as specified and directed by Engineer - in - Charge. Note:-(i) Cost of scaffolding required deemed to be included in the quoted rate of item and nothing extra shall be admissible on this account.
M&L for Preparation of old painted wooden surface of any description and applying one coats of synthetic enamel paint using mechanical means, not otherwise described over 10 cm width or girth, complete all as specified and directed.
M&L for Preparation of old painted surfaces of steel and applying one coat of synthetic enamel paint using mechanical means over 10 cm width or girth, not other wise described complete all as specified and as directed.
Material and labour for Preparation of old decorated plastered or unplastered surface of wall, brooming down or steel wire brushing down smoke soot, moulds mass, efflorescent , trading, oil, greasy spots and applying one coat of cement based paint complete all as specified and as directed.
Material and labour for Preparation of old decorated plastered or unplastered surface of wall, chajja, balcony, facia etc., brooming down or steel wire brushing down smoke soot, moulds mass, efflorescent, trading, oil, greasy spots and applying one coat of white wash complete all as specified and directed.
Material and labour for Preparation of old plastered or unplastered surface of ceiling brooming down or steel wire brushing down smoke soot, moulds mass, efflorescent , trading, oil, greasy spots and applying one coat of white wash complete all as specified and directed.
M&L Plain cement concrete (1:3:6) type C1 (20 mm graded stone aggregate), 75mm thick, as in plinth courses, top surface of concrete finished even and smooth with out using extra cement, including expansion joint 10mm thick filled with mastic filling comprising of 01 part of heated blown beitumen and 3 parts of sand including demolition existing cement concrete including disposal of demolition material upto MD land complete all as specified and directed by Engineer- In - charge
M&L Preparation of new steel surfaces of any description exc 10 cm width or girth and applying Two coats of synthetic enamel paint over a coat of redoxide primer on new steel surfaces complete all as specified and as directed.
M&L Granite 18 to 20mm thick (table rubbed and polished) in steps,Jamps, Pillars, Windows, cills, platforms and like CM (1:4) including pointing in white cement (1:2) using marble dust with admixture of pigments to match with marble shade of Granite over screed bed or bedding layer of mortar 15mm thick for laying floor finishes in cement mortar (1:4) all as specified and as directed. Note : (a) The Unit rate quoted is included for Demolition of Stone Slabs and tiles of any description or thickness in floors, aprons etc laid bedded and pointed in any mortar (b) The manufacturer's test certificate and individual test certificate of Tiles must be submitted for approval by the concerned authority prior to installation.
M&L Repair to ends of chajjas/ parapets by removing old concrete, loose material & cleaning of the reinforcement and finishing the surface with rich cement mortar 1:3 , finished fair & even and making good with existing finishes complete all as specified and as directed. Note: Rate quoted by the tenderer shall be deemed to inclusive of double steel scaffolding.
Removing plant/Uprooting of vegetation growth including roots on wall/roof/parapet near pipes etc and applying acid treatment after removing roots for preventing regrowth and making good disturbed surfaces/area in superficial area exc 150sq.cm but n.exc 400 sq.cm and averaging depth not exceeding 10 cm by using PCC 1:2:4 type B-0 (using 12.5 mm graded stone aggregate) or 10mm thick plastering in cement mortar 1:3 as required and finishing the surfaces to match with the existing surface complete all as specified and directed.
Note for item No 196 :- (a) Rate quoted by the tenderer shall be deemed to inclusive of double steel scaffolding. (b) Contractor shall provided safety gears to his workers at his own cost and safety precaution to avoid accidents.
Dismantling the existing unservicible gully trap including chamber and material and labour for provision of new salt glazed stoneware gully trap, square or round mouth type "P" of size 180X150mm, including setting and jointing in cement mortar 1:1 in chamber with plain cement concrete base in PCC 1:2:4 type B1, brick work in cement mortar 1:4, rendering in cement mortar 1:4, all around finished even and fair using extra cement, Precast cover slab in RCC 1:2:4 type B1 using 20mm graded stone aggregates, reinforcement with 6mm dia in both ways etc, including provision of handle etc complete all as specified and as directed.
Petty repair to renewing/matching glazed or ceramic coloured tiles in floors/walls in patches area not exceeding n exc 2.00 Sqm including dismantling, removing and cleaning old tiles preparing beds and laying screeb bed in CM 1:4 setting, jointing and pointing new or old tiles and joints filling and apply white cement and complete all as specified and directed
Petty repairs to Renewing glazed or ceramic tiles in patches area not exceeding 5 Sqm including removing and cleaning old tiles preparing beds and laying or setting, jointing and pointing new or old tiles and joints filling and apply white cement complete all as specified and directed
Petty repair to plain cement concrete type B1 (using 20mm graded aggregate) 1:2:4 in floor,column , beam,window cill,door cill,balcony rep etc area n. exc 2 sqm of any height of bldg using scaffolding including matching to existing surfaces complete all as specified
Supply and fixing in repairs 8 feet 4 pipes pulley operated cloths drying system consisting of aluminium pipe of outer dia 22mm, inner dia 19.80mm, made up of detrin with rope guide mounted on channel pair of length 24 feet (distance between two pipes is adjustable) locking system to hide rope knot, channel to be mounted or fixed with self taping screws provided in kit. Rope will be HDPE double core of 4mm dia fixing to ceiling as specified and directed by Engr-in-Charge and minimum weight of one pipe shall not be less than 0.20kg/, minimum weight of rope shall not be less than 7700Gms/unit .
Grinding of existing mozaic/kota stone/tiles in wall/flooring including mirror polishing, cleaning and joints filling and apply white cement complete all as specified and directed complete all as drected
Repair, maintenance and making the continuity of supply after rectifying the defects of the electrical items such as light point, fan point, call bell point, socket point 5A/15A, switches, sockets, regulator, lamp holder, brackets, bell, buzzer, push button, batten, ceiling rose, pendent, any type of MCB's, DB's any type of light fixtures, any type of lamp, ceiling fan, exhuast fan, geyser, capacitor, replacement of fuse wires and all elcectrical accessories in day to day/door to door maintenance including reconnection with S&F small pieces of elctrical cable of size upto 10 sqmm single core and length not exceeding 0.50m complete all as specified and as directed. Note : Any major items required to be repaired/replaced will be measured and paid under relevant items as supply only.Cost of labour for replacement will be deemed to include in the unit quoted rate.
Note for item No 204 :- (a) The above job shall be carried out by a trained electrician having ITI in electrical, documentary proof of the education of tradesman shall be produced to Engr-in-Charge before commencement of work.
(c) Record of complaints/complaint slip showing qtr No, bldgs No, nature of job supported with users signature shall be prepared as per format directed by Engr-in-charge & will be deposited to concerned JE E/M within 24 hrs.
(d) All sort of petty T&P items such as PVC insulation tape, ladder, galvanised screws, nuts, bolts, washers etc. required to accomplish the job shall be provided by the contractor with out any extra cost to dept.
(j) In case of any delay in attending the complaint more than 12 hrs after handing over routine/urgent complaints, the contractor shall be liable to pay the penalty as described in penalty clause given here as under.
(k) The penalty shall be applicable to the contractor if the delay is noticed by the Engr-in-Cahrge more than twelve hrs after handing over works of urgent/ routine nature to the contractor. The Engr-in-Charge shall handover the slip containing specification of work to the contractor by lodging the time and signature of contractor be obtained on slip. The contractor shall attend the complaint immediately and shall report to Engr-in-Charge with in 12 hrs. The contractor will keep his tradesmen in stand by for attending any routine / urgent works from the executive. If the nature of job is such that the work cannot be completed within period of 12hrs then the facts shall be brought to the notice of the GE/Engr-in-Charge and the period for the working to the complaint shall be decided by the GE/EIC. If the delay is more then twelve hrs period and the GE is not satisfied with the reason for delay then penalty at the rate of Rs 50/- per job shall be deducted from the dues of the contractor. Please note that this penalty is exclusively other then the condition 56 of IAFW - 2249 and shall be treated as interim condition of the contract and shall be enforce above as and when delay in individual job is noticed and no claim whatsoever on this account shall be entertained by the Deptt.
(l) The decision of the Accepting Officer in this regard shall be final and binding.
Supply only switch piano flush type 5 Amps 240 volts single pole one way. Make : Anchor, Havells, L&T
Supply only switch piano flush type 5 Amps 240 volts single pole two way. Make : Anchor, Havells, L&T
All as per item No 211 here-in-before but 15 Amp Make : Anchor, Havells, L&T
Supply only shuttered socket outlet 3 pin 5 amps, flush type Make : Anchor, Havells, L&T
Supply only shuttered socket outlet 2 in 1, 5 pin, 5 and15 amps Make : Anchor, Havells, L&T
Supply only switch socket combination out let 3 pin 5 amps, flush type. Make : Anchor, Havells, L&T
Supply only switch socket combination out let 5 in 1, 5 pin 5 and 15 amps, flush type.Make : Anchor, Havells, L&T
Supply only for Ceiling rose 3 plates flush type 6 Amps,250 volts AC ISI marked,
Supply only electronic fan regulator 230 volts, step type socket type, hum free 100/240 watt. Make : Havells / Anchor/ crabtree
Supply only PVC gang box 1 way 05 amp . Make. Cona/L&T/Anchor
Supply only single pole MCB 6 to 32 Amps, 240 v, 50 Hz AC suitable for ‘C’ curve, 10 KA breaking capacity conforming to IS 8828 of 1996 all as specified (Make/Model : Lexic MCB of MDS Legrand Cat No :408587 to 408595 / Indoasian/ Havells.
Supply only metal clad switch socket single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20A concealed in walls. Legrand/ Havells/ Indoasian
Supply only electric bell, AC 230 volt, single pole Ding Dong type complete all as specified and directed. Make : Anchor/ cona/ Plaza
Supply only 7 watt LED lamp complete all as specified and directed. Make : Philips/ Bajaj/ Crompton
Supply only bakelite sheet not less than 3 mm thick of suitable size complete all as specified and as directed.
Supply only TPN, MCB 20 to 32 amp, 240 v, 50 Hz AC suitable for ‘C’ curve, 10 KA breaking capacity complete conforming to IS 8828 of 1996 all as specified (Make/Model : Indoasian/Schneider/ L&T/Havells.
Supply only electronic fan regulator modular typre 230 volts, step type socket type, hum free 100/240 watt Make : Havells / Anchor/ Crabtree.
Supply only insulation tape 25 mm width 10m long
Supply only electronic LED driver 46/47W suitable for 2' x 2' ceiling light indoor fitting of make Philips/ crompton/ Bajaj as directed by Engineer-in-Charge.
Supply only 4' 20W/ 18W LED Retro bar tube rod suitable for existing fitting. Make : Philips, Bajaj, Havells,Crompton
Supply only 4 mfd condensor for exhaust fan complete all as specified and directed. Make : Epcos/ Asian/ Tyton
Supply only modular switch 1 way 6 amp.1 module. Make : Legrand (Model- Arteor), ABB (Cheiron)/ Anchor (Penta)
Supply only modular Socket, 6A - 2/3 pin combined 2 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply only modular switch 1 way 16 amp.1 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply only modular Socket, 16A - 3/5 pin combined 2 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply only modular white cover plate with frame,3 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply only modular white cover plate with frame,4 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply only modular white cover plate with frame,6 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply only modular white cover plate with frame,08 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply only modular white cover plate with frame,12 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply only rigid, non-metalic, PVC conduit pipe, ISI marked, 25 mm bore, including bends, saddles, accessories complete all as specified and as directed. Make : Avon plast/ Supreme/ Diplast
Supply only switch socket combination outlet 3 in 1/ 3 pin 3 and 5 amps flush type with box
Supply only switch socket combination outlet 5 in 1/ 5 pin 5 and 15 amps flush type with box
Supply only SPN MCB 40 amp, 240 v, 50 Hz AC suitable for ‘C’ curve, 10 KA breaking capacity complete conforming to IS 8828 of 1996 all as specified (Make/Model : Indoasian/ Havells/ Legrand.
Supply only TPN, MCB 40 to 63 amp, 240 v, 50 Hz AC suitable for ‘C’ curve, 10 KA breaking capacity complete conforming to IS 8828 of 1996 all as specified (Make/Model : Indoasian/ Havells/ Legrand.
Supply and fixing building security/ LED street light fitting 35 Watt, 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal, management in multiple optics complete with IP 65/66 protection complete.
M&L for sub main wiring with PVC insulated unsheathed FRLS cable 1100 volts grade multi stranded copper conductor cable 2 runs of 6 sqmm drawn through in and incl suitable size surface PVC Conduit/ existing concealed conduit and all accessories fixed to wall/floors along with 6 sqmm surface PVC insulated unsheathed copper conductor multi stranded cable 1100V grade as earth continuity conductor and connected to common earth dolly including taking down existing sub main wiring of any size. Note: (a) 2 runs of 6 sqmm cable along with one run of 6 sqmm cable for earth conductor shall be measured as one length Make:- Havells/ Polycab/ Plaza.
S&F in replacement on distribution board MCCB four pole, 100 Amp ultimate breaking capacity 16 KA complete conforming to IEC -61439-1 complete all as specified. Make : Indoasian/ L&T/ Havells
Supply and fix LED lights fitting 1 x 20 W, 4' long, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete including taking down old/unsv fittings all as specified and directed by Engr-in-charge.
S&F in replacement factory made powder coated distribution board SP & N 4 way double door, including bus bar, Neutral bar, standard DIN rail, earth bar complete including taking down UNSV DB all as specified and conforming to IS: 8623 all as specified. Make/Model : Legrand/Indoasian/ Standard
S&F in replacement on distribution board MCCB four pole, 63 Amp ultimate breaking capacity 16 KA complete conforming to IEC -61439-1 complete all as specified. Make : Havells/ L&T/ Indoasian
Taking down aluminum/copper point wiring on & including hard wood battens, surface conduit and board/ blocks etc or through conduits for light, socket or power point, fan point complete (Taking down of fittings such as switches, sockets, bells, ceiling rose, holders , regulators, light fittings, MCB, lamps etc shall be measured and paid seperately) and making good the disturbed plaster surfaces of wall, floor, ceiling and painting 2 coat of white wash/distamber to meet the existing surface and removing materials and debris to reinstate the premise neat and clean complete all as specified and directed.
M&L in repairs for point wiring using approved colour coding as per IS for one light/bell/buzzer point controlled by one switch or one fan point controlled by one switch & fan regulator with PVC insulated, unsheathed FRLS multi stranded copper conductor 1.5 sqmm (nominal area) 1100 volt grade ISI 694 marked cable for phase & neutral drawn through surface PVC conduit/ existing concealed PVC Conduit, ISI marked with and including new MS/ cast iron sunken boxes duly painted with two coats of anticorrosive paint over a coat of red oxide primer on surface in touch with wall and synthetic enamel paint over a coat of red oxide on other side, covered with 3mm thick plastic laminated sheet for mounting switches, regulators, sockets etc including 1.5 sqmm (nominal area) copper conductor PVC insulated, unsheathed, multi stranded FRLS cable as earth wire and connected to earth dolly complete all as specified and as directed. Make of Conduit : Avon Plast/ Supreme/ Diplast Make of Wire : Plaza/ Polycab/ Havells Note: (a) Switches, sockets outlets, blanking plate, Light fittngs, fans, bells & regulators will be measured and paid for separetely).
One light point/fan/bell point controlled by one switch
All as per item No. 253 here in before but for one 3 pin socket out 5 amp on the same board
All as per item No. 253 here in before but for one switch socket outlet 3 pin 5 Amps on independent board
All as per Sl No 253 above but Wiring with 4 Sqmm copper multistranded unsheathed cable and 4 Sqmm copper cable for earth continuity conductor controlled by one 15A switch socket independently
M&L in repairs for point wiring using approved colour coding as per IS for one light/bell/buzzer point controlled by one switch or one fan point controlled by one switch & fan regulator with PVC insulated, unsheathed FRLS multi stranded copper conductor 1.5 sqmm (nominal area) 1100 volt grade cable for phase & neutral drawn PVC through Casing Capping with and including new MS/ cast iron sunken boxes duly painted with two coats of anticorrosive paint over a coat of red oxide primer on surface in touch with wall and synthetic enamel paint over a coat of red oxide on other side, covered with 3mm thick plastic laminated sheet for mounting switches, regulators, sockets etc including 1.5 sqmm (nominal area) copper conductor PVC insulated, unsheathed, multi stranded FRLS cable as earth wire and connected to earth dolly complete all as specified and as directed. Make of Casing Capping : Polycab/ Modi/ Presto Plast Make of Wire : Plaza/ Polycab/ Havells Note: (a) Switches, sockets outlets, blanking plate, Light fittngs, fans, bells & regulators will be measured and paid for separetely.
One light point/fan/bell point controlled by one switch
All as per item No. 258 here in before but for One 3 pin socket out 5 amp on the same board
All as per item No. 258 here in before but for one switch socket outlet 3 pin 5 Amps on independent board
All as per Sl No 258 above but Wiring with 4 Sqmm copper multistranded unsheathed cable and 4 Sqmm copper cable for earth continuity conductor controlled by one 15A switch socket independently
M&L for point wiring complete with 1.5 sqmm single core PVC insulated, unsheathed fire retacable 1100 volts grade, multi stranded with copper conductor drawn through and incl PVC Casing Capping with accessories in wall/roof/ceiling etc incl MS modular terminal boxes, concealed surface to walls covered with modular plates with cover etc and 1.5 sqmm PVC insulated, unsheathed copper conductor multistranded cable 1100V grade as earth continuity conductor & connecting to common earth dolly all as specified for Make of Casing Capping : Polycab/ Modi/ Presto Plast Make of Wire : Plaza/ Polycab/ Havells Note: (a) Switches, sockets outlets, blanking plate, Light fittngs, fans, bells & regulators will be measured and paid for separetely).
One light point/fan/bell point controlled by one switch
All as per item No. 262 here in before but for One 3 pin socket out 5 amp on the same board
All as per item No. 262 here in before but for one switch socket outlet 3 pin 5 Amps on independent board
All as per Sl No 262 above but Wiring with 4 Sqmm copper multistranded unsheathed cable and 4 Sqmm copper cable for earth continuity conductor controlled by one 15A switch socket independently
M&L in repairs for point wiring complete with 1.5 sqmm single core PVC insulated, unsheathed fire retacable 1100 volts grade, multi stranded with copper conductor drawn through and incl surface PVC Conduit/ existing concealed conduit with accessories in wall/roof/ceiling etc incl MS modular terminal boxes, concealed surface to walls covered with modular plates with cover etc and 1.5 sqmm PVC insulated, unsheathed copper conductor multistranded cable 1100V grade as earth continuity conductor & connecting to common earth dolly all as specified for Make of Cable : Plaza/ Polycab/ Havells Make of Conduit : Supreme/ Diplast/ Avon Plast Note: (a) Switches, sockets outlets, blanking plate, Light fittngs, fans, bells & regulators will be measured and paid for separetely).
One light point/fan/bell point controlled by one switch
All as per item No. 268 here in before but for One 3 pin socket out 5 amp on the same board
All as per item No. 268 here in before but for one switch socket outlet 3 pin 5 Amps on independent board
All as per Sl No 268 above but Wiring with 4 Sqmm copper multistranded unsheathed cable and 4 Sqmm copper cable for earth continuity conductor controlled by one 15A switch socket independently
Supply and Fix switch piano flush type 5 Amps 240 volts single pole one way. Make : Anchor, Havells, L&T
Supply and Fix switch piano flush type 15 Amps 240 volts single pole one way. Make : Anchor, Havells, L&T
Supply and Fix shuttered socket outlet 3 pin 5 amps, flush type Make : Anchor, Havells, L&T
Supply and Fix shuttered socket outlet 2 in 1, 3 pin, 5 and15 amps Make : Anchor, Havells, L&T
Supply and Fix modular switch 1 way 6 amp.1 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply and Fix modular Socket, 6A - 2/3 pin combined 2 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply and Fix modular switch 1 way 16 amp.1 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
Supply and Fix modular Socket, 16A - 2/3 pin combined 2 module. Make : Legrand (Model- Arteor), ABB (Cheiron), Anchor (Penta)
S&F Surface & wall mounted LED fitting including 5 watt LED tube rod complete with all accessories internally, pre-wired, connecting up with twin core twisted flexiable copper conductor cable of suitable size including taking down old light fitting. Make : Bajaj Cat No 112405BCLSB 05 WH or equivalent of Philips /Havells.
Supply and fix LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete including taking down old/unsv fittings all as specified and directed by Engr-in-charge.
S&F in replacement factory made powder coated distribution board TPN, 4 way double door including bus bar, Neutral bar, standard DIN rail, earth bar complete including taking down UNSV DB all as specified and conforming to IS: 8623 all as specified. Make/Model : Indoasian/ Havells/ Legrand.
M&L for sub main wiring with PVC insulated unsheathed FRLS 1100 volts grade multi stranded copper conductor cable 4 runs of 6 sqmm drawn through in and incl suitable size surface PVC Conduit/ existing concealed conduit and all accessories fixed to wall/floors along with 4 sqmm PVC insulated unsheathed copper conductor multi stranded cable 1100V grade as earth continuity conductor and connected to common earth dolly including taking down existing sub main wiring of any size. Note: (a) 4 runs of 6 sqmm cable along with two run of 6 sqmm cable for earth conductor shall be measured as one length including taking down UNSV old wiring. Make:- Havells/ Polycab/ Plaza/Indoasian
M&L for Sub main wiring with PVC insulated unsheathed FRLS cable 1100 volts grade multi stranded copper conductor cable 2 runs of 4 sqmm drawn through in and incl suitable size surface PVC Conduit/ existing concealed conduit and all accessories fixed to wall/floors along with 4 sqmm PVC insulated unsheathed copper conductor multi stranded cable 1100V grade as earth continuity conductor and connected to common earth dolly including taking down existing sub main wiring of any size. Note: (a) 2 runs of 4 sqmm cable along with one run of 4 sqmm cable for earth conductor shall be measured as one length. Make:- Havells/ Polycab/ Plaza.
Supply and fixing square recessed/surface mounted LED slim down Light fitting 35/36W,600mm X 600mm complete with all accessories and including connecting up with 3 core 0.5sqmm copper wire between ceiling rose and fitting terminal complete including taking down old light fittings all as specified and as directed Make : Crompton/Havells/ Philips/Bajaj/Wipro.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5M in depth for laying cable/pole foundation/stay assembly and getting out in soft/loose soil.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm all as specified.
Removal of excavated soil to a distance not exceeding 50M and depositing at a level not exceeding 1.5 meter above starting point all as specified.
M &L for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983 and as directed. Note :- Excavated approved soil shall be ribbed by using sieve to separate composite particles etc as per IS and refiiling in trenchesas per SSR part-I. (ii) For the purpose of measurement punned thickness only will be considered for paymet.
M&L for well burnt as class ‘B’ bricks as mechanical protection to under ground cables laying with length of the bricks equal to the width of the trench complete all as speified and directed.
Material and labour for cutting of bituminious road/ hard standing/PCC path/wall up to a size not exceeding 20cm width and not exceeding 60cm in depth for laying of protection pipe for cable including making good the disturbed road/hard standing by providing PCC (1:2:4) type B1, 40 mm grade crushed stone aggregate upto existing surface level or removing the any type of tiles carefully and refixing properly as per existing surface complete all as specified and as directed.
S&F in replacement of GI tubing light grade of size 40 mm dia fixed on walls / laid in trenches as protection pipe for under ground cable including provisioning of specials and clamps etc complete all as speified and directed.
M&L for XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and overall sheathed of size 16 Sqmm 4 core and laying in trenches/cable ducts, fixed to wall/pole complete all as specified and directed.
M&L for XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and overall sheathed of size 16 Sqmm 2 core and laying in trenches/cable ducts, fixed to wall/pole complete all as specified and directed.
M&L for XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and overall sheathed of size 10 Sqmm 2 core and laying in trenches/cable ducts, fixed to wall/pole complete all as specified and directed.
M&L Earthing with Galvanised Earth Plate Electrode 600x600x 6mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, connected with Galvanised Earth Strip of size 25x6mm (upto 7.5m length) by means of Bolts, Nuts, Check Nuts and Washers of GI or Steel and connected Earthing Testing Point/Bus-bar including GI 40mm bore (dia) light grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt, Magneisum Sulphate (1 : 1 : 0.5) in alternate layers of not exc 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50 mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, Funnel with GI Watering Pipe 20mm bore (dia) medium grade including necessary Excavation in any type of soil, Returning, Filling in and Removal of surplus Spoil disposal to out side MD land and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including taking down old unserviceable one, complete all as per specified and as directed.
(a) All Joints should be joined by Exothermic Welding or Brazing. (b) After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge, User and proper record shall be maintained duly signed by all concerned. (c) Earth resistance tester shall be provided by the contractor. It should be caliberated from authorised company/ lab. (d) After testing if desired earth resistance of less than 5 Ohm is not obtained, the earthing will be redone at no extra cost to Govt till desired result is obtained.
M&L in repairs Galvanised Earth strip of size 25 x 6 mm fixed on proper post insulator at the instrument end complete all as per specified and as directed.
Supply only modular fan regulator 2 module 230 volts complete all as per specified and as directed.
Supply only 2.5 mfd condenser for fan all as per specified and as directed. Make : Epcos/Asian/Tyton
AURA ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .