Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.2 LAccepted-AOC 1ST FLOOR GURJEET MARKET DHANGU ROAD | ₹37.2 L Quoted ₹39.0 L | L1 | Accepted-AOC Lowest |
| 2 | L2₹39.9 LRejected-AOC BYE PASS DALHOUSIE ROAD PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹39.9 L | L2 | Rejected-AOC 2nd lowest |
| 3 | L3₹42.7 LRejected-AOC VILL BUNGDAL DADHANI P O BADHANI DISTT PATHANKOT PIN 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹42.7 L | L3 | Rejected-AOC 3rd lowest |
| 4 | L4₹45.0 LRejected-AOC | ₹45.0 L | L4 | Rejected-AOC 4th lowest |
| 5 | L5₹47.5 LRejected-AOC | ₹47.5 L | L5 | Rejected-AOC 5th lowest |
| Sl No | Description | Qty | Unit | Vijay Kumar Contractor and Engineers L1 | M/S V K TRADERS L5 | KULBHUSHAN AGGARWAL L6 | M/S CANTILEVER ENGINEERS L3 | M/S GULATI ENGINEERING WORKS L2 | RD Engineers L4 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Disconnecting and taking out LT cable up to 25 Sqmm 2/3.5/4 core from trenches/cable duct/through wall/pole carefully complete all as specified and directed.
Note: Earth work, sand, bricks cover will be measured and paid separately. | 3,020 | RM | 5 ₹15,100 | 30 ₹90,600 | 10 ₹30,200 | 5 ₹15,100 | 8 ₹24,160 | 5 ₹15,100 |
| 2.00 | All as per item No 1 but for LT cable 35 to 70 Sqmm 3.5 core. | 890 | RM | 5 ₹4,450 | 30 ₹26,700 | 10 ₹8,900 | 10 ₹8,900 | 11 ₹9,790 | 5 ₹4,450 |
| 3.00 | All as per item No 1 but for LT cable 95 to 240 Sqmm 3.5 core. | 100 | RM | 5 ₹500 | 30 ₹3,000 | 10 ₹1,000 | 20 ₹2,000 | 12 ₹1,200 | 5 ₹500 |
| 4.00 | All as per item No 1 but for LT cable 300 to 400 Sqmm 3.5 core. | 45 | RM | 5 ₹225 | 30 ₹1,350 | 10 ₹450 | 25 ₹1,125 | 18 ₹810 | 5 ₹225 |
| 5.00 | Disconnecting, dismantling aluminium conductor of any description from LT/HT overhead lines after unbinding from insulators and removal and deposited to MES store yard or taking over credit to contractor complete all as specified and as directed. | 3 | Qtl | 100 ₹300 | 500 ₹1,500 | 500 ₹1,500 | 500 ₹1,500 | 200 ₹600 | 500 ₹1,500 |
| 6.00 | Dismantling GI earth wire from LT/HT OH line after unbinding from pole for re-use or for shifting to MES store for taking credit to contractor complete all as specified and as directed. | 0.4 | Qtl | 100 ₹40 | 500 ₹200 | 500 ₹200 | 500 ₹200 | 200 ₹80 | 500 ₹200 |
| 7.00 | Disconnecting, dismantling and taking out old steel tubular/PCC pole any size/ length, making good all disturbed surface to match with existing and removal to a distance exc 100m but not exc 250m complete all as specified and as directed. | 23 | Each | 100 ₹2,300 | 500 ₹11,500 | 500 ₹11,500 | 500 ₹11,500 | 200 ₹4,600 | 20 ₹460 |
| 8.00 | Disconnecting electrically, dismantling from foundation with due care, setting aside LT feader pillar box any type any size with all accessories complete all as specified and as directed. | 9 | Each Job | 100 ₹900 | 500 ₹4,500 | 1,000 ₹9,000 | 750 ₹6,750 | 450 ₹4,050 | 400 ₹3,600 |
| 9.00 | Disconnecting, dismentling and taking down carefully GI strip of any size up to 32x6mm, seggregating unserviceable or serviceable parts incl removing from site or setting aside for reuse complete all as specified and as directed. . | 90 | RM | 5 ₹450 | 10 ₹900 | 25 ₹2,250 | 10 ₹900 | 22 ₹1,980 | 10 ₹900 |
| 10.00 | Dismantling insulators of any type, any size from LT overhead lines, setting aside or removal from site complete all as specified and as directed. | 146 | Each | 1 ₹146 | 10 ₹1,460 | 5 ₹730 | 5 ₹730 | 222 ₹32,412 | 10 ₹1,460 |
Updated dates
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
11 Mar 2026, 6:00 pmClosed
Garrison Engineer (N) Mamun
Garrison Engineer (N) Mamun PIN-145001
REPAIR/ MAINT OF LT CABLES, OH LINES, FOR D-III, DIA, D-IV AND MAP BHASKAR ZONE AND MAINT OF E/M INSTALLATION UNDER AGE E/M-I OF GE (N) MAMUN
2026_MES_752272_1
GE(N)/M-89/2025-26
Open Tender
Civil Works
180 days
Garrison Engineer (N) Mamun
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
Garrison Engineer (N) Mamun
₹90,000
30 Mar 2026
11 Feb 2026
18 Mar 2026
11 Feb 2026
11 Mar 2026
25 Feb 2026
Disconnecting and taking out LT cable up to 25 Sqmm 2/3.5/4 core from trenches/cable duct/through wall/pole carefully complete all as specified and directed. Note: Earth work, sand, bricks cover will be measured and paid separately.
All as per item No 1 but for LT cable 35 to 70 Sqmm 3.5 core.
All as per item No 1 but for LT cable 95 to 240 Sqmm 3.5 core.
All as per item No 1 but for LT cable 300 to 400 Sqmm 3.5 core.
Disconnecting, dismantling aluminium conductor of any description from LT/HT overhead lines after unbinding from insulators and removal and deposited to MES store yard or taking over credit to contractor complete all as specified and as directed.
Dismantling GI earth wire from LT/HT OH line after unbinding from pole for re-use or for shifting to MES store for taking credit to contractor complete all as specified and as directed.
Disconnecting, dismantling and taking out old steel tubular/PCC pole any size/ length, making good all disturbed surface to match with existing and removal to a distance exc 100m but not exc 250m complete all as specified and as directed.
Disconnecting electrically, dismantling from foundation with due care, setting aside LT feader pillar box any type any size with all accessories complete all as specified and as directed.
Disconnecting, dismentling and taking down carefully GI strip of any size up to 32x6mm, seggregating unserviceable or serviceable parts incl removing from site or setting aside for reuse complete all as specified and as directed. .
Dismantling insulators of any type, any size from LT overhead lines, setting aside or removal from site complete all as specified and as directed.
Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth for laying of cables/taking out of cables, foundation of poles or stays, for re-routing of cables complete all as specified and directed.
All as per item No 11 but depth exc 1.5 mtr but not exc 3.00 mtr.
Returning filling, in including spreading , levelling, watering and well ramming in layers not exc 25 cm each complete all as specified and directed.
Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
Relaying of LT cable up to 25 Sqmm 2/3.5/4 core in same or other indicated location and testing on completion including making good all distributed wall surfaces/ flooring/tilling/road to match with existing specifications complete all as specified and directed.
All as per item No 15 but of LT cable 35 to 70 Sqmm 3.5 core
All as per item No 15 but of LT cable 95 to 240 Sqmm 3.5 core
All as per item No 15 but of LT cable 300 to 400 Sqmm 3.5 core
Supply, laying in trenches or fixing to wall/pole or passing through pipe XLPE insulated heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 10 Sqmm 4 core including making good all distributed wall surfaces/ flooring/tilling/road to match with existing specifications complete all as specified and directed.
All as per item No 19 but cable of size 16 Sqmm 4 core.
All as per item No 19 but cable of size 25 Sqmm 3.5 core.
All as per item No 19 but cable of size 35 Sqmm 3.5 core.
All as per item No 19 but cable of size 50 Sqmm 3.5 core.
All as per item No 19 but cable of size 16 Sqmm 2 core.
All as per item No 19 but cable of size 10 Sqmm 2 core.
M&L for Cable jointing kit for 1100 volt grade cable for straight through termination, heat shrinkable type with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 10 to 16 Sqmm 2/3.5/4 core complete all as specified and directed.
All as per srl item No 26 but of size 25-50 Sqmm 3.5 core.
All as per srl item No 26 but of size 70-150 Sqmm 3.5 core.
All as per srl item No 26 but of size 185-240 Sqmm 3.5 core.
All as per srl item No 26 but of size 300-400 Sqmm 3.5 core.
M&L for Cable jointing kit for 1100 volt grade cable for outdoor termination end joint heat shrinkable type complete with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 16 to 35 Sqmm 3.5/4 core complete all as specified and directed.
All as per srl item No 31 but of size 50-95 Sqmm 3.5 core.
All as per srl item No 31 but of size 120-185 Sqmm 3.5 core.
All as per srl item No 31 but of size 225-300 Sqmm 3.5 core.
M&L for Galvanised Iron tubing light grade 50mm bore with fittings laid for protection of cable under road crossing/ fixed to walls or pole complete all as specified and as directed. Note: Clamps for fixing pipe, nuts, bolts washers etc shall be measured and paid for separately.
All as per srl item No 35 but of size 40mm bore.
All as per srl item No 35 but of size 80mm bore.
M&L for ACSR of LT OH line including securing with insulators using aluminium binding wire, jointing jumpers etc including all disconnected cables, jumpers with proper binding complete all as specified and as directed.
Unbinding ACSR conductor any size from insulators of LT/HT over head line for repairs, re-stretching of ACSR conductor to achieve proper sag, re-binding to the insulators using new aluminium/GI binding wire and making all existing cable connections as required complete all as specified and as directed.
M&L for Galvanised steel earth wire of service feeder or distributor span of street light poles including binding with insulators using GI binding wire, jointing jumpers etc making connections of incoming and out going cables complete all as specified and as directed.
Unbinding of GI earth wire of any size of LT/HT overhead lines, from insulators, re-stretching the GI earth wire to achieve proper sag, re-binding to the insulators using new aluminium/GI binding wire after repair complete all as specified and as directed.
Dismantling cross-arms of MS channel or angle iron etc from LT poles setting aside for re-use or removal from site complete all as specified and as directed.
Fixing only the cross arms items with supports/ angle iron frame etc includiing nuts, bolts, washers, welding, bending, hot or cold drilling holes for insulators bolts in any size or shape complete all as specified and as directed.
M&L for Cross arms, bracings, supports, clamps, back plates etc fabricated from structural steel sections including nuts, bolts, washers, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed, welding and inclusive of one primer coat, one under coat and one finishing coat with synthetic enamel paint complete all as specified and as directed.
Dismantling and taking out old/unserviceable stay assembly including Stay wire and insulator and removal from site complete all as specified and as directed.
M&L for stay assembly complete with MS stay plate of size 300x300x6mm thick, stay rod 20 mm dia, stay bow, nuts, bolts and check nuts of GI all as shown in Electrical Plate No 01 of SSR Part-I, 2009 complete all as specified and as directed. Note: Excavation, PCC, saty wire and loop type insulators will be measured and paid for separately
M&L for galvanized stay strand of 7/4mm size complete all as specified and directed.
M&L for loop type insulator large size with overall dimensions (90 x140) mm with clearance of hole 25.5 mm vitreous white brown or green complete all as specified and as directed.
Fixing only insulators any type/size in LT overhead lines complete all as specified and as directed.
M&L for shackle type insulator porcelain, vitreous, white, brown or green insulator 100 mm height,115 mm dia, 31x5 mm GI strap,14 mm dia bolts, washers and nuts complete all as specified and as directed.
M&L for Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade complete all as specified and as directed.
Supply, erection and installation of steel tubular swged pole complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9 metres long) duly painted with two coats of black bituminous paint through out, internally and externally up to planning depth, and painting remaining portion of pole with two coats of aluminium paint to the entire exposed surfaces over one coat of red oxide primer, making/painting three Nos circular strips each of 30 cm wide with one yellow and 02 Nos black colour strip with synthetic enamel paint, marking pole number with black paint complete all as specified and directed. Note : Excavation, earth work, PCC work shall be measured and paid for separately.
Supply, installation, commissioning with making connections LT feeder pillar box, outdoor type of size 0.90 x 0.70 x 0.60 Mtr size factory fabricated made out of MS sheet of thickness 3.15 mm front door openable with locking arrangement with 200 amps rated copper bus bar suitable for 3 phase 4 wire supply system duly drilled holes, making all cable connection with proper thimbles mounted on epoxy based post insulators, MCCB 200 Amps 4 pole 415 Volt, 35/36 KA -01 No, MCB 4 pole 80 Amps- 03 Nos, MCB DP 63 Amps 04 Nos, digital multimeter showing ampare, voltage etc., feader pillar mounted on MS angle iron legs of size 40x40x6mm, 1.5 mtr long, 1.0 mtr above ground level and 0.50 mtr duly painted with two coats of synthetic enamel paint over a coat of red oxide primer embedded in PCC 1:2:4 type B1 using 20mm graded crushed stone aggregates blocks of size 0.30x0.30x0.50 mtr- 04 Nos complete all as specified and directed.
Repair & maint of broken doors for LT panel and bus bars by welding, fixing of new hinges and other materials as required at site, making all connection as per existing complete all as specified and directed.
Removal of vegetation/bushes/small plants shrubs around the water/electric supply installations/ inside the valve pit etc and surface excavation not exceeding 15 cm depth leveling the ground, removing the excavated material to a distance exceeding 50 M complete all as specified and directed.
M&L for cutting, trimming of branches along the OH conductor of LT/ HT line within 2 mtr distance along both side of line and strictly all branches in one place complete all as specified and directed.
M&L for sand filling in trenches as cushion to under ground cables 8 cm thick before laying the cable and 15 cm thick when cables are laid and tested complete all as specified and directed. Note: Only punned thickness i.e 18cm shall be measured and paid.
M&L for Sub class ‘B’ bricks (fly ash bricks) old size laid dry, flat over the cable abutting each other, length of cable equal to width of brick complete all as specified and directed.
M&L for cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregrate for foundation, filling as mass concrete including necessary form work complete all as specified and directed.
M&L for cement concrete 1:3:6 type C-1 using 20 mm graded stone aggregrate for foundation of stay, filling as mass concrete including necessary form work complete all as specified and directed.
S&F in replacement MCCB 3 pole 415 volts fixed type 63 Amps with braking capacity 16 KA, thermal release adjustable from 80 to 100% & fixed magnetic release with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
S&F in replacement MCCB 3 pole 415 volts fixed type 100 Amps with braking capacity 16 KA, thermal release adjustable from 80 to 100% & fixed magnetic release with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
S&F in replacement MCCB 3 pole 415 volts fixed type 200 Amps with braking capacity 36 KA, thermal release adjustable from 80 to 100% & fixed magnetic release with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
S&F in replacement MCCB 4 pole 415 volts fixed type 100 Amps with braking capacity 16 KA, thermal release adjustable from 80 to 100% & fixed magnetic release with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
S&F in replacement MCCB 4 pole 415 volts fixed type 200 Amps with braking capacity 36 KA, thermal release adjustable from 80 to 100% & fixed magnetic release with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
S&F in replacement MCCB 4 pole 415 volts fixed type 400 Amps with braking capacity 36 KA, thermal release adjustable from 80 to 100% & fixed magnetic release from 5 to 10 In with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
S&F in replacement MCCB 4 pole 415 volts fixed type 630 Amps with braking capacity 36 KA, thermal release adjustable from 80 to 100% & fixed magnetic release from 5 to 10 In with Ics = 100% Icu , including spreaders after taking out old U/S one all as specified and directed .
Supply, install, testing and commissioning in replacement of LT busbar chamber box, indoor type, wall mounted, made out of CRCA sheet 2.00 mm thick, CPRI approved, weather proof, dust and vermin proof, IP -43, powder coated with 8 tank process, sleeve insulated aluminium bus bar 100 Amps, 3 Phase, 4 wire 415 volts including MCCB of 63 Amps, 4 pole, 16KA, 415 volts ,630 amps, 36KA, 50 Hz with fixed megnatic and thermal release, making connection from bus bar to meter in meter box with 10 Sqmm single core wire duly concealed with PVC pipe single side openable with locking arrangements for compartment including grouted on wall with necessary PCC 1:2:4 using 12.50mm graded crushed stone aggregate complete all as specified and directed.
All as per ser item No 68 but bar of cap of bus bar 150 Amps, MCCB 100 Amps, 16 KA.
S&F in replacement of heavy duty cable 1100 Volts 10 Sqmm 2 core flat PVC insulated aluminium stranded conductor served with inner sheathing of PVC tape and overall PVC sheathed for service connection complete all as specified and directed.
S&F in replacement of heavy duty cable 1100 Volts 6 Sqmm 2 core flat PVC insulated aluminium stranded conductor served with inner sheathing of PVC tape and overall PVC sheathed for service connection complete all as specified and directed.
M&L for boring of holes under road, pavement hard standing by mannually or trenchless technology using ultra sound technique for laying pipe/cables complete all as specified and directed.
M&L for painting existing cemented plateform of any size of LT panels/transformer with two coats of cement base paint, painting MS gate, XPM jalli/fencing all around the plateform with two coats of aluminium paint after preparation of surfaces complete all as specified and directed.
Cleaning grass/mud in and around the earth pits after taking out earth pit cover, pouring of salt solution i.e salt and water ratio 1:5 (appx 15 ltr) to existing pit there after put on the existing pit cover on pit, restoring existing connection to the equipments complete all as specified and directed.
M&L for painting to steel tubular pole up to 11 mtr long including cross arms without removing all accessories, preparation of old steel surfaces and painting the pole - (above coping) with 5 Nos circular strips each of 30 cm (of colour combination as directed) with synthetic enamel paint duly marked pole number in a 12 cm dia yellow circle, number writing with black synthetic paint. The remaining pole alongwith cross arms shall be painted with two coats of aluminium paint, PCC coping of pole shall be painted with one coat of cement base paint complete all as specified and directed.
M&L for painting of PCC pole 9/11 mtr long including cross arms without removing accessories after preparation of surfaces, the pole shall be painted (above coping) with 5 Nos strips each of 30 cm (of colour combination as directed) with synthetic enamel paint duly marked pole number in a 12 cm dia yellow circle with number writing with black synthetic paint. Colour washing the remaning pole and coping by using snowcem of approved colour including painting of cross arms by applying one coat of alumn paint all as required at site or directed.
All as per item No 77 here in above but bus bar capacity 200 Amps and comprises of the following incoming and outgoing:- (i) Incoming MCCB 100 Amps, FP, 415 V, 36 KA - 01 No (ii) Outgoing MCCB, 63 Amps, FP, 415 V, 16 KA - 02 Nos (iii) On load change over switch front operated 415 volts 4 pole 200 Amps rating euro load - 01 No
All as per item No 77 here in above but bus bar capacity 300 Amps and comprises of the following incoming and outgoing:- (i) Incoming MCCB 200 Amps, FP, 415 V, 36 KA - 01 No (ii) Outgoing MCCB, 125 Amps, FP, 415 V, 16 KA - 01 No (iii) Outgoing MCCB, 100 Amps, FP, 415 V, 16 KA - 02 Nos (iv) On load change over switch front operated 415 volts 4 pole 200 Amps rating euro load - 01 No
All as per item No 77 here in above but bus bar capacity 300 Amps and comprises of the following incoming and outgoing:- (i) Incoming MCCB 200 Amps, FP, 415 V, 36 KA - 01 No (ii) Outgoing MCCB, 125 Amps, FP, 415 V, 16 KA - 02 Nos
Supply and laying synthetic rubber insulated mats 2mm thick sizes 2m x 1m suitable for electrical shock dafety for voltage upto 3.3 kv for electrical purpose confirming to I5652-2006, complete all as specified and directed.
All as per item No 81 above but 2.5mm thick suitable for 11 KV.
S&F danger notice plate of 1.6mm thick MS sheet of size 20x15cm, vitreous enamelled white, with letters, figures and conventional skull and bones in singal red colour (as per sample), fixed with MS clamps, bolts and nuts of approved size for LT complete all as specified and directed.
All as per item No 83 above but for HT, of size 25x20cm.
Material and labour for construction of earth pit (excluding pit cover) as required at site and as per specification of Electrical plate No-03 of SSR part-1 complete all as specified and directed .
Material and labour for construction of earth pit cover of size 450x450x75mm of RCC 1:2:4 type B-0 (using 12.50mm crushed stone aggregate with lifting handle complete (as per sample) and placing on earth pit complete all as specified and directed.
Fixing only GI strip obtained from site as per srl item No-09 above buried in ground upto 50 cm depth or fixed to wall etc including jointing by welding for loop earthing complete all as specified and as directed. .
S&F for Galvanised iron strip size 32x6mm, buried in ground upto 50 cm depth/ fixed to wall with nut, bolt, saddles, insulators etc for loop earthing including welding of joints all as required at site including necessary excavation and earth work complete all as specified and directed or directed.
M&L MCB single pole 240 volts 5 to 30 Amps with rupturing capacity 10KA using thimles of required size, complete all as specified and directed or directed.
M&L for earthing complete with GI earth plate electrode of size 60cm X 60cm and thickness not less than 6mm buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers etc and connected to and including GI strip of size 32x6 mm by means of bolts, nuts, check nuts and washers made of brass and protected by light grade 40mm dia GI pipe connected to equipments and GI pipe light grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover 50mm thick and PCC chamber pit with PCC 1:2:4 type C2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 metre) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 making test point and all connections complete all as specified & directed.
Please Enable Macros to View BoQ information
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.45 MB
BOQ_842574.xls
BOQ • 0.34 MB
Tender89.pdf
Tender Documents • 1.09 MB
Download all tender documents and submit your bid