Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹13.7 LAccepted-AOC 361 BEHIND DAV SCHOOL JAWAHAR NAGAR SRINAGAR 190008 | SRINAGAR | JAMMU AND KASHMIR | 190008 | L-1 | Accepted-AOC Tender accepted due to lowest and quoted reasonable rates | |
| 2 | L-2₹14.6 L+₹85,310 (6.22%)Rejected-Finance HOUSE NO 95 STREET NO 08 JAWAHAR COLONY NEAR LAXMI DAIRY FARIDABAD SECTOR 22 HARYANA 121005 | FARIDABAD | HARYANA | 121005 | L-2 | Rejected-Finance Higher side quoted amount |
Tender Value
₹13.6 L
EMD Value
₹27,200
Closing Date
21 May 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE Khumbathang
CWE Khumbathang
PROVN OF 01XGENR SET (100 KVA) AT 259 TRANSIT CAMP DRASS
2022_MES_511331_2
CWE/K-82/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE KARGIL
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE Kargil
₹27,200
8 Jun 2022
30 Apr 2022
24 May 2022
30 Apr 2022
21 May 2022
7 May 2022
60 days
Amount
Supply, Installation, testing and commissioning of 100 KVA (80 KW), 415 Volt, 0.8 PF, 3 phase, 50 Hz, factory assembled Silent Diesel Engine Driven Generating set mounted on common base plateform with flexible coupling 1500 RPM alongwith sound proof enclosure (acoustic enclosure) designed for reducing the sound level to 75 DB(A) average IS 8528 Part-10 as per approved CPCB norms and as per GSR 371 (E) and independently supported from engine to outside of power house upto 1.00 mtr, AVM pads foundation as per manufacturer's design, cold starting kit battery start with suitable cables for connecting from DG set to panel board, DG set shall be capable of operating in temperature range of (-35 to +35 degree centigrade) complete with and including of the following accessories suitable for parallel operation/independent operations :- (A) Prime Mover :- Diesel Engine of capacity not less then 156 BHP Liquid cooled radiator type closed circuit as per BIS 649 or IS-1002 direct iject type turbo with turbo charger. The DG set shall be capable of running 24 hrs continuously with 10% overloading for one hour in every 12 hrs as per BIS-5514 / BIS-649, Engine shall be equipped with all standard fitting as per manufacturers recommendations and mounted on common base frame through flexible coupling with following accessories :- (i) Battery charging ammeter (ii) Battery charging voltmeter (iii) Ignition key and starting with push button switch (iv) Lubricating oil pressure gauge.
(v) Electronic / Microprocessor based Governor controlling (vi) Toggle switch for idle running (vii) Oil temperature gauge (viii) Water temperature gauge (ix) Safety Control (Trip):- (x) High water temperature (xi) Low lubricant oil pressure (xii) Over speed. (xiii) Lubricant oil heater to avoid freezing (xiv) 24 Hours starting equipment comprising of the following :- (a) 01 Nos, 12 Volts, 180 AH Batterie (b) Battery charging alternator with inbuilt regulator (c) Self starter motor of suitable capacity (d) Battery leads (copper standard cable) of suitable size with brass thimbles and terminals (B) Alternator :- Alternator of capacity of 100 KVA / 80 KW at NTP, 50 Hz, 415 Volt, 1500 RPM, 0.8 PF, running rate @ 1500 RPM, self excited, self regulated, screen protected with self excited field drush rotating fixed designed to be coupled with above engine through flexible coupling, the alternator shall be conforming to BIS-2613 or IS-4722.
(D) Other Fittings :- (i) Battery charger:- Battery charger having electric circuit consisting of rectifiers, capacitors and resistance etc. The battery charger should be able to charge 12 volts, 180 AH battery 02 Nos at a time and with 01 Nos ammeter or suitable range provision of incoming electric connector single phase 220 Volts and two terminal of connecting outgoing leads to connect battery including suitable size of 02 Nos copper leads with connecting clips duly fixed on suitable size of angle iron frame made out of 40x40x6 mm angle iron and suitable size of wooden plank complete all as specified and directed. Note :- The contractor shall produce a copy of approved certificate to authenticate the above from the OEM/OEAD. (ii) Fuel Tank capacity as per manufacturer recommendations on steel frame at suitable height with all connecting pipes and fitting upto pump and over flow pipe form engine to tank includingl level indicating gauge duly marked and drain valve and air vent plug etc. (E) Maintenance Spares :- (i) Fuel fitter element - 02 Nos (ii) Oil fitter – 03 Nos (iii) Fan Belt – 01 Nos (iv) Hose Belt - 01 Nos (v) Tappet cover gasket - 01 Nos
(F) DG Set shall be supplied alongwith acoustic original enclosure of the manufacturer suitable for 100 KVA DG set as per CPCB Norms. (G) Tool kit as supplied by the manufacturer alongwith each set - 01 set complete. (H) The DG set shall be tested by the Contractor in presence of the Accepting Officer’s representative / IEM & Engineer-in-Charge without any extra cost to the department and the quoted rates are deemed to be included for all these aspects. (J) Payment of DG set will be made after satisfactory testing. (K) The DG Set 100 KVA shall be supplied, installed, tested & commisioned at Drass(location as directed by Engineer-in-charge) under the AOR GE Kargil and the quoted rates are deemed to be included for this aspects. (L) Quantity of Cement concrete for DG Set foundation will be included in item rate.
M&L for earthing complete for DG SET with GI earth plate electrode 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25 Mtr below ground level) with top edge of earth plate not less than 1.5 Mtr below from ground level connected to GI strip 32x6mm by means of nuts, bolts, thimbles, chuck nuts, washers of copper, PCC (concrete chamber) 1:2:4 type B-1 using 20mm graded stone aggregate copy shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4 funnel wiht wire gauge of 22 gauge (0.68mm) 8 mesh per liner inch, 50 mm thick cover of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with 8 mm four MS bars @ 80mm centre to centre both ways and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision of earth wire protected by 15mm dia medium grade pipe and watering pipe shall be 40 mm bore medium grade, all excavation and earth work & connectiing the earthing to an earthing test point as specified and testing on complete all as specified & directed by Engr-in-Charge.
Supply , installation, connect test and commission factory made, cubical type outdoor vermin, dust proof LT distribution panel made out of 3.15 mm thick CRCA steel sheet and angle 50x50x6mm front and rear opening cubical shutter with locking arrangements duly tested and powder coat painted confirming to IS-8623 and accumulated of the following accessories and components:- INCOMING: (i) MCCB 160 Amps,4 pole, 415 volts, 35 KA rupture capacity with adjustable terminal setting-01 Nos
Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5M depth in hard/dense soil for laying of cable, pipes etc and getting out in hard/dense soil complete all as specified and directed by Engr-in-Charge.
Retruning, filling, including spreading, levelling, watering and well ramming in layers not exc 25cms of soil complete all as specified and directed by Engr-in-Charge.
Removing the surplus excavated materisl/soil to a distance not exc 50Mtrs and depositing, where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed by Engr-in-Charge.
Sand cushioning to under ground cable with dry sand locally available 8cm thick before laying the cable and 15 cm above the cable, stretching and testing of cable complete all as specified & directed by Engineer-in-Charge. Note: Punned thickness only will be measured and paid.
Supply and laying factory made ISI Marked unreinforced precast concrete cable cover of PCC 1:1.5:3 type A-1, class LV, Type1, flat, size 250mmx150mmx40mm laid dry over electric cable for protection complete all as specified and directed by Engr-in-Charge.
Supply, laying and testing cable LT XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of sizes 70 sqmm 3.5 core with Lt terminal both side laid in tranches or fixed to walls/poles or passing through pipe complete all as specified and directed by Engr-in-Charge.
RND ENGINEERS & CONTRACTORS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .