Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.0 LAccepted-Finance 1ST FLOOR FLAT NO 103 SCHEME NO 51 234 AVANTIKA NAGAR INDORE INDORE MADHYA PRADESH 452006 | INDORE | MADHYA PRADESH | 452006 | L1 | Accepted-Finance Financial Bid Accepted |
Tender Value
₹36.5 L
EMD Value
₹72,987
Closing Date
6 Feb 2026, 3:00 pmClosed
EE(E) HMED(N) PWD,
EE(E) HMED(N) PWD, Dr. BSA Hospital Sec-6 Rohini Delhi-85.
Replacement of 04 Nos damaged AHUs Window type AC Unit and cleaning of ducts at Bhagwan Mahavir Hospital Pitampura Delhi 110034
2026_PWD_285851_1
91/EE(E)HMED(N)/PWD/BSAH/2025 26
Open Tender
Composite Works
Percentage
30 days
BM Hospital Pitmapura Delhi
Please refer the tender Documents as per NIT
10 documents required · 10 mandatory
₹0
₹72,987
10 Feb 2026
29 Jan 2026
6 Feb 2026
29 Jan 2026
6 Feb 2026
29 Jan 2026
Supplying, Installation, Testing and commissioning of factory built floor mounted chilled water double skin type horizontal/vertical air handling units in confirmation to IS 18794 : 2024 made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for varialbe frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities. (Total static pressure considered is max. 50 mm wg). (Note:- AHU shall be AHRI/Eurovent certified )
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
Supplying, fixing testing commissioning of return air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
Cleaning all Supply Air Ducts internally by NADCA Certified agency only with skilled personnel with specialized latest Robotic Technology equipment and Vacuum machines. A robotic camera to be used for inspection and or cleaning. contractor has to provide access in duct opening for present and future cleaning requirement and sealing the same after cleaning to avoid air leakage. The contractor shall give copy of the video footage in CD before and after cleaning of ducts. Upon completion a cleaning certificate will be issued within 10-15 days, valid for 12 months. Cleaning Certificate will be issue and signed by ASCS (Air System Cleaning Specialist) & OSHA certified Complete work will be supervised & signed the daily report BY NADCA certified ASCS only on DAILY Basis.
Providing access in duct opening for present and future cleaning requirement and sealing the same after cleaning to avoid air leakage as per NADCA standard.
Replacement of following accessories of cooling tower i/c dismantling of old wornout & installation of new at its place along with accessories complete etc as required at site.
PVC nozzles
Spacer
End cap
Supply / Fixing of new P.V.C. fills of 600x300x150 mm size in induced forced draft FRP cooling tower for proper air flow for suitable capacity i/c testing,throwing and dumping of old fills complete as req.
Supply, Installation, Testing and Commissioning of Window type Air conditioners complete with copper power cable upto 3 Mtr, wireless Remote, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing, cooling, dehumidification, air circulation, R-32/R-410A /R-407B Green Refrigerant with Scroll / rotary compressor with min 5 year Original EquipmentManufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB), antifreeze thermostat on the coil as a safety feature, complete with fixing including T&P & labour etc as required complete in all respect as specified of following capacity. Sound level of up to 50dB inside the room is acceptable. The unit shall be in confirmation with IS 1391 Part-I 2023 and CPWD Specification. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. The system shall be able to operate up to 50 0C (out door ambient temperature).
Non Inventor type 1.5 TR with fixed speed 5 Star BEE rating
Dismentalling the old existing AHU and Window AC etc. i/c safely dismentalling of other allied equipment i/c less credit for dismantled material etc complete as reqd.
13600 CMH AHU
28900 CMH AHU
34000 CMH AHU
Window AC 1.5 TR.
Aluminum
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.59 MB
NIT.pdf
Tender Documents • 3.57 MB
BOQ_378335.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .