Tender Value
₹31.7 L
EMD Value
₹75,000
Closing Date
18 May 2020, 12:00 pmClosed
CHIEF GENERAL MANAGER(OandM)
O/o The Chief General Manager(Civil), First Floor, Bijulee Bhawan, Paltan Bazar, Guwahati
(1) Supply, installation, testing and commissioning of VRF Air Conditioning system at first floor (west side) of Bijulee Bhawan. (2) Comprehensive Annual Maintenance Contract for five years beyond warranty period.
2020_AEGCL_16896_2
AEGCL/DGM (Civil)/2019-20/28
Open Tender
Civil Works - Others
Works
120 days
First Floor, Bijulee Bhawan, Paltan Bazar, Guwahati
Please refer Tender documents.
2 documents required · 2 mandatory
₹750
AEGCL
₹75,000
21 Sept 2020
27 Apr 2020
19 May 2020
27 Apr 2020
18 May 2020
27 Apr 2020
Amount
Civil Works
Supply, Installtion Testing & Commissioning of Variable Refrigerant Flow / Volume SYSTEM ( with both Cooling & Heating facility ) comprising of 100% DC inverter based scroll compressor only ,connectable to multiple indoor units as per specification.Outdoor units shall be factory assembled weather proof.Casing constructed from heavy gauge mild steel(sheet metal material is hot zinc plate & sheet metal thickness is 1 mm),must have 100% DC Inverter Scroll compressor in each module & with top Air discharge through. The outdoor unit should contain error code LED display for ease of operation.The system should be equipped with eco - freindly refrigerant R 410A.The system should be of Heat Pump type and should also be suitable for operation within the ambient temperature range of 0 deg C to 40 deg C The outdoor unit shall be be complete with safety devices .The outdoor unit should be fitted with low noise fan with multiple speed DC motor and large air flow.The unit should also be capable to deliver at least 70pa external static pressure to avoid short cycling of hot exhaust air. t, Air-cooled condenser along with in built Micro Processor Panel. Units should be capable to handle incoming voltage fluctuation during operation it should have a voltage operting range from 320V - 460 V 3 phase 50Hz, balanced volt. Considering the long length piping the unit should have a good oil management system to ensure reliability.The unit should have oil separator to ensure oil recovery in the system. To maintain the oil balance in the system the units should have a facility of swapping the oil on the next ODU on a regular basis.Units should capable to operate on very low load condition upto 5%.To handle extreme climatic condition, corrotion and polluted atomshpheres unit should have powder coated GI sheet metal cabinets,all hardware of anti rust quality,conformal coating on PCBs to protect from dust and humidity,hydrophilic blue fins for better corrosion resistance, weather - proof enclosures for critical components. The minimum COP of the modules should be 3.5 at 100% load at ARI conditions. Units should be of 5th generation variant. Including Supply and installation of cordless remote controllers, Lifting and shifting of machine manually to the installtion place in complete, Supply, Installation, Testing & Commissioning of communication cable for VRF unit, Supply, Installation of MS Stand for VRF outdoor unit. 26 HP OUTDOOR UNIT (power requirement 3ph, 4 wire, 50 Hz,AC power of 18KW)
Supply , fiting, fixing installation, commissioning and testing of Non-Ductable 4 Way Cassette Unit to be connected to the VRF system and convenient to mount on false ceiling ,powder coated for long life,detacheable panel for easy service, various level of fan speed for user comfort and convenieence, low sound level of 39-41 dB. Operate on 1 phase 50 Hz AC power supply. Maximum power requirement of 62 Watt, 0.32Amps for each units.
1.0TR Capacity (513 CFM )
2TR Capacity (656 CFM )
2.8TR Capacity (1100 CFM )
Refrigerant Piping :
Supply, Instalaltion, Testing & Commissioning of Hard Drawn Copper piping along with copper bend tees elbows ,Y joints duly insulated with Nitrile Rubber Insulation of 19 mm for suction line and 13 mm for liquid line including all fittings & fixtures.
Supply, Instalaltion, Testing & Commissioning of UPVC/HDPE Drain Pipe and arrangement should be made so that lastly all drain pipes to be connected with rain water pipe:-
Supply, Instalaltion, Testing & Commissioning of UPVC/HDPE Drain Pipe and arrangement should be made so that lastly all drain pipes to be connected with rain water pipe:PVC drain piping 25 mm with 6mm nitrile insulation PVC drain piping 25 mm with 6mm nitrile insulation PVC drain piping 32 mm with 6mm nitrile insulation PVC drain piping 40 mm with 6mm nitrile insulation
Supply and Erection of galvanized Perforated Cable tray of size 300mm X 50mm X 5mm, including fittings material from outdoor unit to First floor. The work includes supplying fitting, fixing of all required fittingds, clamps, making necessary scafolding, cost of labous, repairing of damages during execution, painting, earthing etc, complete as required and directed.
Supply, erection, testing & commissioning of 4C x 16 sq mm copper cable from MCB to ODU, including supply of MCCB/MCB nearest to outdoor unit.
Comprehensive Annual maintanance for 5 (five) year beyond 1 (one) year warranty period for complete Job
for first year
for second year
for third year
for fourth year
for fifth year
RS COOLING APPLIANCES
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .