| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.0 CrAccepted-AOC | ₹17.0 Cr | L1 | Accepted-AOC Being the lowest tenderer (L1) and reasonable tender |
| 2 | L2₹17.8 CrRejected-Finance | ₹17.8 Cr | L2 | Rejected-Finance Not being the lowest |
| 3 | L3₹21.3 CrRejected-Finance | ₹21.3 Cr | L3 | Rejected-Finance Not being the lowest |
| 4 | L4₹22.7 CrRejected-Finance K 99 LGF KALKAJI NEW DELHI 110 019 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110019 | ₹22.7 Cr | L4 | Rejected-Finance Not being the lowest |
Tender Value
Refer Docs
EMD Value
₹12.5 L
Closing Date
4 Nov 2020, 6:00 pmClosed
Shri Subodh Kumar, CE (Navy) Mumbai
HQ CE (Navy) Mumbai, 26 Assaye Building, Colaba Mumbai 400005
PROVISION OF OTM ACCN (OFFICE, SINGLE ACCN AND OFFICERS MESS) FOR HQ CE (NAVY), COLABA MUMBAI
2020_MES_370518_2
87874/E8
Open Tender
Civil Works
540 days
GE (P) NW Mumbai
As per Tender Documents
8 documents required · 8 mandatory
₹3,000
GE (P) NW Mumbai
₹12.5 L
Yes
7 Dec 2020
30 Sept 2020
6 Nov 2020
30 Sept 2020
4 Nov 2020
14 Oct 2020
Amount
SCH 'A' PART-I "BUILDINGS & STRUCTURES" Total of Sch-'A' Part-I C/o to BOQ(Schedule ‘A’) Serial Page No. 40
SCH 'A' PART- II "SITE CLEARANCE, EXCAVATION & EARTH WORK. Total of Sch "A" Part-II C/o to BOQ at Sl page No 42
SCH 'A' PART-II(A) "TREE CUTTING" Total of Sch "A" Part-II(A) C/o to BOQ at Sl page No 43
SCH 'A' PART-III "INTERNAL WATER SUPPLY" Total of Sch "A" Part-III C/o to BOQ at Sl page No 44
SCH 'A' PART-IV "INTERNAL ELECTRIFICATION" Total of Sch "A" Part-IV C/o to BOQ (Schedule 'A') on Serial Page No 47
SCH 'A' PART-V "EXTERNAL WATER SUPPLY" Total of Sch "A" Part-V C/o to BOQ at Sl page No 48
SCH 'A' PART-VI "EXTERNAL ELECTRIFICATION" Total of Sch "A" Part-VI C/o to BOQ (Schedule 'A') on Serial Page No 53
SCH 'A' PART-VII "ROAD/PATH/ CULVERTS" Total of Sch "A" Part-VII C/o to BOQ on Serial Page No 55
SCH 'A' PART-VIII "COMPOUND WALL & GATE" Total of Sch "A" Part-VIII C/o to BOQ (Schedule 'A') on Serial Page No 57
SCH 'A' PART- IX "AREA DRAINAGE" Total of Sch "A" Part-IX C/o to BOQ (Schedule 'A') on Serial Page No 58
SCH 'A' PART-X "SEWAGE DISPOSAL" Total of Sch "A" Part-X(A) C/o to BOQ (Schedule 'A') on Serial Page No 60
SCH 'A' PART-X(A) "RCC HUME PIPE" Total of Sch "A" Part-X(B) C/o to BOQ (Schedule 'A') on Serial Page No 62
SCH 'A' PART-XI "LIGHTIENING PROTECTION" Total of Sch "A" Part-XI C/o to BOQ (Schedule 'A') on Serial Page No 63
SCH 'A' PART-XII "FIRE FIGHTING" Total of Sch "A" Part-XII C/o to BOQ (Sch 'A') on Serial Page No 70
SCH 'A' PART-XIII "LIFT" Total of Sch "A" Part-XIII C/o to BOQ (Schedule 'A') on Serial Page No 77
SCH 'A' PART-XIV "DG SET" Total of Sch "A" Part-XIV C/o to BOQ (Schedule 'A') on Serial Page No 78
SCH 'A' PART-XV "DEMOLITION" Total of Sch "A" Part-XV C/o to BOQ on Serial Page No 81
SCH 'A' PART-XVI " TV & TELEPHONE CONDUIT" Total of Sch "A" Part-XVI C/o to BOQ (Sch 'A') on Serial Page No 82
SCH 'A' PART-XVII "AVIATION LIGHT" Total of Sch "A" Part-XVII C/o to BOQ (Schedule 'A') on Serial Page No 83
SCH 'A' PART-XVIII (MISCELLENEOUS ITEMS)
INTERNAL WATER SUPPLY
S&F of 2way bib cock 15mm dia .Make JAGUAR/ Model No 23041-GD or equivalent in Crab Tree/Kohler brand.
S&F Angular stop cock quarter turn(wall mount) with 20 mm diameter made of brass Make - Jaquar /Model No CQT-CHR-23059 or equivalent in Crab Treek/Kohler brand.
S&F for Stainless steel concealed stop cock, Regular body with adjustable wall flange, size 20/25mm dia, Make - Jaquar /Model no CQT-CHR-23089 or equivalent in Crab Treek/Kohler brand.
S& F overhead shower rose 80mm dia (ABS body crome plated for fixing shower arm 15mm size with bend of 45 degree with flange Make - Jaquar Model No-1989GA or equivalent in crab tree/Kohler.
S&F Florentine Pillar cock with quarter turn of brass, knob controlled, Make - Jaquar/ Model No. 5015 or equivalent in Crab Treek/Kohler brand.
S&F Health faucet (ABS body) with 01 meter long PVC tube & wall hook. Make - Jaquar Model No ALD-CHR- 583 or equivalent in Crab Tree/Kohler brand.
S&F Brass Urinal flush valve of 40mm diameter round shape(installation type :wall mount) jaguar Model NO-1093 or equivalent in Crab Tree/Kohler brand.
S&F Sink Cock with swinging casted round shape spout (wall mounted model) 20mm dia ,quarter turn Make-Jaguar Model No 23347 -GD or equivalent in crab Tree/Kohler brand.
S&F wall mixer with provision for overhead shower connection with 115mm long bend pipe on upper side,connecting leggs & wall flanges .Make jaquar/ Model no 23281 UPR-GD or equivalent in Crab Tree/Kohler brand.
"INTERNAL ELECTRIFICATION"
S &F LED tube light fittings including LED bulb decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x20 Watt ,4 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc. make-HAVELLS /Model No :-LUMILINEPLUSBS20WLED965SPCSS or equivalent in Philips/bajaj
S &F LED tube light fittings including LED bulb decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x10Watt ,2 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc. Make-HAVELLS / Model No :- LUMILINEPLUSB10WLED865SPCSS or equivalent in Philips/bajaj model of Precision or other make approved by GE
S & F LED light fittingsincluding LED bulb decorative 36Watt recessed mounting type extruded metal/aluminium body, and electronic LED driver, connector block ect. with all accessories internal prewired & including connecting up with 2 core flexible cppper conductor cable with suitable size and mounting clamps etc. Make-HAVELLS/ Model No :- STRATO2X2LR36WLED840MOD or equivalent in Philips/bajaj model of Precision or other make approved by GE
S & F LED light fittings decorative 15Watt recessed mounting type extruded metal/aluminium body, and electronic LED driver, connector block ect. with all accessories internal prewired & including connecting up with 2 core flexible cppper conductor cable with suitable size and mounting clamps etc. Make-HAVELLS/ Model No:- PLUTOSURFACE1X1PLS15WLED840S or equivalent in Philips/bajaj model of Precision or other make approved by GE
S & F LED Security light fittings including LED bulb 70Watt wall mounting type extruded metal/aluminium body, and electronic LED driver, ect. with all accessories internal prewired & including connecting up with 2 core flexible cppper conductor cable with suitable size etc. Make-HAVELLS / Model No :- ENDURACITYLINERNEOSL70WLED 757PSSYBOTG or equivalent in Philips/bajaj
S &F LED light fittings including LED bulb decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x8/9 Watt ( for mirror light) ,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc. make- HAVELLS /Model no :- LUMILINEBS9WLED865SPCWH or equivalent in Philips/bajaj
S &F LED light fittings including LED bulb decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x8/9 Watt (batten holder) ,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc. make- HAVELLS/ Model No :- LED ADORE 9W B22 WW 3 STAR LAMP or equivalent in Philips/bajaj
S&F Energy efficient BEE five star rated ceiling fan, 1200 mm sweep and connecting up including provision of three core flexible copper wire of size 23/0076 from ceiling rose to ceiling fan complete in all respect all as specified and directed. ( for Tech Building & Adm Building ) -Make : Havells/ Model no Aeroking 50 or equivalent in Crompton/bajaj
S&F Exhaust fan heavy duty of size 300 mm sweep metal body complete with and louvers connecting up including provision of three core flexible copper wire of size 23/0.0076 from ceiling rose to exhaust fan. Make Make , - Havells / Model No :- Turbojet SP or equivalent in Crompton/bajaj Note:-The cost shall be inclusive of all civil works to fix & fit the Exhaust fan in the wall including making of hole in wall complete with grouting of nuts, bolts and washers and all other accessories required for fixing of fan including testing on completion.
S&F Exhaust fan of size 225/230 mm sweep Metallic body complete with powder coated metallic finish, adjustable upward and downward tilt mechanism, fan sweep area : 225/230 mm, air flow rate 510 CMH, speed 1350 RPM and louvers (Aluminium) connecting up including provision of three core flexible copper wire of size 23/0.0076 from ceiling rose to exhaust fan complete all as specified and directed. Make:- Havells /Model No Ventil -DS or equivalent in Crompton/Bajaj Note:-The cost shall be inclusive of all civil works to fix & fit the Exhaust fan in the wall including making of hole in wall complete with grouting of nuts, bolts and washers and all other accessories required for fixing of fan including testing on completion.
S& F Modular Switch with indicator (2M) , 32 A DP all as directed. Make : Havells model No :- AHFSDIW321or equivalent in Anchor/Legrand ( For AC/Geyser)
S& F Modular Socket 25 A shuttered Socket all as directed. Make : Havells model No :- AHFKCXW253 or equivalent in Anchor/Legrand (For AC/Geyser)
S&F Modular cover plate with frame 8 module .Make:havells or equivalent in Legrand.
M&L for MCB TPN 63A, 415 v, C-curve all as directed. Make ; L&T cat no BB40630C or equivalent in Wipro/Schneider
M&L for MCB TPN 32A, 415 v, C-curve all as directed. Make ; L&T CAT No BB40320B or equivalent in Wipro/Schneider
M&L for MCB TPN 16A, 415 v, C-curve all as directed. Make ; L&T Cat No BB40160B or equivalent in Wipro/Schneider
M&L for MCB TP 63A, 415 v, C-curve all as directed. Make ; L&T Cat No BB30630B or equivalent in Wipro/Schneider
M&L for MCB TP 32A, 415 v, C-curve all as directed. Make ; L&T BB30320B or equivalent in Wipro/Schneider
M&L for MCB TP 16A, 415 v, C-curve all as directed. Make ; L&T Cat No BB30160B or equivalent in Wipro/Schneider
M&L for MCB SP 6 to 32A, 240 v, C-Curve all as directed. Make L&T Cat NO BB10060B To BB10320B or equivalent in Wipro/Schneider
M&L for MCB SPN 40 A, 240 v, C-Curve all as directed. Make L&T Cat No BB20400B or equivalent in Wipro/Schneider
M&L for MCB SPN 32 A, 240 v, C-Curve all as directed. Make L&T Cat No BB20320B or equivalent in Wipro/Schneider
M&L for MCB DB SPN 8 way with IP 43 protection,Glazed double door, 1 phase all as directed.Make :L&T (for 9th floor ) Cat No DBSPN008DD or equivalent in Wipro/Schneider.
Supply & fix Hand Dryer automatic all as specified (for officer toilet) Make Dolphy Model No :- DETUAMHDRY001-B or equivalent in Dyson/american hand dryer model.
Supply & fix Geyser capacity 25 liter 5 star rating incl grouting nut bolts of suitable size .Make :Havells/ Model No :- GHWAICTWB025 or equivalent in bajaj/crompton model of Precision or other make approved by GE
Supply and fix three phase energy meter , 3 PH 4-WIRE ,RATING 10-60 AMP 240V ,EM301B Make:-L&T CAT no WM301BC7D10 or equivalent as given in PS .
Supply and install hit purification capacity 20 ltrs/ hr water purifier mineral RO technology- double purification by RO+UV with TDS controller suitable for attachement to water cooler all as specified and directed. Make Kent GRANT + or equivalent in Eureka/Aquaguard Note:- Including extended comprehensive AMC warranty of 3 years (1 year after DLP) The contractor will submit AMC contract to the ADM Officer of HQ CE (Navy) Mumbai all as specified and directed.Make:- Dr Aquaguard Eureka Forbes Model No NRICH RO+UV+MTDS
S & F LED Street light fittings including LED bulb 25Watt wall mounting type extruded metal/aluminium body, and electronic LED driver, ect. with all accessories internal prewired & including connecting up with 2 core flexible cppper conductor cable with suitable size etc. Make-Havells/ Model No :-ENDURAPEARLSL25WLED757SASYTOPCMP or equivalent in bajaj/Phillips
"EXTERNAL WATER SUPPLY"
Supply, installation, testing and commissioning of monoblock, centrifugal pump self-priming, single-stage, centrifugal volute type pump having cast iron casing, enclosed type dynamically balanced phosphor-bronze/SS impeller, high tensile steel shaft, carbon steel stuffing box (sealed by mechanical seal), deep groove ball bearings, TEFC squirrel cage induction motor having IE- 3 efficiency and conforming to IS: 12615- 2018, base plate, mounting channel frame, elastomeric insulation, accessories and fittings, viz. mechanical seal, pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring / rubber type mounting suitable for operation on 3- Phase, 415 V ± 10%, 50 Hz AC supply suitable for 6.0 LPS water flow and 54 mtr head complete all as specified and directed. Make :- Kirloskar/Crompton/CRI/KSB Necessary civil work viz. foundation for placement of pump, mounting of star/delta starter panel and pump accessories shall be covered in the scope of work.
Supply, installation, testing and commissioning of PN 1.0 rated 50 mm NB CI 'Y' -type strainer for suction conforming to IS: 907- 1984 with SS filter screen and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories for suction side of fire pumps all complete as specified and directed.
Supply, Installing, Testing and Commissioning of Ultrasonic Level Transmitter and level indicator in 4 steps duly interconnected at domestic water tank (for measurement of level) Range : 0-2.5 meters Accuracy : 0.5 % minimum Supply Voltage : 24 V dc Output : 4-20 mA Make : Banner / ABB / Emerson / Kroshne Marshall
Supply, Installing, Testing and Commissioning of Motor Actuated Butterfly Valves with appropriate bracket / mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclouser along with wafer type butterfly valve with the following specifications. Valve size : 50 mm dia. Designed line pressure : 10 kg/sq cm Operating Angle : 90 degrees Disc Material : CI with nylon coating Limit Switches : 02 Nos. For Open and Close Mounting : Direct Make : RITETORK / HASSEL HOFENER / EMTORK
M & L for ISI marked 1.1 kV grade 2 core 1.5 mm² copper conductor, XLPE insulated armoured cables, conforming to IS: 7098 (Part 1)- 1988 having stranded copper compact shaped conductor as per Cl. 2, IS: 8130- 1984, PVC inner sheath, single armouring of galvanized steel strip/wire and PVC Type ST- 2 outer sheath conforming to IS: 5831- 1984, including termination complete as specified and directed
Supply, Installation, test and Commissioning Indoor type fabricated, LT panel board ,made out of 2 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :– ( For building pump )
INCOMING:- (a) Incoming MCCB 63 A 25 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- CM97919OOH2OG
"EXTERNAL ELECTRIFICATION SUPPLY"
Supply, installation, testing and commissioning of indoor type 3 Phase, 11 kV, 50 Hz multi-panel shunt trip, indoor type motor operated spring closing vacuum circuit breaker (VCB), conforming to IEC 62271-100 of 630 A rating having SCADA compatible facilities and complete with all accessories, overload and earth fault protection for rupturing capacity of 350 MVA for augmentation with the existing HT Panel complete all as specified and directed by engineer-in-charge. Make: Schneider, ABB, Siemens, L & T
[vi] Potential transformer shall be 3-Phase, 3-Limb type with 50 VA per phase of class 0.5/3P accuracy and shall be mounted on incomer breaker truck. The same shall be mounted in a separate withdrawable truck in a separate verticle panel for bus connected PT. [vii] Control supply for closing and tripping shall be 110/220 V DC through an external battery source. 230 V, 50 Hz 1-Ph A.C supply shall be also be available for the operation of spring charging motor and cubical space heater. Wattage rating of clossing and tripping coils shall be within 250 W. Auxiliary supply shall be suitably distributed along with swithchgear in loop-in loop-out fashion. [viii] All other secondary wiring in the panel shall have high quality PVC insulation and the same shall have conductor size of not less than 1.5 m2 copper. [ix] Compact Cl0.2S power measurement device (PMD), conforming to IEC 61557-12, with battery backed-up real time clock, 4th CT for neutral and ground current measurement, dual ethernet ports for daisy chain communication, internal webpage, up to 63rd harmonic (magnitude and direction), two relay outputs for circuit breaker monitoring and control, multi-tarrif schedule, peak demand with time stamping D/T for current and power.
Supply, installation, testing and commissioning of indoor type 3 Phase, 11 kV, 50 Hz dead front, floor-standing, fully compartmentalized metal clad dust, damp and vermin-proof HT Panel conforming to IEC 62271-200 with provision of bolting to the floor, suitable for severe tropical climate conditions and fully complying with climatic aging tests as per IEC 60932, having separately earthed IP5X rated HV and busbar compartments and IP4X rated LV compartment made of CRCA sheet steel, multi-panel shunt trip, indoor type motor operated spring closing vacuum circuit breaker (VCB), 01 I/C + 02 O/G, conforming to IEC 62271-100 of 630 A rating having SCADA compatible facilities and complete with all accessories, overload and earth fault protection for rupturing capacity of 350 MVA complete all as specified and directed by engineer-in-charge (Fully assembled by company only). Make: Schneider, ABB, Siemens, L & T
[vii] Control supply for closing and tripping shall be 110/220 V DC through an external battery source. 230 V, 50 Hz 1-Ph A.C supply shall be also be available for the operation of spring charging motor and cubical space heater. Wattage rating of clossing and tripping coils shall be within 250 W. Auxiliary supply shall be suitably distributed along with swithchgear in loop-in loop-out fashion. [viii] All other secondary wiring in the panel shall have high quality PVC insulation and the same shall have conductor size of not less than 1.5 m2 copper. [ix] Compact Cl0.2S power measurement device (PMD), conforming to IEC 61557-12, with battery backed-up real time clock, 4th CT for neutral and ground current measurement, dual ethernet ports for daisy chain communication, internal webpage, up to 63rd harmonic (magnitude and direction), two relay outputs for circuit breaker monitoring and control, multi-tarrif schedule, peak demand with time stamping D/T for current and power.
NOTES: [i] The bidder shall furnish dimensional drawings of the items offered, indicating all the fittings, dimensional tolerances, typical GADs of the windings, etc. with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer.
Supply, installation, testing and commissioning of factory made, CPRI type tested, floor standing indoor cubical compartmental type MAIN LT PANEL of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by engineer-in-charge. Make: CPRI approved OEM
The Main LT Panel shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 800 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection
[B] OUTGOING [i] 400 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 02 Nos. [for BBT rising mains, spare]
[ii] 250 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [for APFC panel] [iii] 200 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [for Utilities Panel] [v] LED phase indicators (Red, Yellow, Blue)- 04 Set [vi] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 04 Nos.
NOTE: [i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System. [ii] 06 Nos. of ON / OFF / TRIP status and operations counters as well as meters shall be wired to Ethernet gateway part of the Panel. [iii] The bidder shall furnish dimensional drawings of the items offered, indicating all the fittings, dimensional tolerances, typical GADs, etc. with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer. [iv] The bidder shall intimate the Garrison Engineer of the routine tests in accordance with IEC 61439-1 & 2 and IEC 61641 in the OEM factory in presence of a representative nominated by the Garrison Engineer before dispatch.
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor cubical compartmental type UTILITIES PANEL of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by engineer-in-charge. Make: CPRI approved OEM
The UTILITIES Panel shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 320 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection
[B] INCOMING [i] 200 A, 415 V, 50 Hz AC 23A duty, 4 Pole Auto Transfer Switch (ATS)- 01 Nos. [ii] 200 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos [iii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos. [iv] LED phase indicators (Red, Yellow, Blue)- 01 Set [B] OUTGOING [i] 63 A, 10 kA, 415 V, 50 Hz, FP MCB- 02 Nos. [ii] 32 A, 10 kA, 415 V, 50 Hz, FP MCB- 03 Nos. [iii] 32 A, 10 kA, 230 V, 50 Hz, SPN MCB- 06 Nos.
NOTES: [i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System. [ii] 06 Nos. of ON / OFF / TRIP status and operations counters as well as meters shall be wired to Ethernet gateway part of the Panel.
Supply, installation, testing and commissioning of free-standing indoor semi-compartmentalised cubical type 120 kVAr APFC CAPACITOR BANK made out of 2.0 mm thick CRCA sheet and built upon rigid framework, having MPP type capacitor with 7% aluminium wound reactor units type tested in accordance with IS 16636: 2017 with contactor switching, IP 4X protection and including air system provided by axial flow fan or centrifugal fan, control wiring with FR-LSH copper wires complete all as directed by engineer-in-charge. Make: L & T, Schneider, Siemens, ABB
The APFC Capacitor Bank shall comprise of the following: [i] 250 A, 415 V, Ics = Icu = 36 kA, 50 Hz, TP MCCB with adjustable overload settings, adjustable short-circuit settings, adjustable earth- fault settings, current limiting type double break roto active type, instantaneous protection and microprocessor based trip unit- 01 Nos. [ii] High performance microprocessor based APFC relay with auto / manual switch option- 01 Nos. [iii] 3- Phase power analyser with in-built digital VAF meter, phase indicating LED lamps (R, Y, B), step indicating LED lamps, ON / OFF push buttons, timer, CT- 500/5 A, Cl1.0, 15 VA- 01 Nos. [iv] MPP capacitor of 100 ( 3 X 10 + 1 X 20 + 1 X 50) kVAr [v] 10 kVAr- 04 STEPS [a] 40 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 03 Nos. [b] 3P, 10 kVAr power contactor, 415 V, 50 Hz 230 VAC coil- 04 Nos. [c] 7% detuned reactor, 3- Ph, 10 kVAr, 440 V, 50 Hz- 04 Nos. [vi] 20 kVAr- 02 STEPS
[a] 50 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 01 Nos. [b] 3P, 20 kVAr power contactor, 415 V, 50 Hz 230 VAC coil- 01 Nos. [c] 7% detuned reactor, 3- Ph, 20 kVAr, 440 V, 50 Hz- 01 Nos. [vi] 50 kVAr- 01 STEPS [a] 100 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 01 Nos. [b] 3P, 50 kVAr power contactor, 415 V, 50 Hz 230 VAC coil- 01 Nos. [c] 7% detuned reactor, 3- Ph, 50 kVAr, 440 V, 50 Hz- 01 Nos.
NOTES: [i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System. [ii] The bidder shall furnish dimensional drawings of the items offered, indicating all the fittings, dimensional tolerances, typical GADs, etc. with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer. [iii] The bidder shall intimate the Garrison Engineer of the routine tests in accordance with IEC IS 16636: 2017 in the OEM factory in presence of a representative nominated by the Garrison Engineer before dispatch.
Supply, installation, testing and commissioning of sandwich type (3L+N+PE) busbar trunking system complete with two runs of 50 mm X 6 mm aluminium earthing strip and accessories all as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens
The BBT shall conform to the following technical specifications: [A] GENERAL [i] The busbar trunking system (BTS), both feeder and plug-in, shall be of sandwich construction. All components and fittings (straight length, elbow, tee, flanged end, cable tap-off box and circuit breaker etc.) shall conform to IEC 61439-6:2012 or UL 857 and shall be procured from the OEM of BTS. The BTS shall have IP 66 protection for outdoor application and IP 54 protection for indoor application in accordance with IEC 60529: 1989. [ii] The rated operation voltage of BTS shall not be less than 1 kV. The neutral conductor shall have the same cross-sectional area as the phase conductor and the earth busbar shall be provided on both sides of the housing.
[B] CERTIFICATE [i] The busbar , of full range and each rating, shall pass full type tests specified in IEC 61439-6-2012. The certificate shall be issued by an international independent testing authority, e.g. ASTA. KEMA. UL and ERDA etc. [ii] A product safety mark, e.g. KEMA-KEUR, ASTA DIAMOND, UL and ERDA, etc. shall be on the product offering a visual assurance of full product safety testing, factory inspection and ongoing surveillance under independent authority. [iii] The BTS shall have UBC seismic zone 5 compliance tested with busduct and plug-in box assembly by an internationally recognized earthquake research body, e.g. Asian Pacific Network of Centres for Earthquake Engineering Research (ANCER) as per IEEE 693- 2018. The OEM shall also furnish a certificate to confirm that the BTS assembly is capable of withstanding the additional vibration in shaft owing to air movements.
[C] SHORT-CIRCUIT RATINGS & TESTS [i] The entire BTS (busduct and plug-in box assembly) shall be capable of withstanding the short-circuit of electrical installation without undergoing any electrical, mechanical or thermal stress under fault condition at a service voltage of 1 kV at 50 Hz frequency. The minimum rated insulation voltage shall be 1 kV. [ii] The minimum certified short-circuit withstand capacity for 400 A rating shall be 25 kA for 1 sec. [iii] The minimum certified short-circuit withstand capacity for 800 A rating shall be 50 kA for 1 sec. [iv] The minimum certified short-circuit withstand capacity for 1250 A rating shall be 65 kA for 1 sec. [v] The minimum certified short-circuit withstand capacity for 2000 A rating shall be 80 kA for 1 sec.
[D] HOUSING [i] The busbar trunking housing shall be constructed of 1.6 mm thick electro- galvanised steel and shall be provided with a suitable protective finish of epoxy paint. [ii] The busbar trunking housing shall be totally enclosed non-ventilated for protection against mechanical damage and dust accumulation and it shall be tested for its characteristics offering resistance against corrosion [iii] The totally enclosed housing shall be manufactured by the BTS OEM and modifications of busbar trunking to make it totally enclosed by housing other than the busbar trunking OEM shall be unacceptable without written consent of the OEM.
[E] BUSBARS [i] The busbars shall be of aluminium with tin / silver plating at joint. [ii] There shall be no bolts passing through the busbars of the BBT. [iii] Each busbar shall be insulated with Class- F (155 ˚C) insulation. Epoxy insulation shall be unacceptable. [iv] The temperature rise at any point of busbar trunking enclosure shall not exceed 55 ˚C above the ambient temperature of 40 ˚C when operated at the rated current.
[F] JOINTS [i] The busbar trunking joint shall be of one-bolt type utilizing high strength steel bolt(s) and Belleville washers to maintain proper pressure over a large contact surface area. [ii] The bolt(s) shall be torque indicating and at earth potential. [iii] The bolt shall be of two-headed design to indicate proper torque has been applied and shall require only a standard long handle wrench to be properly activated. [iv] Access shall be required to only see one side of the busbar trunking to tighten joint bolts. [v] It shall be possible to remove any joint connection assembly to allow electrical isolation or physical removal of a busbar trunking length without disturbing adjacent busbar trunking lengths.
[G] PLUG-IN OPENING [i] The connecting jaw of a plug-in unit shall plug directly onto the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is unacceptable. [ii] All contact on joint and plug-in opening shall be of copper strip in order to avoid external force damage on busbar while plugging in or plugging out operation. [iii] On plug-in busbar trunking there shall be three dead front, hinged cover type plug-in opening on each side. [iv] All openings shall be usable simultaneously. Busbar trunking shall be installed in such a manner that plugs are side mounted to permit practical use of all plug-in openings. [v] It shall be possible to inspect the plug-in opening and busbars prior to the installation of plug-in units.
[H] SUPPORT STRUCTURE [i] Support structure shall be provided as per OEM's recommendation. [ii] Indoor feeder and plug-in busbar trunking shall be approved for hanger spacing of up to 3 m for horizontally mounted run and 4.88 m for vertically mounted runs. Outdoor feeder busbar trunking shall be approved for spacing up to 1.5 m for horizontally or vertically mounted runs. [I] VOLTAGE DROP [i] The voltage drop (sending end voltage minus receiving end voltage) specified shall be based on the busway operating at full rated current and stabilized operating temperature in
[ii] The 3- Phase line to line voltage drop shall not exceed 3.4 V per 100 feet length at 40% power factor concentrated load which may exist during motor starting. [iii] The line to line voltage drop shall not exceed 4.1 V per 100 feet at the load power factor which produces the maximum voltage drop in the busway. [J] INSPECTION / SUPPORT OF INSTALLATION [i] The installation of BBT shall be executed by skilled professionals with minimum experience of 4 yrs. having sufficient installation base and pre-commissioning experience. [ii] The entire installation shall be directly supervised by the OEM. [iii] The OEM shall also furnish a commissioning report underlining satisfactory installation after the commissioning of BBT system.
800 A Straight Run Feeder (IP 54 protection)
Flange End with Equilizer / Shorting Plate
Horizontal / Vertical Bend
Plug-in Point
Vertical Spring Hanger / Fix Hanger
Tinned Copper Braided Flexibles with Hardware- Nuts & Bolts
Adapter Box
End Feed Unit with 400 A, 415 V, 36 kA, 50 Hz, FP MCCB
STANDARD PLUG-IN BOX / TAP-OFF UNIT WITH FP MCCB PIB / TOU with 63 / 80 A, 415 V, 16 kA, 50 Hz, FP MCCB
SUPPORTING STRUCTURE Horizontal Fixing Clips
S & F vertical triple pole & neutral, 4 Way double door, metallic modular distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for MCCB up to 250 A as incomer and SP/TP MCBs as outgoing, reversible metal door, fully insulated 250 A copper busbar for each phase, two fully insulated & shrouded neutral bars, two earthbars, cable ties for cable management, prefitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified and directed. NOTE: MCCB/MCBs shall be measured and paid separately.
S & F moulded case circuit breaker (MCCB) in single frame size up to 250 A with thermal magnetic trip unit (TMD), 80 A, Ics = Icu = 16 kA, 415 V, 50 Hz FP MCCB compression lug connectors, protection against overloads (Ir adjustable from 0.7- 1 X In), protection against short circuits (Isd adjustable from 1.5- 10 X Ir), inbuilt encapsulated double break roto active type instanteneous protection, earth fault leakage protection, etc. having Ics = 100% Icu as per IEC 60947-2, complete all as specified and directed.
S & F MCB for AC applications conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, 63 A, 10 kA, 415 V, 50 Hz TP MCB (c- curve) sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified and directed.
S & F LED street light fitting including LED bulb having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of > 100 lm/W, integral SMPS based constant current electronic LED driver with THD < 10%, surge voltage protection and other safety tests as per IS 15885 (Part- 2/Sec- 13): 2012, IP 66 protection, polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35 mm to 42 mm, including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket having 40 mm diameter light grade GI pipe, nuts, bolts, washers, GI clamps with tw coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed by engineer- in- charge. Make: BAJAJ, Philips, Havells
S & F weather- proof PVC junction box of size 250 mm x 200 mm x 100 mm, having IP 65 protection for outdoor installation fixed with 4 way bakelite cable terminals including 03 Nos. of polymide gland with check nuts fixed on poles with flat aluminium clamps of size 20 mm x 3 mm, nuts, bolts, washers, etc. complete all as specified and as directed by engineer- in- charge. Make: Sintex, Hensel, HPL
M&L for Decorative LED 40W post top lantern fittings including LED bulb for 360 indirect light ,IP 65 protection ,resistant to impact and corrosion glare free and better uniformity inclding necessary electrical connection and fixing arragements (GI pipe, bolts, nuts) on post all as specified and directed by engineer- in- charge. Make :- Crompton Cat No LPTO-40-CDL, Havells ect.
Supply, installation, testing and commissioning of intelligent street light control (ATSC) suitable for 6 kW maximum load, wall/pole mounted, having built-in networking support, built-in astronomical timer, 32 A TP contactor, 40 A TPN MCB housed in 3.15 mm thick powder CRCA sheet housing all complete as specified and directed by engineer- in- charge. Make: Havells, HPL, Insu
"COMPOUND WALL GATE"
S&F barbed razor tape concertina coil SG hot galvanized spring tensile wire to particular here-in-after or other equivalent make as approved by GE of UTS 145 to 150Kg/sqm and Dia od Coil when unstretched 601mm having minimum number of circles 10/Rm ,minimum nmber of clips 25/RM and minimum weight of coil 1.625Kg/rm ,hot dip galvanized razor ribbon tape of size 0.5 mm thickness,19mm width before wrapping on central core wire fixed with GI 1.66mm clips and special nut bolts to hold two coils together and extra 2 rows parallel wire of 10 gauge tied by binding wire wherever complete all as specified and directedby engineer-in-charge.
S and F Framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunkfor screw, including bending and welding angles, as necessary,gusset plates, riveting, etc .. n exc 10 kg each brackets, conforming to Fe.290.Gde-E-165 (Brackets over 10 kg each to be measured under 'Structural Steel')
"FIRE FIGHTINING"
Construction of brick masonary valve chamber in repair of size 0.9x0.9x1.0mtr(internal dimension) above ground level 30mm suitable for 100mm dia sluice valve ,15cm thick foundation using PCC 1:4:8 type D-2 (using 40mm graded stone aggregate )over 15 cm thick hardcore 23cm thick brick wall builts in cement and sand motor 1:3 ,finished even and smooth ,without using extra cement ,10mm thick mild steel plate cover on 50mmx50mmx6mm MS angle iron frame embeded in PCC 1:2:4 type B-1 (using 20mm graded stone aggregate coping having rectangular hinged opening of size with locking arrangenment & handle made out of 25 cm dia MS round bar,hold fast etc. aaplying one coats oxide primer and two coats of synthetic ,enemelled paint to all steel surface and earth work in any type of soil including disposal of surpulus soil distnce not ex 50 mtr complete all as specified.
M&L for low smoke zero helogen (LS0H) flame redundant fire alarm cable 2 core 1.5 mm² conforming to BS 7629-1,BS 6387&BS EN 50200 and rated for 500 V, having plain annealed stranded copper conductor with primary insulatio of glass mica fire resistant tape and secondary insulation of high perfomance silicone rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheath conforming to BS 7655, suitable for operating temperature range -30°C to + 70°C and minimum bending radius being 6 times the overall cable diameter, RED in colour, including laying, termination and ferruling complete all as specified and directed by Engr-in-charge. Make:- RR Kabel, Havells or Polycab. .
Material and labour for fire points made out from MS angle iron 40x40x6mm cutting welding etc ,including rain protection canopy made out of 2.0mm thick CRCA Sheet ,painting with two coats of red post office colour all as directed for keeping various accessories
Providing ,Fixing ,testing and Commissioning 150 mm dia CI double flanged control valve assembly (Tyco/HD) with alarm gang,consisting of installation stop valve ,alarm valve drain 50mm dia and 15mm dia test valve,pressure guage on inlet and outlet with alarm motor and gang,alarm check valve clack with padlock and stop drain plug ,alarm stop valve and strainer including making inlet /outlet connection by providing necessary nuts,bolts, gasket (6mm thick) all complete.Make:Aira or equivalent kirloskar.
Providing and Fixing paddle type flow switch (switzer/Danfoss) on pipes with welded socket including stainless steel paddle suaitable to pipe dia 150mm to 25mm testing and commissioning etc complete.Make:Honeywell or equivalent in charun.
Providing and fixing bronze orifice with 12mm thick disc with tag on plate mentioning dia of orifice for sprinkler system to control the pressure including rubber gasket packing ,bolts nuts,washers all complete.Make:Teleflo/Flowtech
Providing and Fixing suitable C.I air release single valve (Zoloto /ZIP) of 20mm dia including necessary support and painting with two coats of enamel paint over a coat of primer etc for wet riser termination.Make:RPI/zoloto
Fire Extinguisher Dry Chemical (IS 15683) -4 kg capacity Powder (ABC) Type.Make:Bariex/VFF-4ABC
Fire Extinguisher CO2 Type light (IS 14683) -3 kg capacity weight squeeze grip type.
Supply & Fix Zonal Annunciator panel conforming to IS:2189 with battery backup with built in Charger ,16X1 Line Dot matrix LCD display Operating temerature 0 to 40 degree c ,AC power 220V ,50HZ,and stand by:24V DC ,Operating humidity ;95%(non-Condensing) all as specified.
Supply and fix Fire Alarm main control panel 240V AC supply input and built in battery backup , mainly consisting of loop driver,repeater,detectors and associated Testing kit for performing the major functions as below: i) Detection of fire in its incipient stage and give an audio-visual annunciation at specified locations/backup location with quick and exact identification of the fire location as well as operated auxiliary devices as programmed. ii)The detectors shall be analouge Adderasable type and suitable for connection to the control panel via a two wire loop circuit ,it shall have dual alarm and power leds. iii)Compatible Plug in types bases shall be supplied with all detectors ,MCPs ,sounder etc.cable wire size up to 1.5sqmm recommended.Make:Karsan
M&L for construction of fly ash brick masonry valve chamber of size 1000mm x 800mm x1000mm (internal dimensions) with PCC foundation 1:4:8 type D2 using 40mm graded stone aggregate, 150mm thick and 150mm wide offsets around over 100mm thick, hardcore, 200mm thick fly ash brick masonry walls build in CM 1:6, 100 mm thick PCC 1:2:4 type B1 coping finished ever and smooth, rendering 10mm thick cement mortar (1:6) finished even and smooth, with out using extra cement internally including top of floor including excavation earth work in hard/dense soil 6mm thick MS sheet cover fixed on 25mm x 25mm x 6mm thick angle iron frome with hold fasts embedded in PCC coaping with locking arrangement, mild steel handle and painting to steel surfaces with two coats of synthetic enamel paint over one coat of primer including disposal of surplus soil to a distance not exceeding 50m etc complete all as specified and directed.
S&F of FM approved and UL listed sprinkler flexible pipe of stainless steel complete with 15 NPT on reducer thread having 175 psi maximum working pressure with branch line (inlet) 25 mm NPT make to sprinkler head (outlet) 15 mm NPT female thread with reducer,nipple,2 side bracket, stockbar, etc. 900mm in length complete all as specified and directed by Engr-in- Charge.
"TELEPHONE CONDUIT"
M& L for telephone jak with module metal flushed including flushed Box cover plate Box for 2 way module complete all as specified.Make:Havells/AHLKHWW000 or equivalent in Legrand.
S & F for socket TV socket module metal flushed including flushed Box cover plate Box for 2 way module complete all as specified. Make:Havells/AHLKTOW000 or equivalent in legrand.
Supply and lay RG 6 Co axial cable for TV cable drawn through conduit complete all as specified and directed. (Note:- From electric room to officers (10 nos) and single living accn & mess (12 nos) approximately).Make:havells/finolex.
M&L for 2 pair telephone cable copper conductor of 0.5mm dia drawn through conduit complete all as specified and directed
"AVIATION LIGHT"
Supply and fixing aviation light luminaire,LED type comprising of aluminium housing with polycarbonate enclosure complete all as specified. Make :Bajaj,Model No : 110731 or equivalent Havells/phillips.
"ARBORICULTURE"
Spreading of good earth, sludge/manure in required thickness including filling with earth or earth mixed sludge or/and manure before and after flooding trench with water all as specified and as directed
Supply of organic manure neemstrid. NPK 19:19:19 for mining with good earth in required portion
Supply and planting of plants with decorative concrete pots, height of plants not less than 600 mm above ground level and having good health and well developed root system of Palm trees
Supply of potted decorative indoor plants
S&F of the sapplings of decorative bordering plants akalifa all colours/duranthas/pisoniya alba/decorative flowers/red night including all transportation and labour charges and incl of excavation in any type of soil for planting the sappling, pack size 8" to 15" and height 2 ft to ft completed all as specified and as directed by GE
S & F sapplings of Mangifera Indica (Mango) height 1.50 in plus. girth 2 cm to 4 cm pit size (0.9 m dia x 0.9 in depth) including at transportation, labour charges and incl of excavation in any type of soil for planting the sappling, pit size 8" to 15" and height 2 ft to 5 ft. completed all as specified and as directed by GE
S & F sapplings of Cocos Nucifera (Coconut) height 1.50 m plus, girth 2 cm to 4 cm pit size (0.9 in dia x 0.9 in depth) including all transportation. labour charges and incl of excavation in any type of soil for planting the sappling, pit size 8" to 15" and height 2 ft to 5 ft. completed all as specified and as directed by GE
S & F sapplings of Phyllanthus Emblica (Goose berry/Amla) height 1.50 in plus, girth 2 cm to 4 cm pit size (0.9 m dia x 0.9 m depth) including all transportation. labour charges and incl of excavation in any type of soil for planting the sappling. pit size 8" to 15" and height 2 ft to 5 ft. completed all as specified and as directed by GE
S & F sapplings of Citrus Limon (Lemon) height 1.50 in plus. girth 2 cm to 4 OR pit size (0 9 in dia x 0.9 in depth) including all transportation, labour charges and incl of excavation in any type of soil for planting the sappling, pit size 8" to 15' and height 2 1105 ft. completed all as specified and as directed by GE
S & F sapplings of Syzygium Cumini (Jamun/Black plum) height 1.50 in plus. girth 2 cm to 4 cm pit size (0.9 m dia x 0 9 in depth) including all transportation labour charges and incl of excavation in any type of soil for planting the sappling. pit size 8" to 15" and height 2 ft to 5 ft completed all as specified and as direct. by GE
S & F sapplings of Psidium Guajava (Guava) height 1.50 in plus, girth 2 cm to 4 cm pit size (0.9 in dia x 0.9 in depth) including at transportation, labour charges and incl of excavation in any type of soil for 8" planting the sappling. pit size to 15" and height 2 ft to 5 ft. completed at as specified and as directed by GE
Comprehensive Maintenance of Lifts
Comprehensive maintenance and repair of fully automatic electrically operated passenger lift of any make and 13 Passenger capacity lift installed against Sch 'A' Part- VII, Item No. 1, herein before in building (G+10), (Total 3 Lifts) comprising of all devices and accessories through out 12 months on all days including holidays for period of 03 years after expiry of defects liability period as shown below and all as specified and directed by GE. Note:- Contractor shall carry out comprehensive mainenance (routine, daily, weekly, monthly, quarterly, half yearly, yearly) as per attached proforma and maintain all the lifts in serviceable condition 24 Hrs X 365 days without any extra cost.
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(c) 3rd year after expiry of defects liability period
DG Sets
Supply, installation, testing and commissioning of silent DG Set, confroming to IS: 10002-1981,complete with Diesel Engine of suitable BHP & AC Brushless SPDP alternator, conforming to IS: 13364-1992, mounted on a common base frame & coupled through a flexible coupling or close coupled complete with platform, control panel having meters, sound-proof canopy, as per CPCB norms etc of capacity 62.5 kVA complete all as specified and directed. Make:- Kirloskar, Crompton Greves, Cummins or other make approved by GE
(a) Engine: 4/6 cylinder, in-line, 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude, Inline fuel pump with A1 class mechanical governing, spin on fuel filter, standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature, full flow spin on lube oil filter, electrical starter motor with soft start engagement feature, ffbattery charging alternator with 1x 12 V DC battery. [b] Alternator Brushless type, screen protected, revolving field, self-excited alternator, conforming to IS/IEC 60034-1 3-phase reconnectable winding with 12 terminals brought out for connection, dedicated winding specially designed for single operation, impregnation on all wound components for better mechanical strength. [c] Control Panel: Manufactured with 14/16 gauge CRCA sheet and powder coated for weather-proof and long lasting finish.
The control panel consists of the folowing parts (i) Controller: Aluminum bus bars with suitable capacity with incoming/outgoing terminals (ii) Indicating lamps for Load ON' and 'Set Running' (iii) Instrument fuses duly wired and ferruled (iv) MCCB of suitable rating with overload and short circuit protections (d) Microprocessor based generator set monitoring and control system including an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics, LED backlit LCD display with tactile feel soft-switches & generator set status LED lamps, remote START-STOP
[e] Engine Metering: Oil pressure, engine temperature, starting battery voltage, engine running hours AC Alternator Metering: L-L voltage and L-N voltage, current (phase and total), kVA (phase and total) and frequency. (g) Engine Protection: Low lube oil pressure, high/low coolant temperature, battery over/under/weak volts, fail to crank/start, sensor failure, cranking lockout, low fuel level. (h) AC Altenator Protection: Over/under voltage, over/under frequency, loss of AC sensing. Data Logging: Engine hours, control hours and upto 5 recent fault codes. (j) Configurable glow plug control. (k) 12 V DC operation. (l) Silencer Critical grade silencer suitably optimized to meet stringent noise emission standards laid down by MoEF/CPCB & the insulation of silencer. (m) Mounting Arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. (n) Base frame with integral fuel tank is provided with drain Plug, air vent, inlet and outlet connection, level indicator and Provision for cleaning. Note:- The foundation for the DG set as per the manufacturer Recommendation deem to be included in the rate quoted for DG set.
M& L for Enclosed Automatic transfer Switch capacity125A complete all as specified and directed. (a) protection ;UV/OV, Phase sequence, single phasing (b) frequency author control through password protection (c) Terminal shrouds, phase barriers & source separator (d) double break contact system offering high short-time withstand (lcw) (e) High mechanical and Electrical life double than requirement of IS/lEC standard (f) Suitable for aluminium terminal Make:- L&T Cat No CK90161BsOO or other make approved by GSE
RAMDEV CONSTRUCTION CO.
MC Gandhi and Sons
SOOD ASSOCIATES PVT LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid