Superintending Engineer
Estate Office NIT Warangal
Design, Supply, Installation, Testing and Commissioning of Power Management System PMS SCADA based on premise for all Substations 6 Nos at NIT Warangal campus
2026_NITW_908679_1
02/NITW/EO/ELEC/2026-27
Open Tender
Electrical Works
Works
120 days
NIT Warangal
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,180
The Director
₹78,400
20 Jul 2026
14 May 2026
19 Jun 2026
14 May 2026
18 Jun 2026
14 May 2026
14 May 2026 - 28 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Design, Supply, Installation, Integration, Testing and Commissioning with programming and configuration of Modbus RTU to Modbus TCP/IP gateway for Power Management System (PMS-SCADA based) on premise with Wired Architecture using Company LAN for 10,000 tags with Data base, Reporting tool and minimum 5 users webview provision at a time. PMS software should have Customized Dashboard Reporting with Historical database and Dedicated display of Energy and PQ Dashboard and PMS software shall be complete in all respect with following Functionalities.
1. Data Acquisition for metering devices, sensors, and other intelligent electric devices i.e., The PMS Software suitable for monitoring and control of Electrical Substations equipment’s comprising of VCB panels (Breakers, relays), Transformers, S/S LT Panels and Sub Panels (Control of incomer breakers, status monitoring of all switchgears), Power Quality Equipment’s. DG Synch, ATS, APFCR etc..
2. Power Quality analysis (including harmonics, voltage sags/swells, transients and voltage and current sinusoids), Power Quality compliance reporting for international standards (IEC61000 4 30)
3. Reports (100ms PQ Report, Energy Period over period Report, Energy usage by shift report, System configuration report, Hourly Usage Report, Data Export Report and any other customer requires) and Reports are easy to read and understand - they are fully customised reports with user-created templates
4. PMS software should be SCADA-based for device communication, integration, data acquisition, data management, monitoring & control and Business Intelligence with License engineering software.
5. PMS Software should be Customisable for SLD creation and SLD's are to be created for Overall Power Distribution and Individual Substation wise SLD of 6 No's i.e., can programme the system as per specific needs. The system has a customised SLD creation and Trends.
6. PMS Software should be Real-time reporting: Real-time communication for monitoring, control and diagnostics and system should supports multiple protocols and drivers like Modbus TCP/IP, Modbus RTU, IEC 61850, Simatic S7, OPC-UA, MQTT.
7. The system should provide a facility with alerts and acknowledgments.
8. PMS software should have Fully customized Dashboards to Create own dashboard to monitor KPIs such as:
• Energy consumption
• Power factor
• Maximum demand
• Regenerative power
• Harmonic distortion
• Specific energy consumption etc.
9. PMS software should have Compile energy monitoring for different loads to obtain holistic picture.
• View instantaneous parameters like voltage, current and power factor at a single location, through aesthetic dial gauges.
• Continuously monitor drive parameters, e g. power, energy, current, voltage, frequency etc.
10. Instant alerts by email & SMS notifications.
Make: L&T (L&K)/ Honeywell/ Schneider/ Siemens/Jhonson Control/Equivalent | 1 | Lot | 10,87,246.1 | ₹10,87,246.1 |
| 2 | Supply and Installation of Modbus RTU to Modbus TCP/IP gateway converters i.e. from D+ and D- to Ethernet wiring standard for the communication-capable products with RS485 port with EMS software and Gateway supports Modbus RTU, ASCII (Master/ Slave) with and without mapping.
Make: L & K/ Honeywell/ Schneider/ Siemens/Jhonson Control/Equivalent | 30 | Each | 17,912.4 | ₹5,37,372 |
| 3 | Supply and drawing of 0.5 sq.mm 2 core Shielded twisted pair data cable, copper with low impedance, capable to transmit the data of the energy meters serial port RS485 with PVC sheath to gateway converters including conduit on surface/ recessed steel/ PVC conduit, ties/clamps and including terminations etc as required.
Make: Beldon/ Finecore/Varsha/ AT&T/Caliplast | 2,300 | Meters | 210.04 | ₹4,83,092 |
| 4 | PC System
Supplying Installation Testing Commissioning of Client PC System comprising of PC Hardware with minimum 11th Gen Intel® I7 processor CPU x64 (or better), compatible with 8 core processors minimum 3.1 Ghz and 32GB RAM, Hard Drive Space of 256 GB SSD and 2TB HDD and DVD ROM, Video card and monitor (24 inch full LED) capable of 1920 x 1080 pixel resolution or better with Ethernet adapter (10/100/1000 Mbps with RJ-45 connector), USB Ports (2Nos), NIC (2 No's - 4 ports) with 2 GB or higher Graphics card HDMI ports with USB keyboard, USB Mouse three button and scrolling, . With licensed Windows 10 Pro/11, 64 bits software or higher, MS Office 2013 or better 64 bits software, Anti Virus Software and Adobe reader as per suitable for BMS/PMS System complete etc. as required.
Make: Hewlett Packard/ Lenevo/ Dell
Monitor Make: Samsung/ Sony/LG/ Dell/HP | 1 | Each | 2,30,100 | ₹2,30,100 |
| 5 | Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Data Cable in existing conduit on surface/recessed including ties/ clamps, terminations etc., Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force : 11.5Kg etc. complete as required.
Make: D Link/AMP/Molex/Legrand/Krone/R & M . | 1,400 | Meters | 60 | ₹84,000 |
| 6 | Supply and fixing of Cat 6 RJ-45 information outlets including Single face plate and fixing of 2 module GI/PVC box along with modular base & cover plate including terminations and ferruling. | 15 | Each | 1,081.08 | ₹16,216.2 |
| 7 | Supplying and fixing of 25mm sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as
required.
Makes : Sudhakar / Finolex / Modi / VIP/ Precision / Universal / Million Plast /Goldmedal / GM / DEC / Beljin | 550 | Meters | 168 | ₹92,400 |
| 8 | Supply and Installtion of 16 port or site suitable requirement basis of 10 / 100 / 1000 Gigabit unmanageable Ethernet switch.
Make : TP Link / D link / Netfox | 15 | Each | 7,805.7 | ₹1,17,085.5 |
| 9 | Supplying of external 4TB (Terabytes) capacity Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications.
Make : WD / Seagate or equivalent as approved by Department | 1 | Each | 13,943 | ₹13,943 |
| 10 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of upto 35 sq.mm or laying of OFC cable in HDPE pipe direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. | 500 | Meters | 253 | ₹1,26,500 |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.98 MB
Tendernotice_2.pdf
PDF • 0.13 MB
tenderdocscada.pdf
Tender Documents • 0.97 MB
Niet.pdf
Additional Documents • 0.02 MB
BOQ_955054.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .