Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.1 CrAccepted-AOC 184 NEAR GOODWAY TAILORS PRITHVIPURA RASAL ROAD BRIDGE JODHPUR RAJASTHAN 342006 | JODHPUR | RAJASTHAN | 342006 | ₹3.1 Cr Quoted ₹2.6 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹3.2 Cr+₹60.2 L (23.0%)Rejected-AOC T 3 PARMESHWARI BLDG CHATRIBARI RD GUWAHATI ASSAM 781001 | KAMRUP METRO | ASSAM | 781001 | ₹3.2 Cr+₹60.2 L (23.0%) | L2 | Rejected-AOC L2 |
| 3 | Rejected-Technical | - | - | Rejected-Technical Non-responsive |
| 4 | Rejected-Technical | - | - | Rejected-Technical Non-responsive |
Tender Value
Refer Docs
EMD Value
₹8 L
Closing Date
21 Oct 2019, 1:00 pmClosed
CGM(PPandD)
O/o the MD, AEGCL, Bijulee Bhawan, Paltanbazar
Turnkey Construction of 2 nos. of 132kV Line Bays including Supply of Bay Equipment and line bay materials and associated works etc at Samaguri and Khaloigaon GSS, AEGCL
2019_AEGCL_13524_2
Tech-811/132kVLineBays(2)/AP
Open Tender
Electrical Works
Turn-key
240 days
Guwahati
Please refer Tender documents.
6 documents required · 6 mandatory
₹2,000
AEGCL
₹8 L
3 Mar 2022
23 Sept 2019
21 Oct 2019
23 Sept 2019
21 Oct 2019
23 Sept 2019
Amount
145kV, 3150A, SCR 40kA for 1 sec, SF6 Circuit Breaker, outdoor type, 3-ph gang operated complete with terminal connector, operating mechanism & support structure
145kV Gang operated SF6 Breakers as specified above ( Samaguri-1 set , Khaloigaon-1 set )
Indoor floor mounted, simplex type Control & Relay Panel with mimic & annunciation panel for 132kV feeder as per specification comprising of the C&R panels shall be complete with Numeric Relays as per the Technical Specifications & shall be compatible for SCADA/SAS as open protocol.
For 132 kV Feeder Panel (Simplex Panels) as specified above ( Samaguri-1 set , Khaloigaon-1 set )
145kV outdoor type . live tank single phase Current Transformers as per the details below
CTR 800-400/1-1-1-1 A ( Feeder CT) ( Samaguri-3nos & Khaloigaon-3nos)
145kV , 1-ph, Capacitor Voltage Transformer ( CVT) for 132kV line
132 KV CVT ( Salakati - 3, Kokrajhar-6 & Bilasipara-3)
145kV, 1250A, 40kA for 1 sec, 3-ph gang operated Horizntal Centre Break ( HCB) , outdoor type , motor operated Isolators including solid core post insulators , mounting structure complete with nuts, bolts , washers and foundation bolts
132 kV With single Earth Switch ( Samaguri- 1 set, Khaloigaon-1 set)
132 kV With two Earth Switch( Samaguri- 1 set, Khaloigaon-1 set)
132 kV Without Earth Switch (Tandem Type) ( Khaloigaon-1 set)
120kV, 10kA metal oxide type, heavy duty, station class-3 Lightning Arrester complete with Surge Counter & flexible copper connecting lead
132 kV Lightning Arrester ( Samaguri - 3nos, Khaloigaon-3nos)
Post Insulator with terminal connectors.
132 kV Post insulator ( Samaguri - 6, Khaloigaon-8)
Supply of Mounting structures of all equipment including nuts, bolts & washers ( as per enclosed drg for bidding purpose)
Current Transformers
132 kV, 800-400/1-1-1 Line CT(Samaguri End) ( 174.511kg per CT, 3x174.511kg = 523.533kg )
Foundation Bolts(Samaguri End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
132 kV, 800-400/1-1-1 Line CT(Khaloigaon End) ( 174.511kg per CT, 3x174.511kg = 523.533kg )
Foundation Bolts (Khaloigaon End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
Capacitance Voltage Transformer
132 kV CVT(Samaguri End) ( 184.393kG per CVT, 184.393x3=553.179kg)
Foundation Bolts (Samaguri End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
132 kV CVT(Khaloigaon End) ( 184.393kG per CVT, 184.393x3=553.179kg)
Lightning Arrester
132 kV LA(Samaguri End) ( 218.879kg per LA, 218.879x3=556.637kg)
Foundation Bolts (Samaguri End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
132 kV LA (Khaloigaon End) ( 218.879kg per LA, 218.879x3=556.637kg)
Foundation Bolts (Khaloigaon End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
Post Insulator
132 kV PI (Samaguri End) ( 219.59kg per PI, 219.59x6=1317.54kg)
Foundation Bolts (Samaguri End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
132 kV PI (Khaloigaon End) ( 219.59kg per PI, 219.59x8=1756.72kg)
Foundation Bolts (Khaloigaon End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
Bay Steel Structures except equipment mounting structures
COLUMNS: (For Column types refer drawings)(Samaguri End)
Column Type ‘C1A’ ( 3580.092 kg per column, 3580.092x1=3580.092kg)
Foundation bolt ( 40mm dia, 1500mm length with 300mm threaded , nuts, lock nuts , washers and anchor plate, 17.55kg per fdn bolt)
BEAMS: (For Beam types refer drawings) ( Samaguir End)
Beam Type ‘B1 (867.892kg per beam , 867.892x1=867.892kg’ )
Supply of Power and Control Cables
Power Cables
4C, 4 sqmm ( Samaguri-400m, Khaloigaon -400m)
4C, 6 sqmm ( Samaguri-400m, Khaloigaon -400m)
Control Cables
4C, 2.5 mm2( Samaguri-500m, Khaloigaon-500m)
7C, 1.5 mm2 ( Samaguri-500m, Khaloigaon -500m)
12C, 1.5 mm2( Samaguri-400m, Khaloigaon -400m, )
Supply of ACSR Conductor
ACSR ‘PANTHER’ ( Samaguri-1km, Khaloigaon -1km)
Disc Insulator String complete with all hardware, fittings, clamps etc.
10 Disc Tension Insulator String ( Samaguri-3set, Khaloigaon - 3 set)
9 Disc Suspension Insulator String ( Samaguri-3set, Khaloigaon -3set . )
Earth mat conductor and electrodes
50 x 10 mm GI Flat (Samaguri-400m, Khaloigaon - 400m)
40 mm dia. rod electrodes ( Samaguri-15, Khaloigaon -15)
Supply of Bay Marshalling Kiosk and support structure
PLCC Equipments (alongwith necessary cables, etc. for commissioning)
EPAX (8x24) with 24 nos telephone, cable etc
Digital Protection Coupler with PLC Terminal
LMU/LMDU
HF Cable , 75 ohms(balanced)
132kV , 800A wave trap for 40kA for 1 sec wave trap
Description of Work / Item(s)
Amount
145kV, 3150A, SCR 40kA for 1 sec, SF6 Circuit Breaker, outdoor type, 3-ph gang operated complete with terminal connector, operating mechanism & support structure
145kV Gang operated SF6 Breakers as specified above ( Samaguri-1 set , Khaloigaon-1 set )
Indoor floor mounted, simplex type Control & Relay Panel with mimic & annunciation panel for 132kV feeder as per specification comprising of the C&R panels shall be complete with Numeric Relays as per the Technical Specifications & shall be compatible for SCADA/SAS as open protocol.
For 132 kV Feeder Panel (Simplex Panels) as specified above ( Samaguri-1 set , Khaloigaon-1 set )
145kV outdoor type . live tank single phase Current Transformers as per the details below
CTR 800-400/1-1-1-1 A ( Feeder CT) ( Samaguri-3nos & Khaloigaon-3nos)
145kV , 1-ph, Capacitor Voltage Transformer ( CVT) for 132kV line
132 KV CVT ( Salakati - 3, Kokrajhar-6 & Bilasipara-3)
145kV, 1250A, 40kA for 1 sec, 3-ph gang operated Horizntal Centre Break ( HCB) , outdoor type , motor operated Isolators including solid core post insulators , mounting structure complete with nuts, bolts , washers and foundation bolts
132 kV With single Earth Switch ( Samaguri- 1 set, Khaloigaon-1 set)
132 kV With two Earth Switch( Samaguri- 1 set, Khaloigaon-1 set)
132 kV Without Earth Switch (Tandem Type) ( Khaloigaon-1 set)
120kV, 10kA metal oxide type, heavy duty, station class-3 Lightning Arrester complete with Surge Counter & flexible copper connecting lead
132 kV Lightning Arrester ( Samaguri - 3nos, Khaloigaon-3nos)
Post Insulator with terminal connectors.
132 kV Post insulator ( Samaguri - 6, Khaloigaon-8)
Supply of Mounting structures of all equipment including nuts, bolts & washers ( as per enclosed drg for bidding purpose)
Current Transformers
132 kV, 800-400/1-1-1 Line CT(Samaguri End) ( 174.511kg per CT, 3x174.511kg = 523.533kg )
Foundation Bolts(Samaguri End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
132 kV, 800-400/1-1-1 Line CT(Khaloigaon End) ( 174.511kg per CT, 3x174.511kg = 523.533kg )
Foundation Bolts (Khaloigaon End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
Capacitance Voltage Transformer
132 kV CVT(Samaguri End) ( 184.393kG per CVT, 184.393x3=553.179kg)
Foundation Bolts (Samaguri End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
132 kV CVT(Khaloigaon End) ( 184.393kG per CVT, 184.393x3=553.179kg)
Lightning Arrester
132 kV LA(Samaguri End) ( 218.879kg per LA, 218.879x3=556.637kg)
Foundation Bolts (Samaguri End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
132 kV LA (Khaloigaon End) ( 218.879kg per LA, 218.879x3=556.637kg)
Foundation Bolts (Khaloigaon End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
Post Insulator
132 kV PI (Samaguri End) ( 219.59kg per PI, 219.59x6=1317.54kg)
Foundation Bolts (Samaguri End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
132 kV PI (Khaloigaon End) ( 219.59kg per PI, 219.59x8=1756.72kg)
Foundation Bolts (Khaloigaon End) ( 20mm dia, 500mm length with 125mm threaded, nut, lock nut , washer and anchor plate, 1.816kg per bolt )
Bay Steel Structures except equipment mounting structures
COLUMNS: (For Column types refer drawings)(Samaguri End)
Column Type ‘C1A’ ( 3580.092 kg per column, 3580.092x1=3580.092kg)
Foundation bolt ( 40mm dia, 1500mm length with 300mm threaded , nuts, lock nuts , washers and anchor plate, 17.55kg per fdn bolt)
BEAMS: (For Beam types refer drawings) ( Samaguir End)
Beam Type ‘B1 (867.892kg per beam , 867.892x1=867.892kg’ )
Supply of Power and Control Cables
Power Cables
4C, 4 sqmm ( Samaguri-400m, Khaloigaon -400m)
4C, 6 sqmm ( Samaguri-400m, Khaloigaon -400m)
Control Cables
4C, 2.5 mm2( Samaguri-500m, Khaloigaon-500m)
7C, 1.5 mm2 ( Samaguri-500m, Khaloigaon -500m)
12C, 1.5 mm2( Samaguri-400m, Khaloigaon -400m, )
Supply of ACSR Conductor
ACSR ‘PANTHER’ ( Samaguri-1km, Khaloigaon -1km)
Disc Insulator String complete with all hardware, fittings, clamps etc.
10 Disc Tension Insulator String ( Samaguri-3set, Khaloigaon - 3 set)
9 Disc Suspension Insulator String ( Samaguri-3set, Khaloigaon -3set . )
Earth mat conductor and electrodes
50 x 10 mm GI Flat (Samaguri-400m, Khaloigaon - 400m)
40 mm dia. rod electrodes ( Samaguri-15, Khaloigaon -15)
Supply of Bay Marshalling Kiosk and support structure
PLCC Equipments (alongwith necessary cables, etc. for commissioning)
EPAX (8x24) with 24 nos telephone, cable etc
Digital Protection Coupler with PLC Terminal
LMU/LMDU
HF Cable , 75 ohms(balanced)
132kV , 800A wave trap for 40kA for 1 sec wave trap
Description of Work / Item(s)
Amount
Erection, testing & commissioning of Circuit Breakers including laying & terminating of LT power and control cables as required
145kV Gang operated SF6 Breakers as specified above ( Samaguri-1 set , Khaloigaon-1 set )
Erection, testing & commissioning of Control & Relay Panels including laying & terminating of LT power and control cables as required. The erection, testing and commissioning shall be complete with Numerical relays as per technical specifications and shall be integrated with existing SCADA/SAS.
For 132 kV Feeder Panel (Simplex Panels) as specified above ( Samaguri-1 set , Khaloigaon-1 set )
Erection, testing & commissioning of Current transformers including laying & terminating of control cables as required
CTR 800-400/1-1-1-1 A ( Feeder CT) ( Samaguri-3nos & Khaloigaon-3nos)
Erection, testing & commissioning of Voltage Transformers/CVT including laying control cables as required
132 kV CVT ( Salakati-3, Kokrajhar-6, Bilasipara -3)
Erection, testing & commissioning of Isolators including laying & terminating of LT power and control cables as required
132 kV With single Earth Switch ( Samaguri- 1 set, Khaloigaon-1 set)
132 kV With two Earth Switch( Samaguri- 1 set, Khaloigaon-1 set)
132 kV Without Earth Switch (Tandem Type) ( Khaloigaon-1 set)
Erection, testing & commissioning of Lightning Arrester
132 kV Lightning Arrester ( Samaguri - 3nos, Khaloigaon-3nos)
Erection, testing & commissioning of Post Insulator
132 kV Post insulator ( Samaguri - 6, Khaloigaon-8)
Erection of mounting structures as required for Circuit Breakers including construction of foundations and supply of all foundation materials.(as per Drg enclosed for bidding purpose)
132 kV Gang operated SF6 Breakers ( Samaguri-1, Khaloigaon-1 )
Erection of mounting structures as required for Current transformers including construction of foundations and supply of all foundation materials (as per Drg enclosed for bidding purpose)
132 kV CT ( Samaguri-3, Khaloigaon-3 )
Erection of mounting structures as required for Voltage transformers /CVT including construction of foundations and supply of all foundation materials.(as per Drg enclosed for bidding purpose)
132 kV CVT ( Samaguri-3, Khaloigaon-3 )
Erection of mounting structures as required for Isolators transformers including construction of foundations and supply of all foundation materials.(as per Drg enclosed for bidding purpose)
132 kV With 1 Earth Switch ( Samaguri-1, Khaloigaon-1)
132kV with 2 earth switch ( Samaguri-1, Khaloigaon-1)
132 kV Without Earth Switch (Tandem Type) ( Samaguri-1, Khaloigaon-1)
Erection of mounting structures as required for Lightning Arrester including construction of foundations and supply of all foundation materials.(as per Drg enclosed for bidding purpose)
132 kV Lightning Arrester ( Samaguri-3, Khaloigaon-3 )
Erection of mounting structures as required for Post Insulators including construction of foundations and supply of all foundation materials (as per enclosed Drg for bidding purpose)
132 kV Post insulator ( Samaguri-3, Khaloigaon-3 )
Construction of foundations for lattice steel Columns including supply of all foundation materials and labour for: ( as per drawing attached) ( Excluding Foundation Bolt)
Column Type ‘C1A’ ( Samaguri – 1)
Construction of foundations for lattice steel Columns including supply of all foundation materials and labour for: ( as per drawing attached) ( Excluding Foundation Bolt)
Column Type ‘C1A’ ( Samaguri – 1)
Erection of switchyard lattice Steel Beams:
Beam Type ‘B1’ ( Samaguri – 1,) (867.892Kg/Beam)
PLCC Equipment
Installation and commissioning of all equipment complete with erection of mounting structures, laying & terminations of all cables including construction of foundations & supply of foundation materials as required for following PLCC Links (excluding CVT). (Samaguri-Khaloigaon 2nd Ckt Link)
Hoisting of insulator strings, stringing of Conductors , jumpering of equipments CB, CT, CVT Isolator, LA including supply of clamps, connectors , etc. ( Samaguri-1job, Khaloigaon – 1job )
Installation of earthing system with GI flats, electrodes etc ( Samaguri-1job, Khaloigaon – 1job )
Earthwork in filling, levelling, compacting, grading etc as per site condition and technical Specification
Supply of earth for filling ( Samaguri-1500cum, Khaloigaon-1500cum)
Filling, levelling, compacting, grading etc as per site condition and technical Specification ( Salakati-500sqm, Kokrajhar -1000sqm, Bilasipara-500sqm)
Construction of Cable Trenches including supply of all materials and labour as per specification and drawing
Type B (1100 x 1050 mm) ( Samaguri-20m, Khaloigaon-20m,)
Type C (800 x 1350 mm) (Samaguri-25m, Khaloigaon-25m)
Type D (Sand filled) (Samaguri-35m, Khaloigaon-35m)
Integration of Control Relay Panel into the existing Substation Automation System (SAS)
Erection of Bay Marshalling Kiosk as per drawings and specifications including construction of foundation inclusive of supply of all foundation materials and labour.
T N T Projects Ltd
T N T Projects Ltd
T N T Projects Ltd
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .