| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.3 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹24.4 L+₹53,860 (2.26%)Rejected-Finance | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹27.0 L+₹3.1 L (13.0%)Rejected-Finance NEAR OLD CCS JUNGLIGHAT SRI VIJAYA PURAM 744 103 | SRI VIJAYA PURAM | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744103 | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹27.0 L+₹3.2 L (13.2%)Rejected-Finance | L4 | Rejected-Finance Not Lowest |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
24 Dec 2021, 6:00 pmClosed
GE Haddo
GARRISON ENGINEER HADDO Military Engineer Services Haddo Post Port Blair Andaman and Nicobar 744102
REPAIR/REPLACEMENT AND HYGIENE OF LT UG CABLE AT NAVAL AREA UNDER GE HADDO, PORT BLAIR
2021_MES_488477_1
8586-Rep-LT-cable
Open Tender
Civil Works
Item Rate
270 days
Haddo, Port Blair
Class E- b(I)
9 documents required · 9 mandatory
₹500
Garrison Engineer, Haddo
₹50,000
Yes
4 Jan 2022
16 Nov 2021
29 Dec 2021
16 Nov 2021
24 Dec 2021
29 Nov 2021
Amount
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 m in depth, for foundation of poles, stays, struts or for laying cables/pipes etc., not exceeding 10 Sqm on plan and not exceeding 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed. NOTE: 1. If new cable is laid as replacement of old cable in the same trench, all excavation and earth work shall be measured only once. 2. If any pipe is laid in trenches as cable protection, all excavation and earth work shall be measured either for cable or for pipe only and not for both. 3. If cable is laid in tiers and in loops, all excavation and earth work shall be measured accordingly.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm each as in soils complete all as specified and as directed.
Removing excavated material (soils) to a distance not exceeding 50 metres and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed.
M&L for LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade, cross sectional area 3½ core, 35 Sqmm laid in trenches/floors/ducts or fixed on poles/walls with suitable clamps/saddles or drawn through pipes etc., and connecting up with suitable size of lugs, glands and jointing material including taking out old unserviceable cable complete all as specified and as directed.
M&L for LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade, cross sectional area 3½ core, 50 Sqmm laid in trenches/floors/ducts or fixed on poles/walls with suitable clamps/saddles or drawn through pipes etc., and connecting up with suitable size of lugs, glands and jointing material including taking out old unserviceable cable complete all as specified and as directed.
M&L for LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade, cross sectional area 3½ core, 70 Sqmm laid in trenches/floors/ducts or fixed on poles/walls with suitable clamps/saddles or drawn through pipes etc., and connecting up with suitable size of lugs, glands and jointing material including taking out old unserviceable cable complete all as specified and as directed.
M&L for LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade, cross sectional area 3½ core, 95 Sqmm laid in trenches/floors/ducts or fixed on poles/walls with suitable clamps/saddles or drawn through pipes etc., and connecting up with suitable size of lugs, glands and jointing material including taking out old unserviceable cable complete all as specified and as directed.
M&L for LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade, cross sectional area 3½ core, 120 Sqmm laid in trenches/floors/ducts or fixed on poles/walls with suitable clamps/saddles or drawn through pipes etc., and connecting up with suitable size of lugs, glands and jointing material including taking out old unserviceable cable complete all as specified and as directed.
M&L for LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade, cross sectional area 3½ core, 300 Sqmm laid in trenches/floors/ducts or fixed on poles/walls with suitable clamps/saddles or drawn through pipes etc., and connecting up with suitable size of lugs, glands and jointing material including taking out old unserviceable cable complete all as specified and as directed.
M&L for LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade, cross sectional area 3½ core, 400 Sqmm laid in trenches/floors/ducts or fixed on poles/walls with suitable clamps/saddles or drawn through pipes etc., and connecting up with suitable size of lugs, glands and jointing material including taking out old unserviceable cable complete all as specified and as directed.
M&L for LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade, cross sectional area 3½ core, 500 Sqmm laid in trenches/floors/ducts or fixed on poles/walls with suitable clamps/saddles or drawn through pipes etc., and connecting up with suitable size of lugs, glands and jointing material including taking out old unserviceable cable complete all as specified and as directed. NOTE for all items of cable: 1. Cable test results like continuity test, megger test shall be submitted to Engr-in-charge before the cable is laid. 2. Necessary excavation and earth work shall be measured and paid separately under relevant items of this schedule.
M&L for HDPE DWC (Double wall corrugated) pipe of size 77mm (Outer diameter) x 63mm (Inner diameter) along with connected accessories like couplers, bends, end caps etc., laid in trenches/floors/ducts or fixed on poles/walls for as in protection of LT/ HT cable complete all as specified and as directed.
M&L for HDPE DWC (Double wall corrugated) pipe of size 120mm (Outer diameter) x 103.5mm (Inner diameter) along with connected accessories like couplers, bends, end caps etc., laid in trenches/floors/ducts or fixed on poles/walls for as in protection of LT/ HT cable complete all as specified and as directed.
Disconnecting old serviceable /under rated LT UG cables of size 3½ core, 50 to 185 Sqmm from its connections, taking out the cable from trenches or drawing out from the pipe and shifting the cable from existing location (power house) to different location (feeders/jetty/any other location) and re-using the same by laying in trenches / ducts or passing through pipes or fixed on walls / pole with suitable clamps/saddles and connecting up with suitable size of lugs, glands and jointing material complete all as specified and as directed. NOTE: Necessary excavation earth / lifting of RCC slabs work will be measured and paid separately under relevant items of this Schedule
Disconnecting old serviceable /under rated LT UG cables of size 3½ core, 185 to 500 Sqmm from its connections, taking out the cable from trenches or drawing out from the pipe and shifting the cable from existing location (power house) to different location (feeders/jetty/any other location) and re-using the same by laying in trenches / ducts or passing through pipes or fixed on walls / pole with suitable clamps/saddles and connecting up with suitable size of lugs, glands and jointing material complete all as specified and as directed. NOTE: Necessary excavation earth work / lifting of RCC slabs will be measured and paid separately under relevant items of this Schedule
M&L for removing carefully existing cables, earth strips/wires of any type from existing damaged cable trays with copper of any size, type and from any location etc., and supply and fix new hot dip galvanized iron perforated cable trays of size 250mm wide x 50mm high, made of 2 mm thick GI sheet, vertically/horizontally on walls/ buildings/ floors/ roofs etc., including fixing them with necessary fasteners / nuts and bolts, coupler plates and all connected accessories as per site requirement, replacing and securing the existing cables, earth strips/wires back in position on new cable trays complete all as specified and as directed.
M&L for removing carefully existing cables, earth strips/wires of any type from existing damaged cable trays with copper of any size, type and from any location etc., and supply and fix new hot dip galvanized iron perforated cable trays of size 100mm wide x 50mm high, made of 2 mm thick GI sheet, vertically/horizontally on walls/ buildings/ floors/ roofs etc., including fixing them with necessary fasteners / nuts and bolts, coupler plates and all connected accessories as per site requirement, replacing and securing the existing cables, earth strips/wires back in position on new cable trays complete all as specified and as directed.
Supply and fix in repairs, cover suitable for suspending cable trays vertically on walls/buildings and horizontally on floors/ roof tops/ ceiling, coupler plates necessary fastners/ nuts & bolts made of polypropolene sheet of 2.0mm thick,Size 250mm width and 50mm height complete and securing of existing cables on cable trays including necessary cable ties and making good the surfaces complete all as specifed and as directed.
Supply and fix in repairs, cover suitable for suspending cable trays vertically on walls/buildings and horizontally on floors/ roof tops/ ceiling, coupler plates necessary fastners/ nuts & bolts made of polypropolene sheet of 2.0mm thick, Size 100mm width and 50mm height complete and securing of existing cables on cable trays including necessary cable ties and making good the surfaces complete all as specifed and as directed.
M&L for mild steel framed brackets fabricated made out of angles or tees, web and flanges and in panel doors etc., cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc., conforming to Fe-290 Gde E-165 including fabrication, fixing and painting with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer including dismantling existing old unserviceable brackets and the like complete all as specified and as directed.
M&L for cable jointing kit for LT UG cable, 1100V grade, straight through, heat shrink type joint complete with jointing material and accessories suitable for 3½ core, 25 to 150 Sqmm XLPE armoured aluminium conductor cable including taking down existing unserviceable kit complete all as specified and as directed.
M&L for cable jointing kit for 1100V grade LT UG cable, 1100V grade, straight through, heat shrink type joint complete with jointing material and accessories suitable for 3½ core, 185 to 240 Sqmm XLPE armoured aluminium conductor cable including taking down existing unserviceable kit complete all as specified and as directed.
M&L for cable jointing kit for 1100V grade LT UG cable, 1100V grade, straight through, heat shrink type joint complete with jointing material and accessories suitable for 3½ core, 300 to 500 Sqmm XLPE armoured aluminium conductor cable including taking down existing unserviceable kit complete all as specified and as directed.
M&L for earthing complete with GI earth plate electrode of size 600mmx600mmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of the earth plate not less than 1.5m below normal ground level connected to 32x6mm GI earth strip as earth lead connected by means of bolts, nuts, washers and check nuts made out of galvanised iron or steel all as shown on electrical plate No. 3 of SSR Part-I connected to common earth dolly including testing on completion complete all as specified and directed. NOTES: 1) The unit rate shall also include for earth work in any type of soil, PCC (1:3:6) type C1 chamber, pre-cast RCC (1:2:4) type B-1 using 20mm graded stone aggregate cover 50mm thick reinforced with TMT bars 8mm dia @ 100mm c/c both ways, funnel with watering pipe 20mm dia medium grade, GI protection pipe light grade 40mm dia and wire mesh complete in addition to item No. 1(a) to (e) of preamble (notes) under sub-heading earthing, specified on Sl. Page Nos. 422 & 423 of SSR Part-II. 2) Earthing lead and GI protection pipe beyond 7.5m will be measured and paid separately.
S&F Galvanised iron strip 32x6mm buried in ground or fixed to walls/poles with necessary clamps, bolts and nuts including taking down old unserviceable strip complete all as specified and as directed.
Taking down/removal of old burnt/damaged LT cable end termination after isolating supply to transformer/LT pillar box/LT panel and disconnecting burnt/faulty cable from the bunch of cable gland, M&L for new termination with suitable size of lugs duly crimped for LT, 1100 volts, 3½ core 95 Sqmm to 500 Sqmm, armoured aluminium conductor cables and connecting back with new nuts, bolts and washers of nickel chromium and applying petroleum jelly after end termination, testing and commissioning complete all as specified and as directed.
Material and labour for lifting the RCC slab, approximate length (2 to 4.5m) x width (1 to 2m) and upto 300mm thick and about 3.0 to 5.0 ton in weight on IN Jetty as per site condition by cutting / chipping the clearance, groove all around, keeping aside using a crane for laying of LT/HT cables or removing and relaying after fault rectification including cleaning of cable duct and replacing RCC slab at the same location after carrying out repairs including making good the surface with pack 1:2:4 complete all as specified and directed. NOTE: Two to three Nos of slab shall be taken out/ removed as per site condition for laying of cables / earth strip in the cable duct of Jetty after for a span of 15 to 20 meters or as per site requirement.
M&L for 100mm dia or bore galvanised steel tubing, medium grade as in cable protection at road crossing by cutting existing road and making stone PCC or fixed on poles etc., including 1:3:6 type C1 (using 20mm graded stone aggregate) after laying of protection pipe as per site requirement taking out old rusted GI pipes complete all as specified and as directed.
M&L for mild steel chequered plates conforming to Fe-410-W (Gde-E-250) Quality 'A', of any thickness by cutting/ making into required shape, providing necessary angular supports and handles with 6 mm dia rod as per the site conditions by welding etc., including painting with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and laid over cable trenches of various substations including dismantling old unserviceable ones complete all as specified and as directed.
Taking out existing old unserviceable copper bus bar of any size or shape and S&F new copper bus bar of existing suitable size and capacity to suit the requirement with proper bakelite highlam sheet, insulators, GI bolts, nuts and washers of required size for mounting including reconnecting the electric cables complete all as specified and as directed.
S&F Indoor LT panel / LT pillar box of dimensions 2.5m x 1.4m x 0.6m size with following specifications. Fabrication Details : CPRI approved Main frame 3.15mm thick CRCA sheet, partition sheets / covers / doors of 3.15 mm thick CRCA sheet, gland plates 3.15 mm thick MS sheet (undrilled), all over body front and back cover with hinges and aldrops for locking arrangements 2 mm thick MS sheet for bus bar cover panel partitions and bottom cable entry covers duly painted with one coat of red oxide and two coats of synthetic enamel paint with control wiring to complete LT panel with 2.5 Sqmm FRLS copper cable and 6 A MCB's, meters, indication lamps, base frame on ICMS channel with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted with degree of protection IP-54 and locking arrangements including taking down old unserviceable LT panel complete all as specified and as directed.
Bus bar details: Material shall be aluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for phase 40x20mm aluminium flat, neutral 40x10mm aluminium flat and bus bar support of epoxy type. Painting Details : Pillar box shall be powder coated and painted with two coats of synthetic enamel spray paint over a coat of redoxide primer and marking of details of capacity/ rating/ incoming/ outgoing/ danger notice board in capital English alphabets with red colour radium sticker of required size. Accessories for Pillar Box: (i) 0-500V Digital voltmeter - 01 No (Flush type) (ii) 0-500A Digital Ammeter - 01 No (Flush type) and (iii) Indication Lamps (LED) RYB - Set of 03 Nos. MAKE: L&T / BINAY/ ELMEASURE
(iv) Incomer:- 400A, 4 pole, Change over switch -1 No. (v) Outgoing:- (a) 250A, 3 pole, MCCB, 36 KA -3 Nos. (b) 125-160A, 3 pole, MCCB, 30KA -5 Nos. (c) 100A, 3 pole, MCCB, 30 KA -2 Nos. (d) 63A, 3 pole, MCCB, 30 KA -4 Nos. NOTES: (i) All MCCBs are of adjustable overload 80 to 100% with thermal magnetic release Ics= 100% of Icu. (ii) The unit rate quoted is deemed to include the cost of MCCBs, Volt meter, Ammeter, Indication lamps, Changeover switch and connected wiring with necessary spreader links, lugs, glands and connecting of cables as per site conditions and complete all as specified and as directed. (iii) The unit rate quoted deemed to include for cost of breaking the existing PCC foundation, if any and making good the disturbed surfaces to match with existing surfaces. (iv) Drawings must be approved by Engineer-in-Charge before fabrication of LT Panel. (v) Make of MCCB's / Change over switch : L&T / Schneider / Siemens/ABB
S&F Out door LT panel / LT pillar box of dimensions 1.8m x 1.2m x 0.6m size with following specifications. Fabrication Details : CPRI approved Main frame 3.15mm thick CRCA sheet, partition sheets / covers / doors of 2.0mm thick CRCA sheet, gland plates 2.0mm thick MS sheet (undrilled), all over body front and back cover with hinges and aldrops for locking arrangements 2 mm thick MS sheet for bus bar cover panel partitions and bottom cable entry covers duly painted with one coat of red oxide and two coats of synthetic enamel paint with control wiring to complete LT panel with 2.5 Sqmm FRLS copper cable and 6 A MCB's, meters, breaker control supply and indication lamps, base frame on ICMS channel with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted with degree of protection IP-65 and locking arrangements including taking down old unserviceable LT panel complete all as specified and as directed.
Bus bar details: Material shall be aluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for phase 40x20mm aluminium flat, neutral 40x10mm aluminium flat and bus bar support of epoxy type. Painting Details : Pillar box shall be powder coated and painted with two coats of synthetic enamel spray paint over a coat of redoxide primer and marking of details of capacity/ rating/ incoming/ outgoing/ danger notice board in capital English alphabets with red colour radium sticker of required size. Accessories for Pillar Box: (i) 0-500V Digital voltmeter - 01 No (Flush type) (ii) 0-500A Digital Ammeter - 01 No (Flush type) and (iii) Indication Lamps (LED) RYB - Set of 03 Nos. MAKE: L&T / BINAY/ ELMEASURE
(iv) Incomer:- 400A, 4 pole, Change over switch - 1 No. (v) Outgoing:- (a) 250A, 3 pole, MCCB, 36 KA - 2 Nos. (b) 125A, 3 pole, MCCB, 30KA - 4 Nos. NOTES: (i) All MCCBs are of adjustable overload 70 to 100% with thermal magnetic release Ics= 100% of Icu. (ii) The unit rate quoted is deemed to include the cost of MCCBs, Volt meter, Ammeter, Indication lamps, Changeover switch and connected wiring with necessary spreader links, lugs, glands and connecting of cables as per site conditions and complete all as specified and as directed. (iii) The unit rate quoted deemed to include for cost of breaking the existing PCC foundation, if any and making good the disturbed surfaces to match with existing surfaces. (iv) Drawings must be approved by Engineer-in-Charge before fabrication of LT Panel. (v) Make of MCCB's / Change over switch : L&T / Schneider / Siemens/ABB
NOTE FOR ITEM NO. 01 to 32 (i) The Contractor has to visit the site before quoting the tender. (ii) The items in the BOQ will be operated as and when requirement basis.
NAVJEEVAN ENTERPRISES
SKV Engineering
SRI HARSHITA ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .