PROVN OF AUGUMENTATION OF EXTERNAL ELECTRIC SUPPLY AT MORAR CANTT UNDER GE GWALIOR
2022_MES_508542_1
CEBZ / GWL / TOKEN / 20 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
Gwalior
Please refer Tender documents.
4 documents required · 4 mandatory
₹2,000
Garrison Engineer Gwalior
₹4.6 L
Yes
2 Jun 2022
17 Feb 2022
6 Apr 2022
17 Feb 2022
4 Apr 2022
22 Mar 2022
Amount
Note: (i) Please refer schedule 'A' notes before quoting the tender. (ii) Amount of Schedule of credit shall be deducted off line by the department.
Dismantling existing PCC Poles/rail poles, struts, any size carefully for reuse including necessary excavation demolition of concrete transportation cost etc. and removing the old unserviceable rubbish etc, complete all as specified & directed.
Dismantling steel poles/ rail poles/ struts, any size transporting to out side the cantt area complete all as specified & directed.
Dismantling ACSR conductor of any size from existing overhead service feeder etc complete all as specified & directed.
Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside for re-use with in 50 mtrs complete all as specified & directed.
Dismantling of insulators any type any size for segrigation and re-use or dispose off as per site conditions complete all as specified & directed.
Dismantling unserviceable steel earth wire /craddle guard from existing overhead service feeder etc complete all as specified & directed.
Taking out old 33 KV and 11 KV PT from existing location carefully and refixing the same at new position , complete all as specified & directed.
Taking out old 33 KV and 11 KV CT from existing location carefully and refixing the same at new position , complete all as specified & directed.
Taking out un-serviceable faulty cable & service connection cable of any grade / type / class of sizes from 10 Sq mm to 50 Sq mm 2 core /3.5 core / 4 core for repair / replacement from pole / wall / cable duct under ground trench etc for re-use or removal from site of work , complete all as specified & directed. Note:- Excavation and earth work shall be measured and paid separately under respective item of this Schedule
Description all as per item No 10.00 above but of size ranging from 95 sqmm to 150 sqmm 3 core/3.5core /4 core LT/HT cable , complete all as specified & directed. Note:- Excavation and earth work shall be measured and paid separately
Taking out existing bricks from trenches of cables, cleaning and stacking at site serviceable bricks for re-use and removing unserviceable bricks from site of work , complete all as specified & directed. (Note:- Only serviceable bricks shall be measured for payment purposes).
Dismantling 11/33 KV HT switch gears/GOD/DO Fuse/LA and other accesoories, air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair/replacement of broken/worn out components and insulators etc. or carrying to MES store. (Note:- Spare/ components for replacement to be provided free by department)
Demolition of Concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level)
Supply installation, testing and commissioning of 11KV Package Sub-Station (PSS) / Compact Secondary Substation (CSS) consisting of following :
A. HT SWITCHGEAR : 11kV 630Amps 21KA/3 sec. Non-Extensible Ring Main Unit (RMU), Compact switchgear (DV) consisting of One No. Direct Module and One Fixed Manual Vacuum Circuit Breaker in SF6 insulated stainless steel enclosure with series trip, self powered microprocessor based numerical over current and earth fault relay protection. Interconnection between HT Switchgear and primary of transformer shall be done through 1C x 3 x 150 sq.mm aluminium unarmoured XLPE cable complete. Alfa neumaric Relay shall be of Ashida / ABB Model No: REJ603. -01 No
B. TRANSFORMER - 01 No 500KVA, Copper wound, 11KV/433V DYN-11, cast resin dry type transformer with Off load tap switch of range +5% to -5% insteps of 2.5% all standard fittings required for installation complete all as specified.
C. LVS PANEL:- 1000 Ampsaluminium bus bar- 01 No, LT Indoor panel 433V with Aluminium busbars of suitable rating, fabrication using 2mm thick CRCA sheet steel enclosure, with Ingress protection IP4X , complete including internal wiring using copper flexibles or conductor consisting of following :- (i) INCOMER-1 FROM TRANSFORMER a. 630Amps 433V 50KA 4P Fixed Manual draw out type Air Circuit Breaker with microprocessor based release -01 No b.Current Transformer ,CTR :1250/5 Amps , Accuracy Class :0.5 , Burden :5VA - 03 Nos c. Multifunction Meter Accuracy Class1.0 - 01 No d. Indication Lamp (LED Type) - 03 Nos (ii) OUTGOING FEEDER (a) MCCB, FP, 200 Amp, 25 KA - 04 Nos (b) MCCB, FP, 100 Amp, 16 KA - 04 No Note:- All MCCBs shall be adjustable thermal and magnatic release. Ics = 100% Icu. The unit rate shall be deemed to be included the cost of PCC foundation as per OEM recommendation.
D. Outdoor Enclosure with Slant roof 1 set:- Outdoor type enclosure having modular construction of Galvanised Sheet Steel should be built with Clinching technology (nut-bolt free) and minimum thickness of 1.5mm. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP23 degree of protection for Transformer compartment. The enclosure exterior shall be painted with polyurathene paint ( colour Light Gray & D.A.Gray). Each compartment will be provided with the door and pad locking arrangement. The Compartment illumination lamp with door operated switch shall be provided for each compartment.
E. Interconnection & Earthing 1 set:- Interconnection Between HT switchgear & Transformer using 1Cx3x150 Sq.mm XLPE Single core cable & Interconnection between Transformer & LT switchgear using AL. Busbars. Internal earthing connections by using 50 x 6mm GI strips. Note:- The item rate also incl the plinth as per OEM recommendation.
Supply, installation, testing & Commisioning in replacement of 11KV, 20KA, 400A Outdoor SF6 Circuit breaker with support structure consisting of following:- Over voltage & under voltage trip relay, 30 Volt- DC Voltage, Circuit Breaker type -Univac IS 13118-1991/ IEC56-1987.Breaking Capacity 25kA, Current 400A, Making Capacity 62.5kA pk, Frequency - 50 Hz.,Short time current -25 kA for 1 Sec.No. of pole - 3 Nos.DC Component - 50%, BIL - 70/170 kvp Operating coil - 30 VDC Aux Switch - 8 No + 8 NC, Counters complete with incoming and out going connections aluminium jumpering with lugs nut bolts washer foundation as per company specification , complete all as specified & directed.
Supply, installation,testing & Commisioning of indoor type control panel for 11 KV VCB SF6 Type, consisting of numerical O/C and E/F Relay, IDMT, 3O/C+ 1E/F,with High set (Make:C&S/ Avana), Master Trip relay, Multifuntion Meter Size 96X96mm, Accu. Class 0.5 (Make:Rishab), Master 3440 (Make:Rishabh) , Over voltage & under voltage trip relay, DC voltage - 30 Volt, zonewise auto repeat closing facility, LED Indicating lamps (07 Nos), Push Button switches (05 Nos), 12 window annunciator Breaker Control Switch, 25 Amps, Pistol grip Handle,3 Position,Trip-Neutral- Close, Spring Return, Return to neutral, 2 N.O. contacts for Trip and 2N.O. contacts, Copper Earthing Bus Bar, Size 25X6X250mm Standard 01, Auxiliary Relay for Alarm Circuit Leone, HK, Er 09, Piezo electric Buzzer for Alarm, DC and AC Master 02, HRC Fuses for Control ckt. protection, Panel illumination lamp of 40Watts , Socket 230V, 6 Amps with Switch and Fuse Anchor 01, Cabinet made of 2mm thick sheet,Size : H-1475, W-600, D-300 mm, Powder Coated, Wiring by PVC flexible Copper wire & suitable lugs,Ferrules, PVC Channels , complete all as specified & directed.
Supply and installation in replacement of 11 KV, single phase, out door oil cooled CT of ratio 400/5-5 Amp, class 1/0/5P10, burden 15 VA complete all as specifid and directed.
Supply and installation in replacement of 11 KV, single phase, out door oil cooled PT of ratio 11 KVrt3/110 V/rt3, Class 0.5-3, Burden 50 VA-50 VA complete all as specifid and directed..
Supply, installation,commisining and testing in replacement 33KV, 25KA, 400 Amps outdoor SF6 breaker with support structure consisting circuit Breaker type -36PV25A (Old Rating to IS 13118-1991/ IEC56-1987), Breaking Capacity 25kA, Current 1250A, Making Capacity 67kA pk, Frequency - 50 Hz., Short time current -25kA for 1 Sec. No. of pole - 3 Nos. DC Component - 50%, BIL - 70/170 kvp Operating coil -30 VDC Aux Switch - 8 No + 8 NC complete with incoming and out going connections aluminium jumpering with lugs nut bolts washer foundation as per manufacturers standards complete all as specified & directed.
Supply, installation, testing & commisioning indoor type control panel for 33 KV VCB SF6 Type,consisting of Numerical O/C and E/F Relay, IDMT, 3O/C+ 1E/F,with High set , Master Trip relay , Transformer Protection Relays Salzer(03 Nos), Multifuntion Meter Size 96X96mm, Accu. Class 0.5, Rish Master 3440 (Make:Rishabh), Over voltage & under voltage trip relay, DC voltage - 30 Volt, zonewise auto repeat closing facility , LED Indicating lamps (7 Nos), Push Button switches (05 Nos), 12 window annunciator Breaker Control Switch, 25 Amps, Pistol grip Handle, 3 Position,Trip-Neutral- Close, Spring Return, Return to neutral (02 Nos) contacts for Trip and 2 No. contacts, Copper Earthing, Bus Bar of size 25X6X250mm Standard , Auxiliary Relay for Alarm Circuit Leone, HK, Er 09, Piezo electric Buzzer for Alarm, DC and AC Master 02, HRC Fuses for Control ckt. protection , Panel illumination lamp 40Watt, Socket 230V, 6 Amps with Switch and Fuse 01, Cabinet made of 2mm thick sheet steel enclosure of size : H-1475, W-600, D-300 mm approx,duly powder coated, including wiring using PVC flexible copper wire & lugs, Ferrules, PVC Channels etc complete all as specified & directed.
M&L for automation of existing HT capacitor bank by dismantling the existing bank and re-assemble in two seperate set or circuits with individual ciruit wise control according to the system power factor through PLC control system ,complete all as specified & directed , comprising of following :-
(a) Supply, installation, testing and commissioning SMART PLC based automatic HT Breaker controlling panel for Power Factor Correction with accessoires i.e Rittal panel enclosure, simens SMART PLC with 4" HMI, Schneider PM8000 Energy Meter, APC Backups Pro 1500 VA, SMPS 24V DC-8.5 Amp, Electronic Hooter, Circuit protection relay, Control wiring, Control MCB, Auto/Manual Switch, Indicators, Cooling Fan with Filters incl all type of control cable and connection with CT & PT ,complete all as specified & directed.
(b) Supply, installation, testing and commissioning of 11 KV outdoor type VCB, nominal current rating 800A, 50 Hz frequency, breaking capacity 25 KA, making capacity 62.5 KA peak, 1.2/50 micro second full wave impulse -75 KV peak, rating of the circuit breaker for capacitor switching - 400 A, total creepage distance-450mm, No of poles circuit breaker-03, Number of breakes per phase-1, Number of spare auxiliary contacts provided-04, Spring wound stored energy mechanism, Control circuit voltage- 24 V/110V/220V/30 V DC, Voltage of spring charging motor- 230 V AC, Time required for motor tocharge the spring fully-15 Sec (Max) all as per manufacturers standards. NOTE:- Metal structure for setting capacitors in banks shall be measured and paid under relevent item of this Schedule.
Supply and installation in replacement of 33 KV, single phase, out door oil cooled CT of ratio 400/5-5 Amp, class 1/0/5P10, burden 15 VA ,complete all as specified & directed.
Supply and installation in replacement of 33 KV, single phase, out door oil cooled PT of ratio 11 KVrt3/110 V/rt3, Class 0.5-3, Burden 50 VA ,complete all as specified & directed.
Design, manufacture, supply, installation, testing & commissioning of indoor type Ring Main Unit (RMU) panel, SF6 gas insulated, manual operated, 11 KV, 3 phase, 3 wire, AC, 50 Hz, 3-way extensible on both sides for future addition, comprising of 02 Nos Load Break Switches (LBS) for outgoing and incoming supply 01 No. Vacuum Circuit Breaker (VCB) for transformer feeder, free standing foundation mounting with cable trench beneath for bottom cable entry, made out of 2mm thick CRCA sheet for outer enclosure with IP 54 degree of protection duly powder coated with 7 tank process of approved shade and 2.5mm thick stainless steel main tank gas vessel with IP 67 for HV part including necessary internal copper connections, small wiring, AC / DC control wiring, HT/LT fuses etc complete with the following detailed specifications and provisions confirming to relevant latest IS / IEC standards:- (Description if item Continued on Ser item No 25.01 to 25.30)
(A) Main Busbar:- Three phase electrolytic grade tinned copper busbar of size 30mm x 10mm (WXT) for each phase suitable for 630A for continuous rating and short time withstand current of 21 KA for 3 Sec.
(B) Earth Busbar:- Copper busbar of size 30mm x 3mm (WXT) throughout the bottom of the panel extended both sides of the panel.
(a) Operating mechanism for switch disconnector ON-OFF: Manual operated
(b) Operating mechanism for earth switch OFF - EARTH : Manual operated
(c) Mechanical mimic indications showing ON-OFF-EARTH
(e) Fixed type Capacitive Voltage Indicator (CVI)
(f) Padlocking facility
(g) Cable cover standard with interlocking
(h) Provision for connecting 1 x 95 sqmm, 3 core XLPE cable with 01 set of right angled cable boots.
The rated operating sequence shall be O-3min-CO-3 min-CO. Each and every VCB should be provided with the following:-
(a) Operating mechanism of VCB with position ON-OFF ; Manual operated
(b) Operating mechanism for earth switch OFF-EARTH : Manual operated
(c) Fixed type Capacitive Voltage Indicator(CVI)
(d) 03 Nos Single phase, ring type, epoxy resin cast Current Transformer (CT) of ratio 60-30/1+1A, of burden 2.5 VA, accuracy class 5P10 for protection
(e) Self Powered Relay, Triple Pole Combined Over Current and Earth Fault Numerical Non-Directional IDMT with three over current and one earth fault protections.
(f) Push buttons for On & FF
(g) Padlocking facility
(h) Cable cover standard with interlocking
(j) Provision for connecting 1 x 95 sqmm, 3 core XLPE cable with 01 set of right angled cable boots.
(E) Common Accessories:- The following common accessories shall be provided for the RMU Panel:-
(a) 01 No Manometer without contacts for SF6 gas low indication with marked Green Zone for GO, Red marked zone for NO GO.
(b) 01 No Operating Handle
(c) Rating plate and manufacturer's name plate
(d) 11 KV Danger Notice Plate
(e) Do's and Don'ts sticker
(f) Phase identification stickers at bushing.
Note :- The Contractor shall submit set of all drawings of the VCB Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
M&L, Steel tublar swaged poles, complete with cast iron base plate, finials taper plug , bolts, nuts & screws as specified type 410 SP-55 (11.00 mtr long). Note:- Earth work and PCC shall be measured & paid separately under respective items .
M&L, Steel tublar swaged poles, complete with cast iron base plate, finials taper plug , bolts, nuts & screws as specified type 410 SP-31 (9 mtr long). Note:- Earth work and PCC shall be measured & paid separately under respective items .
M&L for fixing of ACSR conductor on existing or new poles all as directed. Note:- Stringing of ACSR shall be carried out by winch machine.
M&L for fixing of AAC (All Aluminium conductor) conductor on existing or new poles all as directed.
Supply and fix load break switch disconnector, out door type, center post rotation, manually operated double brake 11 KV, 400 Amp capacity horizontal isolator as per the specification IS 9921 (Part 1-4). All isolators shall be of center post rotation, double brake, horizontal isolation type and shall have a short time rating of 12.5KA for 3 seconds. The contacts and blades of the isolators shall be of electrolytic grade copper. The fasteners (nut-bolts) used for current carrying parts shall be of non magnetic stainless steel. Spacing between phases for all isolators shall be of 1000mm. Further the current density for copper current carrying parts shall not be more than 1.6 Amp./ sq mm. in solid conductor and 2 Amp/sq.mm. in hollow tubes. The current density for Aluminium current carrying parts shall not be more than 1 Amp./ sq.mm. Isolators with integral earthing facility shall have built-in mechanical inter lock between the main and earth blades so that the closing of the main blade is not possible without opening (Description if item Continued on Ser item No 30.01 to 30.03)
the earth blade and closing of the earth blade will not be possible without opening the main blade. Flexible branded copper connections shall be provided between rotating earth blades and the frame which shall have a cross section of at least 50 sq mm and shall be tinned or suitably treated against oxidation. The frame of each disconnect and earthing switch shall be provided with two reliable earthing terminals for connection to the purchaser's earthing conductor/flat so also clamping screw suitable for carrying specified short time current. Flexible ground connectors shall be provided for connecting operating handle to the earthing flat. The diameter of clamping screw shall be atleast 12 mm. The connecting point shall be marked with earth symbol. All the fixed contacts shall be provided with a sheet metal rain hood. This rain hood shall be fabricated out of at least 2 mm thick Galvanized iron sheet metal and shall be designed such that it will in no case shall obstruct or restrict the movement of moving
contracts (blades) and arcing horns. The isolator shall also comply the following specifications. Down pipe: 50 mm ID class B Mild steel galvanized single piece pipe shall be provided for operating disconnects. The pipe shall be terminated into a suitable swivel type joint between the tandem pipe driving mechanism and the operating mechanism if required to take care of marginal angular misalignment at site.
Insulators : All outdoor type Porcelain insulators shall have a creepage distance of 25mm/kV (i.e. 300mm). The insulators shall be of outdoor post type conforming to IS 2544. All insulators shall have a rated voltage not less than 12 kV and rated current of 2000 Amps. Post type insulators with 57 mm PCD shall only be provided. Pin type or Polycone insulator shall not be acceptable. The insulator shall be made of homogeneous and vitreous porcelain of high mechanical and dielectric strength. It shall have sufficient mechanical strength to sustain electrical and mechanical loading on account of wind load, short circuit stresses etc. Glazing of the porcelain shall be of uniform brown or dark brown colour with a smooth surface arranged to shed away rain water. The porcelain shall be free from lamination and other flaws or imperfections that might affect the mechanical or dielectrical quality. It shall be thoroughly vitrified, tough and impervious to moisture.
Supply and fix load break switch disconnector Outdoor type 33KV, current charring capacity 2000A/1250A, Horizontal Centre Break Isolator comprises three identical triple pole units which consists of galvanized rigid base made of distortion resistant structural steel having fixing arrangement with the supporting structure and also having two rotating bearing unit on both sides each base with interconnecting pipe fixing clamps for tandem and link pipe (disconnector switch specification shall conform to latest edition IEC- 62271-102). Porcelain insulators made of composite stacks of rated capacity carrying male & female contact assembly are fixed on the rotating bearing unit of base of each pole. Two units of each pole interconnected by link pipes & finally, all three pole are connected to group operating pipe. Movement of group operating pipe for closing & opening operation of isolator is done by Down pipe connected to the operating mechanism (Motor). (Description if item Continued on Ser item No 31.01 to 31.07)
Thus, all three poles of the Isolator shall be mechanically gang operated by a common operating mechanism to ensure that operations of all three poles are simultaneous. The operating mechanism box shall be made out of aluminum extruded (Aluminum alloy) sections of minimum 3.0 mm thickness. The operating mechanism shall be strong rigid and not subject to rebound. All isolators and earthing switches shall be provided with 220V DC auxiliary switches for their remote position indication on the control board and for electrical locking with other equipment. The auxiliary switch shall be provided with a minimum of ten auxiliary contacts-10 normally open and 10 normally closed and 10 normally open and 10 normally closed for earth switch. Separate auxiliary switches shall be provided for isolating and earth switches. Earth switches shall also comply with the requirements of IEC-62271-102, in respect of induced current switching duty as defined for Class-B and short circuit making capability class E-0 for earthing switches. 6 additional NO and NC contact to be provided as spare in each case.
Double Earth Switch should be provided i.e one on Male side & another on Female side. On each side, E/S of all three poles are mechanically ganged with one common motor operating mechanism. The Isolator should also comply the following specifications of the separate spairs.
(i) Control Cabinet: The control cabinet of the operating mechanism shall be made out of minimum 3mm thick aluminium alloy sheet. Hinged door shall be provided with pad locking arrangement. Flexible earthing strips to be provided for moving shaft connecting to the isolator with cabinet body as well as the hinged door with main body. Sloping rain hood shall be provided to cover all sides. 15 mm thick neoprene or better type of gaskets shall be provided to ensure degree of protections of at least IP 55 as per IS 2147/IS-3947. The cabinet shall be suitable for mounting on support structure with adjustment for vertical, horizontal and longitudinal alignment. Details of these arrangements shall be furnished along with the offer.
(ii) Motor : Motors rated 1 Kw and above shall be suitable for operation on 3 phase, 415 V, 50 HZ supply. Motors of lower rating shall be single phase type suitable for 240V, 50HZ system. It shall be totally enclosed type if mounted outside the control cabinet. The motor shall withstand without damage stalled torque for atleast 3 times the time lag of tripping device. The motor shall, in all other respects, conform to the requirement of I.S. 325.
(iv) Space heaters : Space heaters suitable for 1 phase 240V AC supply shall be provided for each motor operated operating mechanism to prevent condensation and shall be operated by MCB. (v) Terminal block and Wirings – Each operating mechanism shall be provided with 1100V grade stud type terminal block. All auxiliary switches, interlocks and other terminals shall be wired upto terminal block. The terminal block shall have at least 20% extra terminals. All wiring shall be carried out with 1.1KV grade insulated 2.5 sq mm copper wires. (vi) Interior Illumination : A holder suitable for a 240 V lamp shall be provided in each of the motor operated mechanism of three poles & shall be door operated type.
(vii) Control and auxiliary supply – A 3 phase switch with MCB for phases and link for neutral, shall be provided for power supply and a 2 pole MCB shall be provided for control supply. (viii) Position indicator : A position indicator to show the isolator is in ON or OFF position to be provided.
M & L for switch air break gang operated triple pole out door type with drop out switch fuse unit on HT 11 KV 50 cycle AC suitable for current rating upto 200 Amps mechanically operated mounted on insulators (12 Nos epoxy insulators) and frame with operating mechanism worked from ground level with earth switch and including locking arrangement complete all as directed.
Supply & Fix HT SFU of 11 KV LBSF panel outdoor complete of capacity 630 Amps having load break switch, 200 Amps with D.O set, Earth switch,PVC sleeved copper bus- bar for Incoming, Door Interlocking mechanism, Tripping mechanism, Epoxy insulator for bus supports, H. V. cable box to be provided for end termination at incoming side, End plate be provided at outgoing side for end termination etc complete all as specified & directed..
M & L for lightening arresters expulsion type 11 KV grade complete with all fittings, transmission class, discharge capacity 65 Kilo Amps complete all as specified and as directed.
M & L for lightening arresters expulsion type 33 KV grade complete with all fittings, transmission class, discharge capacity 65 Kilo Amps complete all as specified and as directed.
M & L for cross arms, bracing, supports, clamps and back plated fabricated from structural steel sections including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape or size as directed inclusive of 2 coats of aluminium paint over a coat of red oxide primer after dismantling old unserviceable cross arms complete all as specified and as directed.
S&F disc type Insulator (single disc assembly) porcelain vitreous, white brown or green 145 mm height and 255 mm dia ball and socket type with tension clamp galvanized iron nut for conductors working pressure 11000 volt grade complete all as specified and as directed.
S&F Epoxy (polymer) pin / post insulators, vitreous, white brown or green 150mm height and 150mm dia including one galvanized mild steel spindle, two galvanized washers and one galvanized iron nut for conductor working pressure 11000 volt grade complete all as specified and as directed.
̶Description all as per Ser item No 38.00 above but for 33 KV, 133 mm height and 125 mm dia, Section of straps in 38x5 mm, Dia of bolts 20 mm complete all as specified and as directed.
Refixing only disc type Insulator retrived from dismentaled item (single disc assembly) porcelain vitreous, white brown or green 145 mm height and 255 mm dia complete all as specified & directed.
Refixing only Insulator pin type porcelain vitreous, white brown or green retrived from dismentaled item 150mm height and 150mm dia including one galvanized mild steel spindle, two galvanized washers and one galvanized iron nut for conductor working pressure 11000 volt grade complete all as specified & directed.
̶Description all as per Ser item No 41.00 above but for 33 KV, 133 mm height and 125 mm dia, Section of straps in 38x5 mm, Dia of bolts 20 mm complete all as specified & directed.
M&L for loop type insulator, vitreous porcelain white ,brown or green large size over all dimension 90 X 140mm, clearance of the hole 25.5mm for stay assembly complete all as specified and directed.
Refixing only for loop type insulator, vitreous porcelain white , brown or green large size over all dimension 90 X 140mm, retrived from dismentaled item complete all as specified & directed.
M&L for stay assembly 16 mm dia rod complete with accessories as shown in electrical plate No 1 (Loop type insulator, stay clamps, excavation and concrete measured separately) all as directed.
M&L for galvanised steel wire 3.15 or 4mm dia stranded 7/1.6mm complete all as specified & directed.
M & L for galvanized steel wire with 4 mm dia as in cradle guard complete all as specified and as directed.
M&L for earthing complete with copper earth plate electrode size 60cmx60cmx3.15mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including copper strip 20X3 mm earth lead by means of bolts, nuts, check nuts and washers of galvanized steel including GI pipe light grade of size of 40 mm dia for protection and GI pipe light grade 20mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including testing on completion for power house or Sub-station ,complete allas specified & directed in MES SSR pt -I , 2009. NOTE:- The unit rate includes for protection pipe and copper earth strip 20 x 3mm dia from top of earth plate up to 7.5 meter above ground level.
M&L for earthing complete with galvanized steel earth plate electrode size 600x600x6.3mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanized iron strip 32X6 mm earth lead by means of bolts, nuts, check nuts and washers of galvanized steel including GI pipe light grade of size of 40 mm dia for protection and GI pipe light grade 20mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including testing on completion ,complete allas specified & directed in MES SSR pt -I , 2009. NOTE:-The unit rate includes for protection pipe and GI earth strip 32 x 6mm dia from top of earth plate up to 7.5 meter above ground level.
M&L for earthing complete with galvanized steel earth plate electrode size 600x600x6.3mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanized earth lead 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanized including GI protection pipe light grade 15mm dia connected to main earth wire on pole or control board and GI pipe light grade 20mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including testing on completion ,complete allas specified & directed in MES SSR pt -I , 2009. NOTE:- The unit rate includes for protection pipe and GI earth wire 4.00mm dia from top of earth plate up to 7.5 meter above ground level.
M&L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit /pipe or fixed to poles or any other indicated but 25x3mm copper strip complete all as specified and as directed.
Description all as per Ser item No 51.00 above but using GI strip of size 32 x 6mm complete all as specified and as directed..
Description all as per Ser item No 51.00 above but using copper strip of size 32 x 6mm complete all as specified and as directed.
M&L Chemical earthing with copper earth plate 90x60cmx5mm & copper earth strip size 32 x 6mm complete.
Supply, laying & testing HT U/G cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminiium conductor, 11000 volts grade cross sectional area 95 Sqmm 3.0 Core earthed complete all as specified and as directed.
Supply, laying, jointing and testing, XLPE insulated, armoured,heavy duty, electric LT UG cable with multi stranded aluminium conductor, 1100 Volts grade, of size 3.5 core 150 Sqmm complete all as specified and as directed .
Description all as per Ser item No 56.00 above but 120 Sqmm 3.5 core.
Description all as per Ser item No 56.00 above but 95 Sqmm 3.5 core.
Description all as per Ser item No 56.00 above but 50 Sqmm 3.5 core.
Description all as per Ser item No 56.00 above but 35 Sqmm 3.5 core.
Description all as per Ser item No 56.00 above but but 25 Sqmm 4 core.
Description all as per Ser item No 56.00 above but 16 Sqmm 4 core.
S&F, Cable joining kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint complete with joining material and accessories suitable for 3 Core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm ,complete all as specified and as directed.
S&F, Cable joining kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm , complete all as specified and as directed.
Dismantling Power transformer 5.0 MVA capacity from existing postion by shutting down, terminating & removing the HT connections,incl opening of nuts , bolts & washers and then taking up the safe shifting of transformer using suitable capacity Crane by lifting form existing postion and transporting to new location within the 33/11KV MRS Yard premises not exceeding distance of 20mtr and installing on plinth complete as specified and directed by Eng-in-Charge including re-erection and commissioning at site complete. NOTE:- 1. Cost of any other tools & plants required to carryout above job including MS channels, nuts bolts or washers is deemed to be included in the quoted rate. 2. PCC plinth shall be measrured & paid seperately under appropriate item under this Schedule.
Dismantling Power transformer 1.6 MVA capacity from existing postion by shutting down, terminating & removing the HT connections,incl opening of nuts , bolts & washers and then taking up the safe shifting of transformer using suitable capacity Crane by lifting form existing postion and transporting to new location within the 33/11KV MRS Yard premises not exceeding distance of 20mtr and installing on plinth complete as specified and directed including re- erection and commissioning at site ,complete all as specified and as directed. NOTE:- 1.Cost of any other tools & plants required to carryout above job including MS channels, nuts bolts or washers is deemed to be included in the quoted rate of the contractor. 2. PCC plinth shall be measrured & paid seperately under respective item of this Schedule.
Description all as per Ser item No 60.00 above but for VCB 33 kV ,complete all as specified and as directed.
Description all as per Ser item No 60.00 above but for VCB 11 kV ,complete all as specified and as directed.
M&L spray of agricultural based chemical inside the installation to control the growth of unwanted herb etc incl cleaning of the grass herbs bushes etc from the installation ,complete all as specified and as directed.
Pruning of tree branches and stacking of serviceable material and disposal of unserviceable material to a distance of exc 50 m and clearing site ,complete all as specified and as directed.
Restringing and stretching of existing sagged LT/HT ACSR conductor of any size on OH electric line of any length on existing poles after disconnection of binding wires (dismantling & taking down) service connection etc and making, binding and service connection ,complete all as specified and as directed.
M&L for boring of holes under road, pavment, hard standing by trenches technology using ultra sound technique jig machine at the depth of 5 mtr below ground level complete all as specified and as direct.
S&F HDPE pipe PE 80 PN 10 of 150mm dia confirming IS-14930 part-I & II through jig machine for conduiting HT cable at the depth of 5 mtr below ground level ,complete all as specified and as directed.
M&L for wrapping 3 band of radium strips of 45mm width of approved colour each (made of HIP retro reflective radium sheet) all around HT Steel tubular pole ( height from foundation as approved ) ,complete all as specified and as directed.
Fixing only 32x6mm galvanised iron strip retrived from dismantaled material ,complete all as specified and as directed.
Supply and laying in replacement 8.0 core 2.5 sqmm 650/1100 volt grade solid copper conductor, XLPE insulated control cable for VCB/CT/PT ,complete all as specified and as directed.
Supply and laying in replacement 4.0 core 2.5 sqmm 650/1100 volt grade solid copper conductor, XLPE insulated control cable for VCB/CT/PT ,complete all as specified and as directed.
Supply and laying in replacement 2.0 core 2.5 sqmm 650/1100 volt grade solid copper conductor, XLPE insulated control cable for VCB/CT/PT ,complete all as specified and as directed.
M&L Marshling Box With 15 terminal for connection of control cable ,complete all as specified and as directed, having following specification (Consisting Ser Item No 73.01 & 73.02):-:
(a) All doors, covers and plates shall be provided with neoprene gaskets provided with removable bolted and undrilled gland plate etc. The required number of knock-out punches shall be provided for outgoing control cables. PVC cable gland of appropriate size shall be provided for each cable entry & exit.
(b) All contacts for alarm, trip and indication circuits shall be electrically potential free, wired for auxilliary supply as specified and brought out to separat terminals at termianal blocks in the marshalling box. If required, separate MCBs shall be provided for protection isolation and distribution of AC and DC control supplies in the marshalling box. Wiring shall be with PTEF insulating (Insulation for wire & cable shall be in consitence with the ambient temperature in the housing), The wiring conductor shall be stranded copper and sizes not less than 4 Sqmm for CT circuit and 2.5 Sqmm for other control circuits. CT terminals shall be provided with standard shorting facility. The wires shall be drawn through neatly clamped conduits. Engraved identification ferrules, marked as per the approved wiring diagrams shall be provided on each wire. Ferrules shall be of yellow colour with black lettering. Preferable the terminals shall be stud type and provided with crimping type cable sockets.
S&F epoxy insulator for earthing strip of size 25 x 3 mm, flame retadrant with breaking current capacity min 5 KA ,complete all as specified and as directed.
Supply and fixing disc type insulator porcelain, vitreous, brown with ball socket and tensioning clamps 2U type for 33 KV complete all as specified and directed.
Earth work in excavation by mechanical means (Hydraulic excavator)/ in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m ,complete all as specified and as directed. Note : (a). Tracing of underground live cable, telephone cable and water pipe line throughout the excavation route before excavation by electronic cable/pipe route tracer. The rate of tracing shall be included in quoted rate under item No 76. (b). Any damage in terms of any pipe line and any cable (electric/signal) shall be repaired in proper cable jointing kit/new pipe with accessories by the Contractor at his own cost all as directed by Engr-in-Charge. (c). The rectification of the breakdown shall be rectified in emergent basis not more than 48 hours from the break down as per direction of the Engr-in-Charge. (d). In case of failure to above rectification penalty @ the rate of Rs. 5000.00 per day will be recovered from the Contractor and paid to other agencies for rectification of the damage.
Excavation in trenches not exceeding 1.5m wide and not exc. 1.5m depth and getting out in hard / dense soil , complete all as specified and as directed.
Excavation in trenches n exc. 1.5 m wide and exc 1.5m deep and n.exc 3.0 m deep for foundation beyond the first 1.5 m ,etc. or for shafts, wells cesspits, manholes, pier holes, etc. n exc.10 sq m on plan and getting out in soft/loose soil , complete all as specified and as directed.
M&L for sand cushioning in trenches for cable protection including consolidation , complete all as specified and as directed.
M&L for laying un-reinforced precast concrete cable cover factory made, class HVP, Type 1 of size 300mm x 180mm x 40mm, complete all as specified and as directed.
M&L for laying un-reinforced precast concrete cable cover factory made, class LV, Type 1, flat size 250mm x 150mm x 40mm, complete all as specified and as directed.
Returning, filling, including spreading, leveling, watering and well ramming in layers not exc. 25 cm in soft/loose soil complete all as specified and as directed.
M&L for PCC 1:3:6 type C-2 using 40 mm graded stone aggregate as in foundation filling and mass concrete , complete all as specified and as directed.
M&L for PCC 1:4:8 type D-2 using 12.5 mm graded BT stone aggregate as in bed block for hold fast or coping including necessary form work , complete all as specified and as directed.
M&L for danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size, for HT of size 25x20cm size complete , complete all as specified and as directed.
M&L for HT cable route indicator precast made from PCC 1:3:6 of size 600mm x 230mm x 100 including excavation PCC for foundation and painting and writing as "HT 11 KV cable" incl preparation of surfaces of both sides , complete all as specified and as directed.
Supply, installaion, commissioning and testing of Mobi Charge-30V (An Emergency 30 V, 20 A DC Power Bank) for back up of VCB and continuous DC Power Supply with Battery Charger comprising of following (Consisting Ser Item No 88.01 & 88.02):-
Interface (HMI) 3.5” Touch Panel Liquid Crystal Display Digital Voltmeter for Output, 0-50V DC Resolution – 16 mV Metering (Displayed on 3.5” LCD) Digital Ammeter for Output DC Current, 0-20A Resolution – 12 mA Digital Ammeter Battery Charging Current, 0-15A Resolution – 12 mA Alarm Annunciation (Displayed on 3.5” LCD) Annunciation will be followed by an inbuilt buzzer. The same can be silenced an Accept button on the LCD. Battery under Voltage Alarm Annunciation Output over Current Alarm Annunciation External DC Reverse Polarity Alarm Annunciation Input AC-ON/OFF Indication (Displayed on 3.5” LCD) Output DC- ON/OFF Battery Charging status & State of Charge Indication Field Programming Parameters (Programmable via 3.5”) Output over current Trip/Alarm (2 to 15A & 1 to 14 A), Date & time (Description of the item continued on Ser item No 87.02)
(Description continued from Ser item No 87.01) Battery Lithium Ion Battery, 30V 10Ah with inbuilt BMS Charger Specifications SMPS Based CC/CV Charger Input Voltage Range 180-264V AC/ 254-370V DC Input Frequency Range 47-63Hz Efficiency AC Input Current =>85% 1.7 A Typical Output DC Voltage 34 V DC Rated Current 10.0A Max Rated Output Power 349.2W Max AC Input Current 1.7 A Typical Inbuilt Protections Over Current, Over Voltage & Short Circuit Protection Total Weight 12 Kg Approx. Physical Dimensions 225 x 280 x 400mm (W x H x D) Max.
Supply, Erection Testing and Commissioning of zinc aluminium Coated CARBON STEEL WIRE MESH CABLE TRAYS of size 500 mm wide.for out door. and as per EN-ISO-9227 and should have tested for 850 Hrs salt spray test, with internal dimensions as specified. The Tray sizes, Area of the Tray and dia of the wire should be Equal or more than the specified. The Load bearing capacity of the Cable Trays should be equal or more than specified. The Cable trays to be manufactured with a longitudinal ‘T- welded’ safety edge along the top wire of the sidewall. All the Tray Jointings or Bends can be made by using side action bolt croppers( cutters), and fastened using 25mm and 30mm counter clamps with M6 nuts and bolts.Without Couplers, the installation will not be accepted. All surfaces are treated as the tray. The coupling must have the same surface finish as the tray. All the cable trays to be earthed by running a cable and fixed by 1 Grife Quip per every 15Mt Length of cable trays. The cutting of Cable Trays to be done by using COUPFILGM Cutter. The deflection characteristics of the tray must be tested in accordance with the European Standard IEC 61537. Fire test certification in accordance with the E30/E90 Standard Directives as per DIN 4102 - 12. Electrical continuity across a coupling must be demonstrated by means of published test methods and results as per IEC - 61537. (Description of the item continued on Ser item No 88.01)
(Description continued from Ser item No 89.00) A degree of EMI protection is demonstrated by means of published test methods and results. The cost of the materials should include the Trays, Couplers, Accessories for Bends and T's, Supporting arrangement at the span of 1.5meter and Erection as per Site Conditions. The cost of the materials should include the Trays, Couplers, Accessories for Bends and T's, Supporting arrangement at the span of 1.5meter and Erection as per Site Conditions, complete all as specified & directed.
Description all as per ser item No: 88.00 & 88.01 above but iron wire meshed cable tray of size 300 mm wide for indoor application complete all as specified & directed.
Surface excavation n.exc 30 cm deep and averaging 15cm deep and getting out soft / loose soil complete all as specified and directed.
Surface excavation Add or deduct from every 3 cm or part thereof above or below 15 cm average depth and getting out soft/ loose soil complete all as specified and directed.
M & L for PCC (1:4:8) type D-2 100mm thick using 40mm graded stone aggregatge as in sub base of floor all as specified and directed.
Dismantling of PCC interlocking paver block any shape and any size all as specified and directed.
M&L for Machine pressed precast concrete interlocking paver block any shape and size with grey cement and pigment confirming to IS 15658-2006 of 80 mm thickness M-40 Grade complete all as specified and directed.
M&L for sand filling under floors or in foundation including watering and consolidation complete all as specified and directed.
Refixing Machine pressed precast conctete interlocking paver block any shape and size with grey cement and pigment confirming to IS 15658-2006 of 80 mm thickness M-40 Grade complete all as specified and directed.
M & L 50 mm thick sand cushion vibrated with mechanical vibrator , including watering & consolidation, complete all as specified and directed.
M&L for PCC 1:2:4 Type B-1 (using 20mm stone crushed agg.) as in coping, rounded or chamfered on edges in any description complete all as specified directed.
M&L brick work 1:4 with sub class B bricks in cement morter complete all as specified directed.
M&L hand rails, half round or other steel section or core for wooden hand-rail straight portion,drilled and countersunk for balusters running bars, for nosing of pcc slab including embeding in concrete and screwing etc. wind ties for roof including securing bolts;
M&L, cement concrete 1:2:4 Type B2 (using 40 mm graded stone aggregate) in foundations, filling and mass concrete , complete all as specified directed.
M&L providing precast cement concrete 1:2:4 ,Type B1 (20mm graded stone aggregate) set in cement mortar 1:4 complete for cover slabs ( for man holes etc. of any section) , with plain fair faces, including chamfering, weatherings, throating etc., complete all as specified directed.
S&F Mild steel bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips, complete all as specified directed.
M&L rendering 15mm thick on fair faces of brick work or concrete surface, without using extra cement , complete all as specified directed.
Removal of excavated soil to a distance not exc 50 m and depositing where directed at a level not exc 1.5 mtr above the starting point , complete all as specified and directed.
M&L Cable joining kit for LT cable for outdoor termination heat shrink type joint complete with joining material and accessories suitable for 3.5 core XLPE armoured aluminum conductor cable of size 70 sqmm to 150 sqmm, complete all as specified and directed.
S & F Epoxy (Polymer) pin/post insulators of 33 KV voltage grade , complete all as specified and directed.
M&L for Loop type insulator, vitreous porcelain, white, brown or green, small size, with overall dimensions 65 x 90mm, clearance of hole 16mm, complete all as specified and directed.
RAVINDRA SALES
GUPTA ENGINEERING WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .