Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.1 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹34.9 L+₹2.6 L (7.97%)Rejected-Finance | L2 | Rejected-Finance not lowest | |
| 3 | L3₹37.8 L+₹5.4 L (16.8%)Rejected-Finance | L3 | Rejected-Finance not lowest | |
| 4 | L4₹38.4 L+₹6.0 L (18.7%)Rejected-Finance | L4 | Rejected-Finance not lowest | |
| 5 | L5₹38.7 L+₹6.4 L (19.8%)Rejected-Finance | L5 | Rejected-Finance not lowest |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
18 Jun 2021, 6:00 pmClosed
GE I R and D Kanchanbagh
GE I R and D Kanchanbagh Kanchanbagh Post Hyderabad 500058
OUTSOURCING SERVICES OF DG SETS AND REPAIR/MAINTENANCE OF GENERATORS AT ASL AREA AND CERTAIN MISC WORKS UNDER GE (I) RND KANCHANBAGH, HYDERABAD
2021_MES_445070_1
GE I KBAGH TOKEN 14 OF 2021 2022
Open Tender
Civil Works
Item Rate
330 days
Hyderabad
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE I R and D Kanchanbagh
₹98,000
Yes
26 Jun 2021
22 May 2021
21 Jun 2021
22 May 2021
18 Jun 2021
5 Jun 2021
22 May 2021 - 29 May 2021
Amount
Outsourcing of services for DG sets on all working days excluding Sundays and holidays in one shift from 0900 hrs to 1700hrs for 110 KVA DG Set at Bldg No. 13 & 300 KVA DG Set at RPD, complete all as directed. Man power: DG set operator (semi skilled) - 01 No
All as per srl item No. 1.00 here-in-before but for 180 KVA DG Set at Data Acquisition Bldg. Man power: DG set operator (semi skilled)-01 No.
All as per srl item No. 1.00 here-in-before but for 100 KVA DG Set at RCS integration Bldg. Man power: DG set operator (semi skilled)-01 No.
All as per srl item No. 1.00 here-in-before but for 300 KVA DG Set at 3 DCNC bldg. Man power: DG set operator (semi skilled)-01 No.
All as per srl item No. 1.00 here-in-before but for 750 KVA DG Set at Forge Shop. Man power: DG set operator (semi skilled)-01 No.
All as per srl item No. 1.00 here-in-before but for 160 KVA DG Set at FRPD. Man power: DG set operator (semi skilled)-01 No.
All as per srl item No. 1.00 here-in-before but for 40 KVA DG set at RCMA. Man power: DG set operator (semi skilled)-01 No.
All as per srl item No. 1.00 here-in-before but for 30 KVA DG set at MDD Bldg. Man power: DG set operator (semi skilled)-01 No.
All as per srl item No. 1.00 here-in-before but for 250 KVA DG Set at SPRITE area. Man power: DG set operator (semi skilled)-01 No.
All as per srl item No. 1.00 here-in-before but for 110 KVA DG Set at old Telephone Exchange. Man power: DG set operator (semi skilled)-01 No.
Note for Item No 01 :- (i) In case of requirement, tradesmen provided per one area may be utilized in other areas at the discretion of the department without any extra cost to department as directed by Engineer-in-Charge. (ii) Rate quoted is deemed to be included for leave reserve/off of the staff employed. (iii) The rate quoted shall be deemed to include the cost of uniform for tradesmen employed and the name of the contractor and the tradesman should be stitched on the front side of the shirt pocket. (iv) The rate quoted shall be deemed to including the Providing Log Books & Stationery for all above mentioned installations. (v) The necessary Tools & Plants shall be provided by the contractor. (vi) Group insurance, E.S.I & PF shall be provided to the operators by the contractor. Documents shall be submitted to the department. (vii) Wages to be paid to employee through individual bank account only and documents to be submitted to department. (viii) Minimum wages certificate along with attendance register and wage register shall be submitted for releasing of payment. (ix) Minimum wages to the employees to be paid as per the norm published by the Min of Labour (wages as declared in particular specification) and the same to be deemed to be included in the quoted rate.
(x) Each employee should be facilitated with adhoc bonus privilege as applicable in accordance with Govt Of India and the same to be deemed to be included in the quoted rate.(xi) In case of absence operator, double the rate quoted to be recovered. (xii) Departmental equipments of each building like fire fighting equipment, motors, pumps, Electric panels and its accessories copper brass materials etc., shall be under safe custody. In case of theft any item recovery shall be made from the contractor as per direction of Engr-in-Charge. (xii) All people employed are responsible for cleaning and maintenance including restricting vegetation growth in his equipment surrounding area, upkeep of installations. (xiv) The contractor will adhere to pay monthly payment cycle to the employees irrespective of RAR/Funds availability with department.
Disconnecting of all electrical connections from the unserviceable self starter of any make model, opening / dismantling of self starters suitable to the following capacity DG set for carrying out repairs, complete overhauling the system including replacing the unserviceable parts such as bearing, carbon brushes, clutch plates etc assembling and refixing the self starter in its original position and connecting up all connections & testing complete all as directed:- Note :- Rewinding of armature coil & field coil measured and paid separately under relevant items of Sch 'A'.
30 KVA DG set.
40 KVA DG set.
100 KVA DG set.
110 KVA DG set.
160 KVA DG set.
180 KVA DG set.
250 KVA DG set.
300 KVA DG set.
750 KVA DG set.
Disconnecting and dismantling the fuel pump assembly from its original position by opening of bolts and nuts, Renewing of Pump Repair Kit & fuel pipe, refixing the same after overhauling including calibration complete of following capacity DG sets and testing complete all as directed.
30 KVA DG set.
40 KVA DG set.
100 KVA DG set.
110 KVA DG set.
160 KVA DG set.
180 KVA DG set.
250 KVA DG set.
300 KVA DG set.
750 KVA DG set.
Supply only Engine Oil-20W/40 for DG set complete all as directed. Make :- SERVO SUPER/VOLVO LINE/CASTROL
Repairs of AMF Panel/DG set panel/control panel of 300 KVA to 750 KVA DG Set including checking of wiring circuit, locating/ removing fault including removing of all faulty Relays, Contactors, MCCBs, Wirings, Timer and other components as required and fixing the new switch gears/components and connecting all control wiring and testing to the entire satisfaction of Engr-in-Charge. Note : Spares like MCCBs, Relays, Contactors, MFMs will be measured and paid separately.
Supply only 8/11 pin Aux protector relays Make : OMRON, ABB
Supply only Industrial power contactors 415V, 50Hz, 3 pole, ACI rating, 100 Amps with NO + NC blocks confirming IS/IEC 60947-4-1
Supply only Industrial power contactors 415V, 50Hz, 3 pole, AC, 160 Amps with NO + NC blocks confirming IS/IEC 60947-4-1
Supply only Industrial power contactors 415V, 50Hz, 3 pole, AC, 250 Amps with NO + NC blocks confirming IS/IEC 60947-4-1
Supply only Industrial power contactors 415V, 50Hz, 3 pole, AC, 300 Amps with NO + NC blocks confirming IS/IEC 60947-4-1
Supply only Industrial power contactors 415V, 50Hz, 3 pole, AC, 400 Amps with NO + NC blocks confirming IS/IEC 60947-4-1
Supply onlyDIN type fuse links type HN of size 1 of rated current 200 Amps
Supply only DIN type fuse links type HN of size 1 of rated current 250 Amps
Supply only MCCB 100 Amps, 25 KA, 4 pole thermal magnetic release adjustable over load settings, Icu = 100%, Ics confirming IS/IEC 60947-2, including spreader links.
Supply only MCCB 160 Amps, 25 KA, 4 pole thermal magnetic release adjustable over load settings, Icu = 100%, Ics confirming IS/IEC 60947-2, including spreader links.
Supply only MCCB 200 Amps, 36 KA, 3 pole thermal magnetic release adjustable over load settings, Icu = 100%, Ics confirming IS/IEC 60947-2, including spreader links.
Supply only MCCB 250 Amps, 36 KA, 3 pole thermal magnetic release adjustable over load settings, Icu = 100%, Ics confirming IS/IEC 60947-2, including spreader links.
Supply only Multifunction nuts VAF + PF meters with class, accuracy with range 50-520 VAC, CT secondary 1/5Amps Make : L&T/Legrand/HPL
M&L for replacing spreader terminals 3 pole complete all as directed
M&L for replacing spreader terminals 4 pole complete all as directed
Supply & fix in repairs Auto Mains Failure (AMF) relay as per existing model and make of AMF panel of DG sets of any capacity complete all as directed
Supply & fixing in repairs crocodile clip for battery charger of required size all as specified and directed.
Taking down the defective turbo charger assembly duly disconnecting the mechanical connections from DG set, opening and thoroughly checking to carry out repairs complete to the turbo charger assembly and replacing the turbo charger kit and spares as required at site including any machining and reassembling and refixing the turbo charger assembly in its original position and reconnecting the same for the following capacity DG set including testing complete all as directed.
30 KVA DG set.
40 KVA DG set.
100 KVA DG set.
110 KVA DG set.
160 KVA DG set.
180 KVA DG set.
250 KVA DG set.
300 KVA DG set.
750 KVA DG set.
Draining out the fuel from the fuel tank of 110 KVA to 500 KVA DG sets and keeping it in separate container, disconnecting all the fuel lines and other mechanical connections and taking out the fuel tank for cleaning, cleaning fuel tank both internally and externally by removing all the accumulated dust/sediments, leak testing the tank and welding/brazing, and refixing the tank in its original position, replacing the drain plug and PVC pipe protected with flexible pipe, calibrating the fuel tank, refilling the drained out fuel back into the tank complete all as directed.
Taking down the radiator assembly by unscrewing all mechanical connections from the existing mounting, cleaning thoroughly the choked pipe of the radiator by using detergent like caustic soda, cotton waste etc. cleaning of all the deposited sediments in the pipes, soldering/brazing the leakage pipe, after completion of above works, including replacement of new clamps rubber hoses and AVM pads as required and refixing the same in its original position with suitable size of nuts, bolts and washers etc for the following capacity of DG sets complete all as directed.
30 KVA DG set.
40 KVA DG set.
100 KVA DG set.
110 KVA DG set.
160 KVA DG set.
180 KVA DG set.
250 KVA DG set.
300 KVA DG set.
750 KVA DG set.
Supply and filling Inhibitor corrosion (coolant additive concentrate) required for top up (TVS Make) complete all as directed.
Maintenance of DG sets and carrying out 'B' check and including cost of replacement of new 'B' check kit such as oil filter, by pass filter, fuel filter, Air filter, CR element and CR plates complete with 'O' rings and draining of Engine oil and filling up with the new engine oil and testing complete all as directed for the following capacities of DG sets of any type/make. Note:- (i) Engine oil shall be measured and paid separately under relevant item as supply only (ii) Labour element for filling of oil shall be included in the quoted rate
30 KVA DG set.
40 KVA DG set.
100 KVA DG set.
110 KVA DG set.
160 KVA DG set.
180 KVA DG set.
250 KVA DG set.
300 KVA DG set.
750 KVA DG set.
M&L for servicing of DG sets of capacity 110 KVA carryout inspection/checking of Radiator assembly for any leakages, Hose pipes, Self starter assembly,DG control panel, Alternator Ir values, FIP system functioning, Exhaust assembly, Ignition system, Battery charger and all general checks to asses the functioning of DG set etc at different locations :- Note : - (a) The cost of spares (material) shall be measured and paid separately under respective item of Sch Á'. (b) The rates quoted against the above mentioned Items is deemed to be included for cost of labour, cost of T & P required. Contractor is responsible to provide 24x7 call back service and repair facility through competent and well experience technician. No DG Set will be left unserviceable more than 4 hrs. If DG set found unserviceable for more than 04 hrs from the time it was reported to the contractor in writing during the term of this contract recovery of 1000/-Rs per such Non functional DG per day will be imposed and will be recovered from the amount due to the contractor. Regarding this the decision of GE will be final and binding. (c) All dismantled old unserviceable items, except those listed in schedule of credit, retrieved from any DG set shall be deposited to MES store yard.
All as per item No. 24 here-in-before but of capacity 300 KVA DG Set.
All as per item No. 24 here-in-before but of capacity 180 KVA DG Set.
All as per item No. 24 here-in-before but of capacity 100 KVA DG Set.
All as per item No. 24 here-in-before but of capacity 750 KVA DG Set.
All as per item No. 24 here-in-before but of capacity 160 KVA DG Set.
All as per item No. 24 here-in-before but of capacity 40 KVA DG Set.
All as per item No. 24 here-in-before but of capacity 30 KVA DG Set.
All as per item No. 24 here-in-before but of capacity 250 KVA DG Set.
Supply and fixing in repairs 12V 180 Ah maintenance free battery suitable for DG set of capacity 500 KVA complete all as directed.
Supply and fixing in repairs 12V 150 Ah maintenance free battery suitable for DG set of capacity upto 300 KVA complete all as directed.
Supply and fixing in replacement of radiator unit including bottom tray for the DG sets as per existing make and model for 110/160/180 KVA DG sets including initial topping up of coolant and all accessories complete all as directed.
All as per srl item No.35 here-in-before but of capacity 250/300/500 KVA DG set Make for srl item No.35 & 36 : Cummins/Kirloskar
Preparation of old painted surfaces of DG set of capacity 110 KVA, degreasing and spray painting the same with one coat of synthetic enamel paint including writing of SM/MES No complete all as directed.
All as per item No. 37 here-in-before but of capacity 180 KVA DG Set.
All as per item No. 37 here-in-before but of capacity 100 KVA DG Set.
All as per item No. 37 here-in-before but of capacity 160 KVA DG Set.
All as per item No. 37 here-in-before but of capacity 40 KVA DG Set.
All as per item No. 37 here-in-before but of capacity 30 KVA DG Set.
All as per item No. 37 here-in-before but of capacity 250 KVA DG Set.
Supply and fix heavy duty battery cable leads of copper conductor cable with copper lugs terminal for the 12 volts 180 Ah batteries.
Supply and fix Battery brass terminal and jelly complete all as directed.
Material and labour for Earthing complete with galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground vertically to a depth of not less than 2.25 mtrs below ground level with the top edge of earth plate at a depth of not less than 1.5 mtrs below normal ground level, connected to and including galvanised iron earth strip of size 32x6 mm with GI medium grade protection pipe of 40 mm dia for earth electrode upto test point or upto 7.5 mtr whichever is less, by means bolts, nuts, check nuts and washers of galvanised iron including necessary excavation earth work in any type of soil, PCC chamber (1:3:6) type C1 and RCC cover (1:2:4) type B1 of 40mm thick with 8mm dia TMT bars @ 100 c/c both ways, GI watering pipe 20 mm dia medium grade, wire mesh, funnel, lugs, charcoal, salt etc complete all as per electrical plate No. 3 or SSR Part-I complete all as directed.
EXELLENT POWER CORPORATION
ELEVATORS MAINTENANCE ENGINEER WORKS
M/s K L M INFRATECH
S.S.ENGINEERING CORPORATION
Maruthi international
M/s Kasturi Pedda Subbaiah Enterprises/M/s K.P.S Enterprises
vvcenterprises
DPS sales and services india
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .